Who is Stellar Tech? Stellar Tech Energy Services is a wholly owned Canadian company Manufacturer of WellMax Datalogger / Controller Specializing in the integration and distribution of VFD’s and motors. Strengths in Pumping Systems Oil, Water, and Municipal
What we do! Oil & Gas production pumping Commercial Pumping Municipal Pump Controls Datalogging and Control Work in a Global Market
Our Capabilities Variable frequency drive (VFD) systems design and integrator. Over 15 years experience in drives and automation Thousands of successful installations Complete systems integrator with design, manufacturing, start-up and service capabilities
Our Products WellMax Datalogger Variable Frequency Drives Down hole Pressure / Temperature Recorders
Our Strengths All products are manufactured to the highest quality standards Knowledgeable customer service representatives and technical support groups Worldwide commitment to customers with sales and service facilities around the globe
WellMax Datalogger / Optimizer / Controller Designed and engineered for pumping applications to optimize production Can be used with VFD’s, Hydraulics or Across the line / Motor starter. Extensive options available Drive / motor control
WellMax Features Rod protection Well OPTIMIZATION Immediate data storage and retrieval Fluid level control Pump off Multiple communication features and protocols Trend analysis Screen for on-site data viewing
Well Conditions WellMax Data Logger and Controller
LEVEL AND RPM CONTROL Equimavenca – Capital Nacional Levantamiento Artificial / Servicio Integral Equimavenca – Capital Nacional Levantamiento Artificial / Servicio Integral
Pump Off – Complete Overview A–SPEED CHANGE B-PRESCO FAULT C-POWER BUMP D-PRESCO E-BROWN OUTS F-PUMPOFF SIGNS G-PUMPOFF OCCURS LEADING UP TO A PUMPOFF CONDITION
A - Speed Change
B - Presco Fault
C - Presco Fault
D - Power Bump
E – Power Brown Outs
F – Signs of Pump-off or Pump Damage
G – Pump-off occurs
Tubing Leak Torque fluctuations are caused by excess volume of gas Significant drop in torque displays tubing leak
Tubing Leak Significant drop in torque displays tubing leak
Tubing Hair line fracture The increase of RPM caused enough pressure to open up the hair line fracture in the tubing, flow decreased but never completely stopped
Sand Avalanche Pump slowly filling with sand Pump is full of sand
Pumped Off Well Pump Off Occurs 80 Ft Lbs 75 Ft Lbs
Waxing Condition
Parted Rods
WellMax Menu Structure
SUMMARY REPORT
NEMA 3R Panel
VERTICAL NEMA 1 Unwired 3 Contactor Bypass Package Showing Fused Disconnect Line Reactor Contactors O/L
IEEE 519 The total harmonic voltage distortion at any point of common coupling with a nominal voltage of less than 66kV shall not exceed 5%. Point of Common Coupling (PCC): That busbar electrically closest to any consumer through which any current must flow to that consumer and one or more other consumers.
Uncontrolled Rectifier Harmonics Line 1 Line 2 Line 3 LOAD D1 D2D3 D4 D5D6 Current in D1 Current D1 & D5 Current D1 & D6
Square Wave Harmonics Content Square wave & Fundamental + 3rd
Types of Harmonic Filters A VFD with no input reactor or filter may result in 100% THID or more, measured at the VFD input terminals A 3%Z line reactor will limit THID to 35~ 40% A 5%Z line reactor will limit THID to 30 ~ 35% A 5%Z line reactor & 3%equivalent Z DC reactor will limit THID to 25~30% Tuned 5 th harmonic trap will limit THID to 20 ~ 25% 12 pulse phase shifting will reduce THID to a minimum of full load 18 pulse phase shifting will reduce THID to a minimum of full load Matrix wide spectrum filter limits THID to 8% or 5% at full load
Input Current – Enhanced 5 th Harmonic Trap (w/VFD input reactor) Load: 100% Input Voltage: balanced Line Impedance: 0.25% Input Reactor: 5% Output Reactor: 1.5% Input Current THID: 23.07%
THID Performance 8% Filter
12 Pulse w/ 1% & 3% Line voltage unbalance Matrix w 1% & 3% Line voltage unbalance Matrix Filters perform better than 12-pulse under Real Life operating conditions (unbalanced line voltages, 0% to 100% loading)
6-pulse VFD with 5% Matrix Filter performs better than 18-pulse drive under normal operating conditions (0% to 100% load, voltage unbalance)
Voltage Unbalance….. ANSI Standard C Reports: 98% of power systems are within 1 - 3% 66% of power systems are within 0 - 1% –all at the point of common coupling Load unbalance within the building power distribution system adds to the utility unbalance at the point of utilization.
Reducing Harmonics Ensure a low network Impedance Distribute harmonic generating loads Use AC line or DC link reactors Install Harmonic filters
IEEE – 519 Solutions Desired % THID at PCC (IEEE- 519) 3% Line Reactor 5% line Reactor 5% Line + 3% DC Reactors 8% Matrix Filter (M8) 5% Matrix Filter (M5) % Maximum VFD Load if all VFD’s use same Harmonic Mitigation Method
Motor Inverter Compatibility Topics Reflected Wave Theory Waveform Analysis with output reactors & filters Long Motor Leads Drive Solutions Motor Solutions
Reflected Wave Theory Mismatch between surge impedance of: Drive-to-motor cable & Motor winding Cable surge impedance fairly constant through hp range Motor surge impedance inversely proportional to hp 2 per unit voltage evident on motors up to 500 hp Motor terminal voltage doubling on leads over 15 feet
Full Voltage, 60 Hz PWM Waveform Half Voltage, 30 Hz PWM Waveform PWM Waveform
VFD Output & Motor Terminal Voltage, Reflected Waves
IGBT VFD, Motor Terminal Peak Voltage & Rise Time Characteristics Peak voltage = twice DC Bus voltage at critical cable length and longer. DC bus voltage = AC input voltage * e.g. 600 VAC * = 850 * 2 =1,700 V Peak. Rise time = 0.015uS to 1uS Depending on IGBT Current Rating Critical cable length = speed of propagation * rise time. e.g. 150meters/uS * 0.03uS = 4.5 meters
IGBT VFD, Motor Terminal Voltage, 10 HP, 460 Volt, 6 KHz Carrier Frequency, 60 Hz Output Frequency, No Load Reactor, 10 Feet of Cable, Peak Voltage 1,200 Volts, Rise Time.03uS
IGBT VFD, Motor Terminal Voltage, 10 HP, 460 Volt, 6 KHz Carrier Frequency, 60 Hz, 3%Z Load Reactor, 10 Feet of Cable, Peak Voltage 820 Volts, Rise Time 2uS
IGBT VFD, Motor Terminal Voltage, 10 HP, 460 Volt, 6 KHz Carrier Frequency, 60 Hz Output Frequency, Sine Wave Output Filter, 10 Feet of Cable, RMS Voltage 460 VAC, No Spikes
IGBT VFD, Motor Terminal Voltage, 10 HP, 460 Volt, 6 KHz Carrier Frequency, 60 Hz Output Frequency, No Load Reactor, 250 Feet of Cable, Peak Voltage 1380, Rise Time.05uS
IGBT VFD, Motor Terminal Voltage, 10 HP, 460 Volt, 6 KHz Carrier Frequency, 60 Hz Output Frequency, 3%Z Load Reactor, 250 Feet of Cable, Peak Voltage 1,000 Volts, Rise Time 10uS
IGBT VFD, Motor Terminal Voltage, 10 HP, 460 Volt, 6 KHz Carrier Frequency, 60 Hz Output Frequency, Sine Wave Output Filter, 250 Feet of Cable, RMS Voltage 460 VAC, No Spike
Long Cables From critical cable length and longer, motor terminal voltage remains at 2 per unit Time spent at 2 per unit voltage increases with cable length therefore transient energy level much higher Insulation stress much higher proportional to transient energy*carrier frequency
NEMA Minimum Design Standards For 3 Phase Induction Motors MG1 part 30 As a minimum motor insulation must withstand 1000 volt 2uS rise time MG1 part 31 As a minimum motor insulation must withstand 1600 volt 0.1uS rise time
VFD Solutions For NEMA MG1 part 30 Motors No output reactor or filter required for 208/240Volt applications Use output reactor for 460 volt applications Use output dv/dt filters for 575 volt applications Keep motor leads short Keep carrier frequency low Keep motor cool
Motor Solutions For NEMA MG1 part 31 Motors No output reactor or filter required for 208/240 volt applications No reactor or output filter required for 460 volt applications unless cable length is extreme Use output reactor for 575 volt applications
END OF PRESENTATION THANK YOU