Basic Fire and Smoke Training Basic Fire and Smoke Actuators & Dampers.

Slides:



Advertisements
Similar presentations
Chapter 12 HVAC Controls Pneumatic Control Systems • Air Compressor Stations • Transmitters and Controllers • Pneumatic Thermostats • Auxiliary Components.
Advertisements

Summary of NFPA 101 Interior Finish Requirements
Enabling Wellbeing 1. Halton - Enabling Wellbeing Halton was established in 1969 Family owned company, operating in 23 countries. We are passionate about.
Steve Williams, P.E. | Brian Olsen, P.E.
Heating Control Devices
1 Direct Fired Gas Heating Presented by Jim Jagers of Applied Air.
Foundations of Real Estate Management
UL/FM Fire Pump Systems Lunch & Learn 04/18/05
©2011, The McGraw-Hill Companies, Inc. Chapter 4.
Presented April 16, 2009 at the ACG Annual Meeting in Chicago, IL. GAYLON RICHARDSON Engineered Air Balance Co., Inc. Houston, Texas 5/7/20151.
Four Learning Objectives Understand Smoke Control Theory Understand Design Methods Know Your Role in Commissioning Tests Be Familiar with Hardware, Test.
Elevators & Fire Alarm Systems: Understanding Interface Requirements Presented by: Antonio Torres- North Central Regional Sales Manager.
2007-CBC - UL Damper Requirements
Engineer Presentation
Backdraft Dampers. Backdraft Damper Training Application Backdraft dampers allow air to flow in one direction only and prevent unwanted (hot/cold outside.
Buildings and Structures 2 Natural and Mechanical Ventilation.
Monitoring Vibration on Tunnel Fans Safety First The worlds developing infrastructure creates many technical challenges for engineering and construction.
Enclosure Fire Dynamics
Control Damper Products Manual Balancing Dampers
2012 International Fire Code Adopted as the minimum fire safety standard by the State of Wyoming City of Sheridan must adopt the minimum standard to retain.
FIRE DESIGN OF BUILDINGS VULNERABLE GROUPS. COMPONENTS OF FIRE building materials unattended stoves Loose electrical connections overloaded electrical.
HVACR416 - Design Pressure Measurement Part 2. Pressure Measurement Several pressure measurements exist. They all measure the same things, the force of.
Chapter 19 Charging Systems.
WELCOME DBI & SFFD Meet the Pros October 11, 2007.
Hydronic Mechanical Controls
Unit 8: Portable Fire Extinguishers & Smoke Control Management Systems
HEAD START CHILD AND FAMILY DEVELOPMENT CENTER, INC
The AHU From A Case Study Presented by David Sellers Portland Energy Conservation Inc. INLAND EMPIRE CHAPTER 1 - 2/27/2002.
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
Fire Safety 7th Grade.
International Fire Door Inspector Association Presents New Annual Fire Door Inspections NFPA 80 – 2007, 2010, 2013 Standard for Fire Doors and Other Opening.
Single-Point Zoning Damper Choices
Fire Safety By Alicia Civile and Alexandra Fernandez.
Code Officials and the Code Process.  To design the interior of the building in conjunction with codes, standards and federal regulations required in.
VAV Box Control Loop The purpose of the VAV Box control loop is to adjust airflow through the box to maintain a space temperature. The difference between.
1 Lamp operating factor Published lumen output is based on laboratory conditions Voltage  Rated at line voltage of 115V Standard reactor ballast  Electromagnetic.
Neil Cooper Fire Safety Residential Implementing the Changes.
ID 308 Construction + Materials IV: Construction Documents Prof. Brody Endicott College Systems Coordination.
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
HVAC sensors. Smoke detection Zone 1 Zone 2 Spread of fire gases in ventilation ducts.
Fire-Resistant Materials & Assemblies Part 2 Chapter 5.
CUE – Make Any Pump an E-Pump
Code Officials and the Code Process.  Concentrates on the code process as a whole.  Different type of code officials  Various steps that are taken.
ME444 ENGINEERING PIPING SYSTEM DESIGN
50% LBNE Concept Design WCD Infrastructure. Mechanical.
3M B&CSD - Fire Protection Space for 3M Montage © 3M All Rights Reserved. 3M Fire Barrier Duct Wrap 615 For Ventilation Ducts.
ACT20X Ex isolator/ amplifier. Page 2 ACT20X (Ex isolators family) Overview - Connects to process equipment in Class/Div, or Zone 0 - Zone 2 areas - ACT20X.
Fundamental Concepts for Design of Special Hazard and Fire Alarm Systems Chapter 1.
Exercise #2 (part 2) Based on what you read in Chapter 4, determine if the corridors and exit doors meet the requirements for egress width, according to.
New Energy Centre at Megawatt Park 15 April 2014.
 The airborne solid and liquid particulates and gases evolved when a material undergoes pyrolysis or combustion. – NFPA 92A  Follows Path of Least Residence.
Integrated Blower Packages Kaeser Integrated Blower Family.
Basic Fire and Smoke Actuators & Dampers
Barrier Management Symposium
Asahi/America Electric Actuators Series 94.
Fire Alarm Systems for Emergency Operations of Elevators
Emergency Evacuations: Multi-Level Apartments
Fire Door Inspections Qualified Training
Design of Evacuation System for High-Rise Building Danqing Yu
Roof Top Unit Overview (MAGNUM)
Fire Alarm Interface of Smoke Dampers
Flip The Long House Let’s imagine the Long house example in Manual J has undergone a house flipping/energy savings update. The insulation was increased,
Asahi/America Electric Actuators Series 94.
Smokes extraction principle
Automotive Technology Principles, Diagnosis, and Service
Presentation transcript:

Basic Fire and Smoke Training Basic Fire and Smoke Actuators & Dampers

Basic Fire and Smoke Training Contents Basic damper and actuator concepts Types of Systems Control Standards and Codes Indicator Lights and Aux Switches Product & New Applications Specifications

Basic Fire and Smoke Training Basic damper and actuator concepts

Basic Fire and Smoke Training UL555 (fire dampers) Courtesy of Pottorff

Basic Fire and Smoke Training Courtesy of Pottorff

Basic Fire and Smoke Training Jackshaft Damper Sleeve Actuator UL555S (smoke dampers) Courtesy of Pottorff

Basic Fire and Smoke Training Blade & Seal Jackshaft Stand-off bearing bracket Damper Frame Sleeve Axle Drive Arm Frame Side Seal Courtesy of Pottorff

Basic Fire and Smoke Training Smoke Damper – no temperature limit. Controlled by smoke detectors or indirectly via smoke control panel.

Basic Fire and Smoke Training Manual Reset High Temperature Limit 165F 185F 210F 250F 350F Combination Fire & Smoke Courtesy of Pottorff

Basic Fire and Smoke Training Actuators are tested as an assembly with the damper. Not listed alone. UL555(S) requires 75 second time. Test covers leakage, high velocity closing, other functions.

Basic Fire and Smoke Training Types of Systems

Basic Fire and Smoke Training Two types of damper use – 1.Containment / Compartmentation 90% simply close to prevent smoke or fire spread. 2. Engineered smoke control Applied in zone pressurization, stairwells, elevator shafts, lobby pressurization, atria and large spaces. Can be exhaust or pressurization to prevent smoke spread.

Basic Fire and Smoke Training Compartmentation

Basic Fire and Smoke Training Engineered Smoke Control Systems Organized control of smoke movement rather than containment is required as indicted in lessons learned from past fires. The total situation is considered.

Basic Fire and Smoke Training Engineered Smoke Control Systems Stairwell pressurization Atria smoke extraction Elevator shaft pressurization Ventilated lobbies Corridor dampers Ceiling dampers Shaft dampers Duct dampers Fire & Smoke doors Smoke Extraction Shafts and Fans Sandwich or building pressurization systems

Basic Fire and Smoke Training Consultants will develop a rational analysis smoke control strategy 1.Sequence of operation 2.Detail the response to alarms. Manual stations will start purge or pressurization sequences in stairwells. Floor by floor sequence to contain smoke. 3.Positive Feedback and what the system should do if feedback is not received in the specified time.

Basic Fire and Smoke Training Dedicated: no other function but smoke control. Non-dedicated may be a HVAC air handling unit. a RELIEF FAN SYSTEM OA RF RA SA MA RP RAD RFD OAD Dedicated & Non-dedicated Smoke Control Non-dedicated

Basic Fire and Smoke Training Each actuator gets separate output from smoke control panel. Reopenable dampers can assist in exhausting dangerous amounts of toxic, low temperature smoke from the fire zone and to pressurize adjacent zones to prevent spread. Courtesy of HPAC Engineering

Basic Fire and Smoke Training Control

Basic Fire and Smoke Training Smoke Control can be managed by BAS or the Fire Alarm System Some trend to shift to an integrated system - Fire protection and BAS combined. UL864 required for Fire Alarms, not actuators or dampers. Control Courtesy of HPAC Engineering

Basic Fire and Smoke Training BAS or the Fire Alarm System can provide: 1.Hardware for operation 2.Firefighter Smoke Control Station 3.Process logic to control devices 4.Monitoring 5.Initiation of automatic smoke control can come from smoke detectors, alarms, water flow switches in sprinkler pipes, or pull stations into the fire system.

Basic Fire and Smoke Training The Front End of every smoke control system is the Fire Fighters Control Station: LED’s associated with every fan & damper Manual overrides for every fan & Damper Fans & dampers are typically tied to BAS Information from dampers & fans is taken and processed by either the Fire or BAS system to control the correct fans & dampers at the right time. Fire Fighters Smoke Control System:

Basic Fire and Smoke Training SMOKE CONTROL

Basic Fire and Smoke Training LOCAL SMOKE CONTROL

Basic Fire and Smoke Training Factory mounted smoke detector Courtesy of Pottorff

Basic Fire and Smoke Training Actuator Power

Basic Fire and Smoke Training Will need parallel wiring for two large section dampers. Actuators

Basic Fire and Smoke Training 80% of dampers use this configuration. Single sensor, manual reset. Smoke detector, high temp limit, contact on fire alarm control panel or system.

Basic Fire and Smoke Training HEAT, SMOKE DETECTOR, OR OTHER RELAY FROM ALARM SYSTEM AUTO: IF DUCT TEMPERATURE REACHES 165F OR EXTERNAL ALARM CONTACT OPENS, POWER IS CUT TO ACTUATOR AND DAMPER SPRINGS CLOSED. MANUAL RESET. Reopenable Damper

Basic Fire and Smoke Training High Limit Sensor and Reset switch Status Lights (Optional)

Basic Fire and Smoke Training Standards & Codes

Basic Fire and Smoke Training Vertical Shafts – fire-smoke dampers required at penetrations This is one of the the most important protection against smoke spread in a fire. Elevator shafts and lobbies – sprinkler trade-offs exist in IBC, not UBC. Corridors – derated requirement in IBC, not UBC. These are the escape paths. They should be protected. You are not safer in an IBC building. Pressurized stairway – required in IBC and UBC. People must be able to escape fires. Codes and Standards

Basic Fire and Smoke Training UL555 & UL555S Damper manufacturer requirement High temperature test for 250F or 350F Damper and Actuator Heated Air Flow test ensures actuator closes damper. Others for damper only: Drop test, salt spray, Leakage rating 75 second is the UL 15 time requirement. UBC required 15 seconds for some years. Belimo is 15 seconds for FSLF and FSNF; 75 sec drive and 20 sec spring for FSAF.

Basic Fire and Smoke Training NFPA 90A, B HVAC 92A, BSmoke Control Systems for atria and large spaces. 80 (fire) & 105 (smoke) doors and dampers TESTING REQUIREMENTS Every 4 years per NFPA. Local codes vary. Hospitals every 6 years.

Basic Fire and Smoke Training NFPA NFPA 80 is fire opening protectives – fire doors and dampers NFPA 105 is smoke opening protectives – smoke doors and dampers. Testing requirements: At end of first year Every 4 years Except hospitals – every 6 years.

Basic Fire and Smoke Training Local Codes Vary by city, county, state, region NFPA 5000 is not used. IBC is now dominant

Basic Fire and Smoke Training Codes and Standards are quite intensive a subject. Not covered here in any detail. Smoke Control System Required Atria, High rise smokeproof exit enclosures (>75’ ), underground buildings, auditoriums & stages. Smoke Dampers required at s moke barrier penetrations

Basic Fire and Smoke Training Life Safety Standards and Codes are always changing and developing. Trade-offs between levels of cost and safety will always exist. Different views exist. Purpose of Life Safety is to protect people, not buildings. By protecting the building we protect people. First code to clearly state this was the 1997 UBC.

Basic Fire and Smoke Training Codes require life safety systems be maintained in operating condition. Rules are mostly unwritten. Use common sense – if it breaks, fix it. AHJ – usually the Fire Marshal – is the final authority on dampers and alarms. Actuator & Damper Replacement and Repair

Basic Fire and Smoke Training Actuator & Damper Replacement and Repair NFPA 80 & 105 require maintenance and repair or replacement. UL accepts actuator replacement; does not regulate. Use Belimo or damper manufacturer instructions. Actuator should be UL555S Listed with the manufacturer. “Equal or Better” is required. Separate Belimo documents detail repairs on different types of dampers.

Basic Fire and Smoke Training Balanced Strategy Sprinklers Structural Compartmentalization Alarms Fire and Smoke Dampers Smoke Control Systems Maintenance

Basic Fire and Smoke Training Indicator Lights and Aux Switches

Basic Fire and Smoke Training

Indicator Lights Red Green Amber Courtesy of Pottorff

Basic Fire and Smoke Training Product & New Applications

Basic Fire and Smoke Training Belimo F&S Product Line FSLF 4 sq.ft. FSNF12 sq.ft.

Basic Fire and Smoke Training FSAF max 18 sq.ft. 2-position 24, 120, 230 volt. 24 VDC as well as AC FSAF24-BAL3-Position FSAF24-SR 2-10Vdc Proportional

Basic Fire and Smoke Training Underfloor HVAC Pressure Control FSAF24-SR

Basic Fire and Smoke Training Stairwell Pressurization Stairwell pressurization allows occupants to safely exit the building, while firefighters can stage and safely access an upper level fire. Typically one damper and pressure sensor per 3 floors.

Basic Fire and Smoke Training Proportional 2-10Vdc F&S Actuator FSAF24-SR

Basic Fire and Smoke Training Unique, first of its kind. 3-position for balancing and F&S BALANCING FIRE & SMOKE FSAF24-BAL

Basic Fire and Smoke Training Why Specify

Basic Fire and Smoke Training 1.5 year warranty 2.Micro Controller: Actuator cannot burn out if stalled before full rotation is achieved. 3.Motor runs cool for a long life span. 4.DC Motor: No noise when holding. 5.Very low Current Draw 6.Steel cold-weld clamp: no shaft slip 7.Steel housing: rugged integrity 8.ISO 9001 Quality Control 9.Not the cheapest. Belimo Quality

Basic Fire and Smoke Training 1.Fire and Smoke actuators have been treated like a commodity item. This has resulted in poor quality and lifespan in the market. 2.Most specifications put the dampers in Duct Accessories. Life safety should be treated with more respect.

Basic Fire and Smoke Training

THANK YOU AMERICAS