Power Quality: A Closer Look Joe Watson APPA – Engineering & Operations Technical Conference April 18, 2005
One of the nations largest 4 service utility providers. ElectricityNatural Gas WaterWastewater 603,025 total customers for all combined services over 470 sq. miles. Electric = 194,369 customers 1,978 employees for all 4 utilities. Generate up to 77% of our own electricity (633 MW). More than 2900 miles of distribution lines (70% ug vs. 25% nation avg) More than 220 miles of transmission lines 19 Transmission Substations, 40 Distribution Substations …just a few facts
Springs Utilities’ Customers High Tech / R&D Intel, Atmel, Honeywell, Kaman Science, LSI Logic, Lockheed Martin, Mitsui, Quantum, Ramtron, UTMC Aeroflex, Vitesse Data/Call Centers HP, MCI, Oracle, FedEx, Progressive Insurance, T Rowe Price, Qwest Manufacturing Western Forge, Metso Minerals, Schlage Lock Military Installations NORAD, Fort Carson Army Base, Peterson Air Force Base, Air Force Academy
Springs Utilities’ PQ History BMI – 8010 PQ Nodes (1993) Portable Monitoring Metrosonic PA7, Metrosonic MR4, Dranetz 658, Dranetz-BMI Power Platform SquareD - Power Logic (1998) Power Measurement – ION (1999) Enterprise Software ION 7700 ION 8500
Where to Monitor Power Measurement - ION Monitors at every transmission substation (115kV or 230kV but not 34.5kV) 27 locations Monitors at customer sites Expand program to offer PQ monitoring service 3 locations Helps to troubleshoot Enhanced Service equipment such as Automatic Transfer and Static Transfer Switches
Communication Challenges How do we communicate with meters? RS232 RS485 Phone / Modem Spread Spectrum radios Internet
Communication Challenges How do we communicate with meters? RS232 RS485 Phone / Modem Spread Spectrum radios Internet
What to do with the system? Disturbance Paging Disturbance Database Fault Locating Waveform Analysis System Protection / Relaying Preventative Maintenance First Response
What to do with the system? Disturbance Paging Page includes time stamp, device, magnitude and duration of event Notify Enhanced Service Engineer on standby as well as other CS Utilities’ personnel. Provide proactive response to most important customers. Indicated a system-wide or isolated event.
What to do with the system? Disturbance Database First used an Excel database but soon switched to Access Data is qualified (ie. Was it really an event?) Compare event with “Outage Database” and “Event Messanger” The following data is logged: Date/Time Magnitude/Duration Which phases were affected Load affected Event path Cause category and description Event location (grid x-y) Protective Device which operated Outage report number
What to do with the system? Disturbance Database Hope to develop indices in order to help rank Capital and O&M projects Outage indexes: SAIFI - System Average Interruption Frequency Index (…how many outages in a year, interruptions/year) SAIDI - System Average Interruption Duration Index (…how many minutes in a year, minutes/year) CAIDI - Customer Average Interruption Duration Index (…how long each outage, minutes/interruption) RBM (Reliability Benchmarking Methodology) index: SARFI %V - System Average RMS Frequency Index Threshold (…how many sags/swells in a year, sags(or swells)/year at threshold level)
What to do with the system? Disturbance Database Ranking Substations 12RM6 2004 data 27 events Zero sags outside ITIC 34NP13 2004 data 56 events 4 sags outside ITIC
What to do with the system? Disturbance Database Ranking by category (all events below 90% nominal) Could also be ranked below 80%, 70%, etc.
What to do with the system? Fault Locating Use fault levels and phases to help troubleshoot
What to do with the system? Waveform Analysis Use fault levels and phases to help troubleshoot
What to do with the system? Waveform Analysis Use fault levels and phases to help troubleshoot Delta/Wye Single phase fault will appear as a phase to phase fault
What to do with the system? Waveform Analysis Use fault levels and phases to help troubleshoot
What to do with the system? System Protection and Relaying Use fault levels to determine if protection worked as designed. Delta/Wye
What to do with the system? Preventative Maintenance Calculating fault on breakers to determine when maintenance is required. Looking for trends or repetitive events.
What to do with the system? Preventative Maintenance
What to do with the system? Rapid Response Economic Development in Colorado Springs has group of individuals from different departments (Fire, Police, Utilities, etc.) to provide information to companies interested in locating in Colorado Springs. Many companies are interested in reliability data – outage AND power quality. Customer meetings Data is used to document events and discuss with customers.
2001 to Current Summary of Disturbances 1A A A&B - 82
2001 to Current Summary of Disturbances HV01A - 40 HV02A - 13 HV01 A&B Sag due to ATO transfer after event on feeder serving 1A. 2.Technician accidentally tripped ATO. 3.PT fuse failed in LS switchgear.
HV01A & HV02A Exposure (since May 2001) North Plant – 36 events 34NP2 – 13 Platte bus – 1 12PL PL2 - 7 34NP12 – 2 34NP 34NP20 – 13 13HL1 – 7 13HL2 - 2 34NP24 – 2 12C2 – 1 Rampart – 4 events 34RM2 – 1 34RM3 – 3 12RV4 – 2 12RV5 – 1 Oak Valley Craigmoor Platte Holland Park Rusina Digital Oak Valley Ind Prk Cust Sub North Plant Rampart