EMC in Electrical Power Systems Frithiof Jensen Power System Engineer www.europeanspallationsource.se November 12, 2013.

Slides:



Advertisements
Similar presentations
Shunt Capacitor Switching For Power Factor Improvement Clayton H Reid.
Advertisements

SWITCH-MODE POWER SUPPLIES AND SYSTEMS Silesian University of Technology Faculty of Automatic Control, Electronics and Computer Sciences Ryszard Siurek.
POWER QUALITY BACKGROUND & ELEC-SAVER TVSS
POWER FACTOR IN ELECTRICAL ENERGY MANAGEMENT
Copyright© Voltimum Experts – not to be reproduced without prior consent of Voltimum UK Voltimum Expert Topic – Power Harmonics.
1 POWER QUALITY -- Bhanu Bhushan -- June, How close is the supply voltage waveform to sinusoidal, and how close are the supply voltage and frequency.
Mike Thornton National Sales Manager
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
QUALITY AND TECHNOLOGY
Siemens Building Technologies Building Technologies Variable Frequency Drives Harmonics Overview.
Chapter 12 Three Phase Circuits
Power Quality during the late 90’s  PQ was dominated by Fluke and LEM  Power Utilities has just started talking about standards to be followed  National.
VARIABLE SPEED DRIVES HARMONIC EFFECTS & EFFECT OF USE WITH LONG CABLES (100 – 300m) Electric Motors & Drives ….OUR VISION, YOUR SOLUTION ……. TOGETHER.
© Copyright 2008 ABB. All rights reserved /29/2008 Results-Driven Roadshow Cincinnati, 2008 Common Cures for Harmonics Larry Stanley RSE,Nashville,TN.
LP33 Series UPS kVA 400Vac/CE
Designing a EMC Compatible Electronic Meter using AD7755 a.
Introduction to ElectroFlow TM System Dhaka, March 8, 2003 Mahmuduzzaman Khan Green Power Canada.
Dry type transformers Zaragoza Traction application
Today’s Topics 1- The per unit system 2-Transformer Voltage Regulation
Power Engineering Society Chicago Chapter Reactive Power: Sources and Solutions 12 February 2003 David E. Mertz, PE Burns & McDonnell Engineers, Inc.
SHUNT CAPACITOR FUNDAMENTALS AND PROTECTION
POWER SUPPILES LECTURE 20.
PRODUCTS TRANSFORMERS ENERGY SAVING TRANSFORMERS (EST) TRANSFORMER RECTIFIER UNITS 3 rd HARMONIC REJECTION TRANSFORMERS (HRT) ULTRA HIGH ISOLATION TRANSFORMERS.
Dry type transformers Zaragoza Drives application
Disconnect Switches There are many purposes for disconnect switches in substations and power lines. They are used to isolate or deenergize equipment for.
Unit 29 Three-Phase Transformers. Objectives: Discuss the construction of three-phase transformers. Discuss the formation of a three-phase transformer.
ESS | Power System | | Frithiof Jensen ESS Power System Ion Source, Front-end.
/1 Testing Harmonics and Flicker /1 Harmonics & Flicker Two different test standards: EN & EN EN controls.
F. Ferrandis_SP_ALPHA 2_BLOCK 2_Paper 35_Presentation Barcelona May POWER FACTOR CORRECTION WITHIN INDUSTRIAL SITES EXPERIENCES REGARDING.
Power Distribution Harmonics Case Study of 285-3F Chiller Plant Michael W. Harmon Principle Engineer Savannah River Nuclear Solutions, LLC Savannah River.
POWER FACTOR CORRECTION
2. Terms and definitions1 # Terms and Definitions # Voltage Sags and Interruptions.
Electrical Installation 2
Applied Harmonics Control of Harmonics
1 Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro Organized by Task Force on Harmonics Modeling & Simulation.
Electrical Distribution Training
POWER SYSTEM PROTECTION
Electrical Distribution Systems
POWER QUALITY.
Voltimum Expert Topic – Power Harmonics. What are Harmonics? They are waveforms with frequencies that are multiples of the fundamental frequency (Typically.
IEEE PES General Meeting, Tampa FL June 24-28, Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro.
1 POWER QUALITY -- Bhanu Bhushan -- April, Simple examples around us : Ceiling fan regulators Tube lights Lap-tops & peripherals Domestic inverters.
Instrumentation & Power Electronics
Electromagnetic Compatibility Test for CMS Experiment. Authors C. Rivetta– Fermilab F. Arteche, F. Szoncso, - CERN.
Understanding Power Quality Monitoring
1 Power Quality EKT 451 CHAPTER 8. 2 Introduction Utilities transmit electricity over power lines into home as an alternating current (AC) wave. This.
Prof R T KennedyEMC & COMPLIANCE ENGINEERING 1 EET 422 EMC & COMPLIANCE ENGINEERING.
Introduction  Utilities transmit electricity over power lines into home as an alternating current (AC) wave.  This is how power travels through wiring.
Power Quality Karsten KAHLE Electric Power Converter Group (TE-EPC) High Power Converter Section Review of CERN’s Electrical Power Network October.
A common 400 Hz AC Power Supply Distribution System for CMS FEE. Authors C. Rivetta– Fermilab. F. Arteche, F. Szoncso, - CERN.
Uninterruptible Power Supply Improves Reliability at The Australian Synchrotron Sean Murphy – ARW 2013 Melbourne.
SMJE 2103 Power Quality, Reliability and Availability.
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
Asea Brown Boveri Jumet S.A. FD 1/30 ASEA BROWN BOVERI Harmonic Problem ? Are Tuned Filters THE Solution ?
J.PRAKASH.  The term power quality means different things to different people.  Power quality is the interaction of electronic equipment within the.
Power Quality Issues Power Electronics Group.
Power Quality Any power problem manifested in voltage, current or frequency deviation that results in failure or misoperation of customer equipment. IEEE.
1 March 2001 EPCOS FK PM PFC Basics of Power Factor Correction BASICS OF POWER FACTOR CORRECTION.
POWER FACTOR CORRECTION
Effects of Harmonics on Capacitors Electrical System
Introduction to Global AC Power
HARMONIC MITIGATION USING PASSIVE FILTERS
MEDIUM VOLTAGE APPLICATIONS.
Chapter 2 Power Electronic Devices
EET 422 EMC & COMPLIANCE ENGINEERING
Fundamentals of Harmonics
WELCOME TO ALL.
Presentation on “Power Quality” Mr. P B Tupe.
Agenda Introduction of Protective Relays
Presentation transcript:

EMC in Electrical Power Systems Frithiof Jensen Power System Engineer November 12, 2013

EMC-Directive The EU EMC Directive 89/336/EEG mandates control of EMC in electrical equipment The EMC Directive specifies two essential requirements: – The device must not interfere with radio or telecommunications equipment operation and must not perturb the environment (Emission). – The device itself must be immune from electromagnetic disturbance due to itself or other equipment (Immunity). From 20 july 2007, the EMC Directive also applies to equipment that is not intended to be sold in the market and is not CE-marked, f.ex. fixed installations and specialised industrial plants and equipment as used within the ESS. 2

EMC-directive (cntd.) Supply voltages – Electrical supply limits are given in SS-EN ”Voltage characteristics of electrity supplied by public electricity networks” EMC – limits for emission and susceptibility – SS-EN – specifies tolerance levels for conducted disturbances in low voltage distribution systems – SS-EN – defines electrical environment and tolerance levels for industrial- and private- distribution systems – SS-EN defines electrical environment and tolerance levels medium voltage distribution systems – Many, many & Many product-specific standards in the family! 3

Electrical system 4 G1 Z1Z1 Z2Z3 z4 L1 L2 SS-EN SS-EN SS-EN SS-EN 61xxx-y-z LEKAB - ESS CF - TS

Flicker What is it? – Flicker is the name for rapid, repetitive voltage changes in electrical networks – The severity depends on magnitude and frequency; at the 14 Hz operating frequency of the LINAC, the acceptable voltage change is 0.3% What causes flicker? – Flicker is caused by load variations; for example arc welding, electrical smelters and klystron modulators Effect of flicker – Mainly visual, the lights are “blinking”. Severe Flicker can confuse the power factor correction logic in switch mode power supplies Prevention of flicker – Increase the short-circuit power of the network – Reduce load power variations so that the flicker level is below the threshold 5

Overtones/Harmonics What is it? – Overtones are frequencies higher than the 50 Hz power line frequency superimposed onto the phase voltage or current What causes overtones? – Overtones are caused by non-linear loads, imbalanced three-phase loads (due to saturation) and power electronic equipment Effect of overtones – Increased power losses in cables, motors and distribution transformers – Third harmonics add up in the Neutral conductor and cause overheating – Harmonics may cause migrating currents due to impedance issues – False triggering of phase controllers and power factor correction logic – Can cause compensation capacitors to overheat Prevention of overtones – Use Power Factor Correction and EMC filtering on power electronics (this is the already the standard for CE-marked- and also most industrial equipment) – Use 12- or 24- pulse rectifiers for large loads – Increase the area of Neutral and Earth connectors 6

Voltage imbalance What is it? – The phase voltages on the same 3-phase system are different What causes voltage imbalance? – Voltage imbalance is caused by different impedances in the electrical distribution system and/or unbalanced loads Effect of voltage imbalance – Torque variation in 3-phase motors and high currents in the neutral conductor – the phases no longer add up to zero. – Overloading of branches in 3-phase power electronics – Disturbance of SCR-triggering in rectifiers – Saturation of distribution transformers, generating harmonics and losses Prevention of voltage imbalances – Distribute loads evenly between phases 7

Transients What is it? – Transients are rapid voltage changes on the phase voltages What causes transients? – Lightning or rapid load variations can cause transients, especially inductive loads Effect of transients – Transients can damage equipment by exceeding the voltage rating of components and insulation Prevention of transients – Control the operation of equipment, f.ex. capacitor banks and large motors – Use transient voltage limiters at sensitive equipment and at the input port of the distribution system. 8

Voltage Dips What is it? – A random drop in phase voltage below 10% of nominal value for a duration between 10 ms – 90 seconds. One or more phases may be affected. What causes dips? – Dips are generated by lightening protection activation and switching operations in the electrical network Effect of voltage dips – Dips up to 150 ms can usually be absorbed by small PFC-type power supplies – Larger ( > 5 kW) power supplies will normally trip because of load imbalance e.t.c. Prevention of voltage dips – Voltage dips cannot be prevented. Instead equipment must be designed to tolerate them, for example: – Specify/Confirm adequate hold-up time for small power supplies – Specify adequate hold-up time for large equipment – Balance the cost of immunity with the frequency and severity of the disturbances – NOTE: The electrical supplier is not required to measure or care about dips shorter than 150 ms 9

What to expect? Nominal voltage400, 690 or 6600 V – Maximum voltage variations+/- 10 % – Typical voltage variations+/- 5 % – Backup power + 10 % / -15 % – Random step changes of 1.5% (increase and decrease) of the supply voltage may occur due to operation of the tap-changers of the main transformers. Nominal frequency50 Hz, +/- 1 % – Maximum variations50 Hz, +4 % / −6 % – Backup power50 Hz ± 15 % Total Harmonic Distortion, THD – Maximum value8 %, 40’th overtone inclusive – Typical value 2 % – Voltage unbalance < 2 % 10