Managing Director, HVPD Ltd

Slides:



Advertisements
Similar presentations
An Introduction to On-line Partial Discharge Surveys
Advertisements

Mitigation of AC Induced Voltage On Buried Metallic Pipelines
Condition Monitoring Of High Voltage Machines By The Analysis of
Electrical Infrastructure Design Considerations David Flood Head of Electrical Systems, Forewind Stakeholder Workshops, April 2010.
Econnect Ltd Independent specialists in the grid integration of renewable energy...
WP3 High Availability Drives Electrical Machines and Drives Research Group University of Sheffield Dr. Georges El Murr
Terry Chandler Power Quality Thailand LTD PQsynergy 2011 Chiang Mai, Thailand Sept 2011WWW.powerquality.co.th1.
HVPD Test Experience of On-line PD Testing on Offshore Wind Farms
Rampion Offshore Wind Farm Onshore Construction Elements.
OFFSHORE RENEWABLE PLANT HVDC POWER COLLECTOR AND DISTRIBUTOR
Presented by Malcolm Seltzer-Grant, HVPD Ltd
Grid Connections: Now and the Future Patrick Smart Head of Commercial and Regulatory 10 th November 2010.
Model-based V-I systems: - using your existing electric motors to tell you about your driven equipment’s condition Geoff Walker, Director, Artesis LLP.
Network Management on the Isles of Scilly Ben Godfrey Western Power Distribution Innovation and Low Carbon Networks Engineer /
Brief on HVDC 2015 Brief on HVDC 2015
SLIM® and Bio-SLIM® The “Life starts at 36”-project:
Some electrical connection design issues for offshore wind farms Paul Gardner, Helen Snodin, & Nigel Scott Garrad Hassan and Partners
The Wider Offshore Industry - Introduction. Why Renewables? Mb/doe Gas Nuclear Oil Renewables Coal Incremental.
Partial discharge analysis of defective three-phase cables An overview of an ongoing project involving the generation and analysis of PD within distribution.
© ABB-EWEC 2006 ATHENS /03/06 EWEC 2006 Athens The Challenges of Offshore Power System Construction Peter Jones Lars Stendius ABB.
By Lauren Felton. The electric grid delivers electricity from points of generation to consumers, and the electricity delivery network functions via two.
1 Fault Assistance Centre David Talbot & Chris Armstrong September 2014.
1111Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS Challenges for Reliable Offshore Transformers Dr. Jan.
درس تئوری وتکنولوژی پيشرفته فشار قوی
Offshore Wind and the European Supergrid Joe Corbett, Head of Technical Services Mainstream Renewable Power Representing: Friends of the Supergrid.
Review of progress and future work SQSS Sub Group 2 August 2006 DTI / OFGEM OFFSHORE TRANSMISSION EXPERTS GROUP.
Aspects of partial discharge measurement
© Offshore Wind A big opportunity? GA-EMA Conferences 22 October 2014.
Book Reference : Pages To understand how electricity is distributed in the UK via the National Grid 2.To understand how transformers are used.
August 13 and 20, 2015 Single Line Electricity (SLE) 6 kV in Tal Shahar Israel is working with virtual groundings 1 Experimental.
1 PredictiveOnLine PREDICTIVE SYSTEMS ENGINEERING Vintec Knowledge Ltd.
ea technology Effective Condition Assessment of MV Switchgear
SMART SENSORS FOR A SMARTER GRID BY KAILASH.K AND LAKSHMI NARAYAN.N.
Aleksandra RAKOWSKA Jozef LORENC Witold HOPPEL Poznań University of Technology Institute of Electrical Power Engineering DISTURBANCES IN POLISH 15 KV NETWORK.
Jicable’11, June Versailles - France EXPERIENCE WITH JOINT FAILURES IN NEW SMART- GRID MV CABLE CIRCUITS Frank DE VRIES, Liandon BV, (The.
Integration of the German Offshore Wind Power Potential into the Electricity Supply System B. Lange, Ü. Cali, R. Jursa, F. Schlögl, M. Wolff, K. Rohrig.
TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3 Barcelona May DATAMINING FOR DECISION SUPPORT OF CBM OF POWER CABLES E. GULSKI (1), F.J.
R.G.A. Zoetmulder, S. Meijer and J.J. Smit
Paul Dyer Condition Criticality Risk Rating and Condition Monitoring in a Distribution Network PAUL DYER DAVE OPENSHAW London Electricity Group.
On-line Condition Monitoring of Distribution Network Assets – Making the Network Smarter Neil Davies Neil Davies – UK – Session 1: Network Components –
Utility Engineers, PC.  Generation  Transmission  Distribution.
1 Author Gillie Country UK Session 4 – Block a Barcelona May 2003 'Virtual' Power Plant  Gas turbine used regulate power and voltage at point J.
Energy System Investment Models Paul Rowley & Simon Watson CREST Loughborough University.
Building Offshore Wind in England: Centres of Offshore Renewable Engineering (C.O.R.E) British Embassy, Lisbon, 25th October 2012.
Pre-Grid Commissioning for Renewables Alf Scambler Renewables Sector Development Manager.
J. Ardila, R. Albarracín, J.M. Martínez-Tarifa, G. Robles.
Joint Radio Company: Making the spectrum and technology work for your business Adrian Grilli Chairman, Radio Spectrum Group, European Utility.
15ELP044 – Unit 4 Uncertainty, Risk & Energy Systems Paul Rowley & Simon Watson CREST Loughborough University.
Getting a Grid Connection to Export Power Energy in Agriculture rd August 2016.
Generator Condition Assessment through EMI Diagnostics Doble Power Services.
Planning and Realisation of Wind Farms
YEL WIND POWER PROJECT. YEL WIND POWER PROJECT.
Maintenance strategies
HYDROELECTRIC CORPORATION
SHORT COURSE MOTOR CURRENT SIGNATURE ANALYSIS FOR
Renewables: Moy Wind Farm
Wind technology: R&I perspective
Public Hearing on: Large Wind Farm Interconnection
WELCOME TO ALL.
Evolution of HV Cable Systems
March 2, 2014 One sector, one target, one message The pathway towards 100 EUR / MWh in 2023.
SALES: HOW TO USE THIS PRESENTATION
Sahar Rahim MS-Electrical Engineering Supervisor: Dr. Nadeem Javaid
Design of Electric Power Systems and Utilities
Overhead Conductors.
Grid integration and stability of 600MW windfarm at Kriegers Flak
Reduce Customer Down Times to a Maximum
HYDROELECTRIC CORPORATION
ENG. Julius Ndirangu and
Presentation transcript:

Managing Director, HVPD Ltd Combined Power Quality and Condition Monitoring of Offshore HV Cable Networks EWEA 2013 6th February 2013 Presented by: Dr Lee Renforth Managing Director, HVPD Ltd lee.renforth@hvpd.co.uk

Key Messages  to achieve this The UK offshore wind farm industry has (to date) suffered a higher-than-expected number of medium voltage (MV) and high voltage (HV) cable faults. MV and HV cable faults presently make up over 80% of UK offshore wind farm insurance claims with many faults occurring during the construction phase. The UK Government (DECC) have stated that they require the (presently high) Capital, Operational and Maintenance Costs to fall by 25%* by 2020 to make this offshore renewables electricity more affordable to the UK consumer It is argued that a radical rethink of existing offshore HV network asset management practices is needed to achieve this through the use with of ‘holistic’ condition monitoring (CM) solutions. *(DECC) Levelised Cost of Electricity (LCOE) model predicts the total cost over the 20-year lifetime of the asset.

A Proposal for a ‘Holistic’ Subsea HV Cable Network Condition Monitoring System Illustration of a typical ‘Round 2’ (500MW+) UK Offshore Wind Farm MV & HV Network. 33kV inter-array cables from the turbine arrays feed back to the offshore 33/132kV GIS substation and then, via 132kV land-sea export HV cables, back to the grid connection onshore.

Offshore Wind Farm ‘Holistic’ Subsea MV & HV Cable Monitoring System Main hubs in the 132kV onshore and offshore substations. Remote monitor units located at strategic locations within the 33kV cable array. The monitor system provides an ‘early warning’ system to detect ‘incipient’ HV insulation faults. Can be used to direct preventative maintenance activity to avoid unplanned outages.

Wind Turbine ‘Holistic’ Electrical Monitoring Solution Concept ‘Quadplex’ SMART sensors are used that are suitable for wideband electrical measurements (0-100 MHz) to detect: On-line Partial Discharge (OLPD) Transient Earth Faults (TEF) Transient Voltage Monitoring (TVM) Power Quality Monitoring (PQM) Voltage & Current Monitoring (V/A) Current Signature Analysis (CSA)

On-line Partial Discharge Sensing Techniques and Measurement Systems Inductive High Frequency Current Transformers (HFCT) – to detect partial discharge in cables and remote plant. Capacitive Transient Earth Voltage sensors (TEV) – to detect ‘local’ PD activity. By combining these two sensors, good sensitivity to different types of PD can be obtained. TEV HFCT

A ‘Round 1’ 90MW Offshore UK Wind Farm Case Study 1 OLPD Cable Testing, Location, Monitoring with Preventative Maintenance on a 33kV Land-Sea Wind Farm Export Cable The weak points on a land-sea MV/HV export cable susceptible to failure from partial discharge (PD) A ‘Round 1’ 90MW Offshore UK Wind Farm

Case Study 1: 33kV Wind Farm Export Cable – OLPD Test and Mapping Data High levels of PD (of up to 10,000pC/10nC) measured on Circuit B, Phase L3. Cable mapping (location) tests identified the source at Joint 7, 800m out on Phase L3 of Circuit B. Due to the high level of PD activity and the high risk of failure, a cable repair project was instigated. L1 L2 L3

Case Study 1: 33kV Wind Farm Export Cables High PD Detected on L3 PD Located 200 400 600 800 1,000 1,200 1,400 1,600 Location (meters) Lower-level sporadic PD signals from different site after joint replacement Joint with PD removed and replacement cable section installed

Case Study 1: 33kV Wind Farm Export Cable – Summary The joints on both circuits A & B were replaced at Joint Pit 7 were replaced as part of a preventative maintenance repair project. Extended OLPD monitoring after replacement, showed the high PD activity had ceased. This preventative maintenance repair during a planned maintenance outage removed the risk of failure and confirmed the cable insulation was now in a healthy state for service. Circuit A- Insufficient mastic around connector Circuit B- Defects along XLPE surface due to bad fitting heatshrink stress control

Conclusions The increasing installation rate of offshore wind farms in Europe, combined with the high MV and HV cable fault rates reported in the UK, has led to a ‘market need’ for better cable condition monitoring (CM) technology. Offshore wind farm subsea cable owners need to consider radically better power quality and ‘holistic’ condition monitoring (CM) systems to help drive down their presently (very high) operational and maintenance (O&M) costs. The purpose of any CM system is to provide an ‘early warning’ of ‘incipient’ cable faults to enable preventative maintenance to avoid unplanned outages A move towards Condition Based Management (CBM) of the MV and HV subsea cable networks (using data from ‘holistic’ CM technologies) is the key to help reduce these O&M costs over the 20-year service life of these assets).