Tests to Verify Low Strength Concrete ACI Georgia Chapter Virgil D. Skipper Seminar June 2009 Robert Jenkins, P. E.

Slides:



Advertisements
Similar presentations
WORKSHOP on In-Situ Compressive Strength of Concrete Structure by Sigma Test & Research Centre Delhi.
Advertisements

Concrete Construction Part 1
Outline CH1.Introduction CH2.Preliminary Design CH3.3D Model.
Chp12- Footings.
Design of Slabs-on-Grade
Subfloor Evaluation Prior to Installation Understanding the science of concrete slabs prior to installation of moisture sensitive floor covering materials.
Lecture 9 - Flexure June 20, 2003 CVEN 444.
1 Class #25.1 Civil Engineering Materials – CIVE 2110 Definitions Material Properties Concrete Compressive Strength, f’ c Fall 2010 Dr. Gupta Dr. Pickett.
Commercial Framing C D Prints Unit 13.
JAB Plastic Products Corp. Technical Information.
Overview Waffle Slab.
CONCRETE TESTING Dr. Sophia Hassiotis.
Reinforced Concrete Design
Reinforced Concrete Flexural Members
Shear and Diagonal Tension
1 Design and drawing of RC Structures CV61 Dr. G.S.Suresh Civil Engineering Department The National Institute of Engineering Mysore Mob:
Chapter-7 Bond Development Length & Splices
ONE-WAY SLAB. ONE-WAY SLAB Introduction A slab is structural element whose thickness is small compared to its own length and width. Slabs are usually.
تم تحميل الملف من
Masonry. Terms –F > 15-5 –Go thru all figures –Joints between brick = ¼ inch.
WORKSHEET 4 CONCRETE. Q1 a) what are the two main properties that concrete must have? (i) strength b) how do we achieve them? by using an acceptable water.
Chapter 33 Foundation Systems.
Assessment of Existing Structures in the Absence of Drawings
1 NDT OF CONCRETE. 2 CUBE TEST INDICATES ONLY POTENTIAL STRENGTH INDICATES ONLY POTENTIAL STRENGTH SUBJECT TO UNINTENTIONAL DEVIATIONS SUBJECT TO UNINTENTIONAL.
The Good, the Bad, and the Ugly 2 May 2008 Sacramento, CA Alan Macnab
Concrete Quality Assurance: How Concrete is Specified and Supplied To Meet Construction Specifications Prepared By: Prof. Marcia C. Belcher Construction.
Introduction: Standard Test Method for Density (unit weight), Yield, and Air Content (Gravimetric) of Concrete –Apparatus –Sample –Procedure ACI Certification.
Slab Design.
Quality Control Testing
1 Class #26 Civil Engineering Materials – CIVE 2110 Concrete Material Concrete Compressive Strength, f’ c Cracking Aging, Maturity Fall 2010 Dr. Gupta.
Topic : MIX DESIGN OF CONCRETE Properties of concrete Submitted To: DR. AYUB ELAHI Submitted By: SOHAIB NASEER 2K9-scet-29/CIVIL M.ZAEEM FAKHAR 2K9-scet-03/CIVIL.
CRACK CONTROL IN CONCRETE MASONRY WALLS
Placing Quality Concrete
COLUMNS. COLUMNS Introduction According to ACI Code 2.1, a structural element with a ratio of height-to least lateral dimension exceeding three used.
Chapter 2b Foundations Shallow & Deep Foundations.
Lecture on CE 4014 Design of Concrete Structures
SHEAR IN BEAMS. SHEAR IN BEAMS Introduction Loads applied to beams produce bending moments, shearing forces, as shown, and in some cases torques. Beams.
Chapter 12 Concrete Construction Part 3 1CE 417, King Saud University.
Plain & Reinforced Concrete-1 CE-313
Roof Terms Span –Distance across the building. Roof Terms Run –1/2 the distance across the building (1/2 span distance)
Reinforced Concrete Design
1.
The Cathedral of Our Lady of the Angels. Los Angeles, California Rafael Moneo.
FOOTINGS. FOOTINGS Introduction Footings are structural elements that transmit column or wall loads to the underlying soil below the structure. Footings.
Final Thesis Presentation Washingtonian Center Lee ResslerApril 15, 2008 Faculty Advisor: Dr. Memari.
Sampling and Testing Concrete Mixes MATERIAL TESTING LABORATORY
Objective Distinguish between site preparation, placing, finishing, and curing.
Roof Terms Span –Distance across the building. Roof Terms Run –1/2 the distance across the building (1/2 span distance)
Shear Stresses in Concrete Beams
Concrete Field Sampling
Control Tests for Concrete Ch. 16. Project Specifications Characteristics of the mixture Maximum size aggregate Minimum cement content Characteristics.
Reinforcement Information - Code
Practical Design of PT Buildings
Concrete Inspection Construction Inspection for Field Office Activities.
SANKALCHAND PATEL COLLEGE OF ENGINEERING,
Concrete Repair presented by: Amirhossein Jodeiri Mapua Institute Of Tecnology.
Demonstrate Concrete Skills Form A wood or metal structure that confines concrete to the desired shape until it hardens.
CVL 2407 Faculty of Applied Engineering and Urban Planning Civil Engineering Department 2 nd Semester 2013/2014 Dr. Eng. Mustafa Maher Al-tayeb.
PRESSURE VESSEL. 1.Determine the bursting steam pressure of a steel shell with diameter of 10 inches and made of ¼ in thick steel plate. The joint efficiency.
Dr. Younis M. ALSHKANE and Dr. Serwan Kh. RAFIQ
Concrete Repair.
“Condition Assessment of Concrete with Non Destructive Testing (NDT)”
Plain & Reinforced Concrete-1 CE3601
G.GUNA….SRVEC DEPARTMENT OF CIVIL ENGINEERING
Lecture - Design of Columns
Lecture 39 - Design of Two-Way Floor Slab System
UTILITY VAULTS: THE PRECAST ADVANTAGE
Reinforced Concrete Design-I Design of Axial members
2018 Revisions to NYCDOB Code
Concrete A structural material made by combining cement, sand, aggregate, and water.
Presentation transcript:

Tests to Verify Low Strength Concrete ACI Georgia Chapter Virgil D. Skipper Seminar June 2009 Robert Jenkins, P. E.

Available Testing Procedures Cores Cores Nondestructive Evaluation Nondestructive Evaluation Load Tests Load Tests

Core Strength Tests Core Strength Tests SPECIFICATIONS FOR STRUCTURAL CONCRETE ACI a Where required by the Architect/Engineer, obtain cores in accordance with ASTM C 42/C42 M Core tests—Strength level of concrete in the area represented by core tests will be considered adequate when the average compressive strength of the cores is equal to at least 85% of fc′, and if no single core is less than 75% of the specified compressive strength fc′.

Nondestructive Evaluation Unanticipated testing of hardened concrete Unanticipated testing of hardened concrete Rebound Hammer ASTM C805Rebound Hammer ASTM C805 Penetrating Probe ASTM C803Penetrating Probe ASTM C803 Ultrasonic Wave VelocityUltrasonic Wave Velocity Through transmission testing ASTM C597 Through transmission testing ASTM C597 Impact Echo testing ASTM C1383 Impact Echo testing ASTM C1383 Pullout Test ASTM C900Pullout Test ASTM C900

Nondestructive Tests SPECIFICATIONS FOR STRUCTURAL CONCRETE ACI Nondestructive tests—Test results will be evaluated by the Architect/Engineer and will be valid only if tests have been conducted using properly calibrated equipment in accordance with recognized standard procedures and an acceptable correlation between test results and concrete compressive strength has been established and is submitted. * * * Nondestructive tests—Nondestructive tests shall not be used as the sole basis for accepting or rejecting concrete, but may be used, when permitted, to evaluate concrete where standard molded and cured cylinders have yielded results not meeting the criteria in

Load Test Evaluation ACI — If the effect of the strength deficiency is not well understood or if it is not feasible to establish the required dimensions and material properties by measurement, a load test shall be required if the structure is to remain in service.

Available Nondestructive Test Methods Rebound Hammer ASTM C805Rebound Hammer ASTM C805 Penetrating Probe ASTM C803Penetrating Probe ASTM C803 Ultrasonic Wave VelocityUltrasonic Wave Velocity Through transmission testing ASTM C597 Through transmission testing ASTM C597 Impact Echo testing ASTM C1383 Impact Echo testing ASTM C1383 Pullout Test ASTM C900Pullout Test ASTM C900

Rebound Hammer ASTM C805

Rebound Number Correlations

Penetrating Probe ASTM C803

Penetrating Probe Correlations

Ultrasonic Wave Evaluation

Ultrasonic Pulse Velocity ASTMC597

Ultrasonic Pulse Velocity Correlation

Impact - Echo Testing ASTM C1383 T=C p /2*f C p =T*2*f

Pullout Test ASTMC900

Pullout Test - CAPO

Pullout Test cracking patterns

Pullout Test – CAPO correlation

In-Place Methods to Estimate Concrete Strength ACI Report ACI Report Review of Test MethodsReview of Test Methods Statistical Characteristics of Test ResultsStatistical Characteristics of Test Results Development of Strength RelationshipDevelopment of Strength Relationship Implementation of In-Place TestingImplementation of In-Place Testing Interpretation and Reporting of ResultsInterpretation and Reporting of Results In-Place Tests for Acceptance of ConcreteIn-Place Tests for Acceptance of Concrete

Construction Project Scenario  High Rise Construction – Office Tower  Concrete Placement  Columns – days 60 yards  Floor slab – days 240 yards

Cylinder Test Reports  7 day strengths  Set 1 (slab) psi  Set 2 (slab) psi  Set 3 (slab) – 2865 psi  Set 4 (column) – 3580 psi

Ultrasonic Testing at 12 days age Columns Top11500 fps Middle12000 fps Bottom12500 fps Slabs12000 fps

Validity of Ultrasonic Wave Velocity  Water content of concrete can have an effect on the wave velocity.  At higher strengths the spread of wave velocity verses compressive strength is less.  The tests of vertical elements must consider the top to bottom effect.  Ultrasonic wave tests are affected by discontinuities in the concrete.

Validity of Ultrasonic Wave Velocity  Water content of concrete can have an effect on the wave velocity.  At higher strengths the spread of wave velocity verses compressive strength is less.  The tests of vertical elements must consider the top to bottom effect.  Ultrasonic wave tests are affected by discontinuities in the concrete.

Ultrasonic Pulse Velocity

Validity of Ultrasonic Wave Velocity  Water content of concrete can have an effect on the wave velocity.  At higher strengths the spread of wave velocity verses compressive strength is less.  The tests of vertical elements must consider the top to bottom effect.  Ultrasonic wave tests are affected by discontinuities in the concrete.

Ultrasonic Pulse Velocity Top to Bottom Effect When concrete is placed in a tall vertical placement such as a column or a wall; there is a difference in the concrete strengths from top to bottom with greater strengths at the bottom of the placement.

Validity of Ultrasonic Wave Velocity  Water content of concrete can have an effect on the wave velocity.  At higher strengths the spread of wave velocity verses compressive strength is less.  The tests of vertical elements must consider the top to bottom effect.  Ultrasonic wave tests are affected by discontinuities in the concrete.

Travel time of wave through concrete

Cylinder Test Reports  7 day strengths  Set 1 (slab) psi  Set 2 (slab) psi  Set 3 (slab) – 2865 psi  Set 4 (column) – 3580 psi  28 day strengths  Set 1 (slab) – 4120 psi  Set 2 (slab) – 4280 psi  Set 3 (slab) – 3820 psi  Set 4 (column) – 4480 psi

Rebound Hammer at 35 days age Columns Average Rn = 29 Range Rn 26 to 35 Slabs Average Rn = 26 Range Rn 20 to 31

Validity of Rebound Testing  Testing the hardness (stiffness) of the concrete surface and shallow depth into concrete.  Affected by:  Form material and type and smoothness  Aggregates, closeness to surface  Reinforcing steel, closeness to surface  Moisture content  Surface finish  Hammer orientation

Rebound Number Correlations

Variation of Rebound Numbers

Cylinder Test Reports  28 day strengths  Set 1 (slab) – 4120 psi  Set 2 (slab) – 4280 psi  Set 3 (slab) – 3820 psi  Set 4 (column) – 4480 psi  56 day strengths     Set 4 (column) – 4930 psi

Coring - PROBLEMS Where to core? Where to core? Columns have No. 8 vertical reinforcing bars at 3 inches on center. Clear distance between bars is 2 inches. Columns have No. 8 vertical reinforcing bars at 3 inches on center. Clear distance between bars is 2 inches. ASTM C42 – cores for load bearing elements minimum 3.70 inch diameter. ASTM C42 – cores for load bearing elements minimum 3.70 inch diameter. Core between bars yields 1.75 inch diameter – less than 2 times nominal maximum aggregate size Core between bars yields 1.75 inch diameter – less than 2 times nominal maximum aggregate size

WHAT TO DO???

Other Nondestructive Tests Penetration Probe Penetration Probe Interference from rebarInterference from rebar Pullout Test – CAPO Pullout Test – CAPOProblems Number of tests required and correlation to concrete strength. Number of tests required and correlation to concrete strength.

Load Tests How do you load test a column? Or 15 columns?

Load Tests of Concrete Usual area load of slab Usual area load of slab Pattern loading of slabs and beams Pattern loading of slabs and beams Concentrated loading of beam haunch Concentrated loading of beam haunch Special jacks and tension rods for punching shear around column. Special jacks and tension rods for punching shear around column. Cyclic load testing using closed loop controllers and hydraulic jacks. Cyclic load testing using closed loop controllers and hydraulic jacks.

Discussion of load tests Strength Evaluation of Existing Concrete Buildings ACI Report 437R-03

Redo ultrasonic tests – concrete has dried sufficiently. Take small diameter cores where lower wave velocities are noted. Engineers determine that 5000 psi is sufficient strength for these columns.

Questions