Janet Haas PhD, RN, CIC Rich Vogel MS, CIC Disclosures: Haas - Hand Hygiene Study funded by 3M Vogel - None VogVela Infection Prevention in Design and.

Slides:



Advertisements
Similar presentations
1 Construction and Renovation Activities in Healthcare Facilities What construction crews should know, but were afraid to ask!
Advertisements

Lesson 9 Design & Construction of Food Premises & Equipment
Mold Hazards And Prevention. © Business & Legal Reports, Inc Session Objectives Understand the potential health hazards of exposure to mold Detect.
HVAC Systems and Their Role in Infection Control and Prevention
BSA Health System, May 2009 Next Slide Previous Slide BSA HEALTH SYSTEM Infection Control during Construction, Renovation, Repairs, and Maintenance All.
Presented By: Kary S. Amin Nova Environmental, Inc.
environmental biosafety in hospitals principles and Practice
What is wrong with our Practices Disinfectants used indiscrimately, Used unnecessarily Not used when needed. Concentration not adequate Economic consideration,
Principles of Decontamination. Objectives Define contamination and decontamination Differentiate between the concepts of exposure and contamination Identify.
Innovative Air Distribution for Healthcare Facilities.
SANITARY DESIGN PRINCIPLES FOR FACILITIES. ZONES OF CONTROL.
HICC An Infection Control Committee provides a forum for multidisciplinary input and cooperation, and information sharing This committee should include.
CDC/NIH Vertebrate Animal Biosafety Level Criteria ► For all Animal Biosafety Levels (1 - 4)  IACUC Approval  Authorized access to facilities  Animal.
The Care and Isolation Unit (CIU) at St Patrick Hospital In 2005 the NIH issued a Request for Proposals for the construction and staffing of a patient.
SETUP Chapter 6 Lead Abatement for Workers Course.
Equipment and Facilities. 154 Plan Review The local health department must assess your facility and equipment before: –Beginning construction of a food.
Governor’s Secure Commonwealth Initiative, Health and Human Resources Sub-Panel Meeting Janis Ober MSN RN CIC Director, Infection Prevention.
3.03 Understand support services
© 2009 Michigan State University licensed under CC-BY-SA, original at Facility Environment.
25 TAC Quality Assurance in a licensed ASC
Unit 6.2. Mechanical and mixed mode ventilation TB Infection Control Training for Managers at National and Subnational Level.
Good hygienic practices
Infection Prevention and Control Competencies for Healthcare Personnel Ruth Carrico PhD RN FSHEA CIC Associate Professor Division of Infectious Diseases.
 Lesson objective to understand the importance of hospital and care setting hygiene.
1 Ventilation, Temps and Humidity Requirements PO Box 3187 Charleston, WV Inquisit February 6, 2014.
Tulane University - Office of Environmental Health & Safety (OEHS) EMERGENCY EYEWASH AND SHOWERS FOR TULANE LABORATORY OR FACILITY EMPLOYEES WITH THE POTENTIAL.
SARS Infection Control. Key Objectives Early detection Containment of infection Protection of personnel and the environment of care Hand hygiene Key Strategies.
Unit 6.4. Filtration TB Infection Control Training for Managers at National and Subnational Level.
The Effects of Construction Activity on Indoor Air Quality for Hospitals Presented by: Tom N. Petersen, P.E. Environmental and Engineering Solutions, Inc.
3.03 Understand support services Introduction
The Physical Environment Tracers How Should I Prepare for the Physical Environment Tracers? Healthcare Engineering Consultants  Will limit.
© 2009 Michigan State University licensed under CC-BY-SA, original at Water Quality.
LEAD SAFETY PROGRAM. REFERENCES 29 CFR CFR MCO F CHAPTER 17 BASE INSTRUCTION Lead Abatement 29 CFR MCO F HUD.
Effective Sanitation 1. GMPs SANITARY EQUIPMENT DESIGN SANITARY FACILITY DESIGN HACCP TRAINED EMPLOYEES VALIDATED & VERIFIED PROCESSES REPEATABLE FOOD.
AIA Guidelines for Design and Construction of Hospital and Healthcare Facilities Presented By: Michael A. Rogers, PE
Environmental Cleaning Tool Kit
Environmental Cleaning Tool Kit
Health Emergency Risk Management Pir Mohammad Paya MD, MPH,DCBHD Senior Technical Specialist Public Health in Emergencies Asian Disaster Preparedness Center.
Premises Basic Principles of GMP Workshop on
Part 5: Meeting the Challenge of the “EC Tracers” Healthcare Engineering Consultants How Should I Prepare for the “EC Tracer” Part of the Survey?
Decontamination of Equipment.
Module 9Slide 1 of 25 WHO - EDM Premises Part One Basic Principles of GMP Part One, 11.
Standard and Transmission-Based Precautions
Course Code: NUR 240 Lecture ( 3). 1.The Risk of Infection is always Present in every Hospital. 2.Identify frequency of nosocomial infection.
Infection Control Lesson 2:
An introduction to… Lockout Tagout. Aim Every year thousands of workers get killed or injured while performing repairs or maintenance on industrial equipment.
HEALTHCARE SYSTEM Infection Control during Construction, Renovation, Repairs, and Maintenance All workers engaged in the construction, renovation, repair,
Joanne Withers Infection Prevention & Control Nurse Infection Prevention and Control – Audit and Mandatory Training Workshop.
Infection Control Risk Assessment Guidelines and Standards Richard Vogel - Infection Control Specialist.
“Ventilation of Healthcare Facilities” Impact of the New ANSI/ASHRAE/ASHE Standard 170 Standard 170 Stephen W. Nicholas, CPMM, CAFS ASHRAE Boston Chapter.
 HCS 446 Week 1 Discussion Question 1  HCS 446 Week 1 Discussion Question 2  HCS 446 Week 1 Individual Assignment Facility Planning - Part I  HCS.
Mintie Technologies, Inc. ECU Product Introduction and Demo/Training Virginia Presentation.
PRESENTED BY ENG. PRISCILLA NAKIBONEKA SANITARY ENGINEER, MINISTRY OF HEALTH, UGANDA.
Prevention and Control of Influenza A (H1N1) in the Workplace Engr. Nelia G. Granadillos Chief, Environment Control Division Occupational Safety and Health.
Facility Environment 1.
USP 797 Guidelines: Compounding Areas and Equipment
Infection Control Risk Assessment
3.03 Understand support services
SANITATION & HYGIENE KHADIJAH ADE-ABOLADE MPH. FPCPharm.
Additional Precautions
Green Cleaning to Meet LEED (Leadership in Energy and Environmental Design) Existing (Green) Building Operations and Maintenance Requirements.
3.03 Understand support services
3.03 Understand support services
Pre Construction Risk Analysis
Infection Control Fundamentals Unit 2.
3.03 Understand support services
Biocontainment Patient Care Unit--Consensus Standards
3.03 Understand support services
IPAC Core Competencies Routine Practices
Biosafety Principles: Separation, Seclusion & Containment
Presentation transcript:

Janet Haas PhD, RN, CIC Rich Vogel MS, CIC Disclosures: Haas - Hand Hygiene Study funded by 3M Vogel - None VogVela Infection Prevention in Design and Construction of the Healthcare Environment 1

Healthcare Facility Design Goals First, do no harm Meet needs of functional program Support delivery of care model Enhance the patient environment, staff effectiveness and stewardship of the environment

Regulations States may have individual requirements Facilities Guidelines Institute –Publish "Guidelines for Design and Construction of Health Care Facilities" (2010) –New edition due in 2014

Joint Commission –“When planning for demolition, construction or renovation, the hospital conducts a preconstruction risk assessment for air quality requirements, infection control, utility requirements, noise, vibration and other hazards that affect care, treatment and services.” EC EP2 

Infection Control Risk Assessment (ICRA) Multi-disciplinary team Design Construction Compliance Risk mitigation

Design Number, location and type of: –Airborne infection isolation and Protective environment rooms These cannot be switchable –Hand washing sinks, sanitizer dispensers –Eyewash stations and deluge showers HVAC systems to meet functional needs -e.g. Procedure rooms, laboratories etc. Water systems to limit legionella

Air Requirements General Principles - Clean to Dirty –Dirty areas (janitors closets, decontamination rooms, areas for bronchoscopy, laboratory with specimens) are negative pressure –Procedure areas, pharmacy compounding, sterile supply areas are positive pressure Best Reference is ANSI/ASHRAE/ASHE Standard Table 7-1

Airborne Isolation (AIIR) Negative Pressure = Air flows from corridor to (anteroom if present) to patient room –12 air changes/hour with 2 outside air changes/ hour Exhaust air grills in ceiling over patient head or on wall at head of bed

AIIR (Cont’d) Toilet and tub/shower and pt sink in the inpatient room as well as hand washing station for staff Air must be exhausted directly outside without mixing with non-AIIR exhaust Continuous visual pressure monitor Area for gowning/storage directly inside or outside of entry In retrofitted settings, can HEPA filter exhaust air Can use for non-isolation patients, but pressure settings do not change

Protective Environment (PE) Positive Pressure Positive Pressure = Cleanest (patient area) to less clean Supply air to PE room is HEPA filtered just before entering the room or suite of rooms –12 Air changes/ hour including 2 outside air changes/ hour Permanently installed visual mechanism to constantly monitor pressure status of the room Anteroom not required per Facilities Guidelines, but does mitigate against pressure changes 10

Combination AIIR/PE Room Reversible air flow NOT allowed. Air supply = PE room Exhaust air = AIIR requirements Airflow patterns may be from anteroom to both the pt room & corridor OR Airflow may be from pt room & corridor to anteroom Must have 2 visual monitors 1 between pt room and anteroom; 1 between anteroom and corridor

Visual Pressure Monitoring Devices

Legionella Prevention Design water systems to reduce risk –Scale system for actual needs (don’t over build), leads to decreased circulation around water circuits –Limit dead legs and areas of stagnation Assess need for filtration in high risk areas –Legionella in the incoming water, high risk patients, amount of water use in the area –COMMISSIONING PROCEDURES

Sinks Hands free Wrist blades, knee control, electronic eye Avoid aerators as these promote water dispersal Electronic eye: Save water, are popular with patients May be more prone to legionella contamination Must consider wiring to emergency power Sydnor ER et al. Electronic-eye faucets: Legionella species contamination in healthcare settings.ICHE Mar;33(3): ICHE. HargreavesJ et al. Bacterial contamination associated with electronic faucets: a new risk for healthcare facilities. ICHE 2001Apr 22(4);202-5

Some Plumbing Basics Mixing Valves - control water temperature at the outlet by use of a thermostat Temperature actuated flow reduction valve - (anti-scald valve) Immediately closes in the event of a loss of cold water protecting patients from being scalded. Used primarily to control the high limit water temperature of showers. These devices may impact ability to superheat water for legionella eradication

Ice and Water Cold water less likely to harbor legionella Need water and ice for patient care/comfort Assure cleaning and maintenance plan is in place Assure people are trained to change filters and clean/disinfect various components of machines Trouble spots are anywhere water sits for prolonged periods Prevent contamination of ice by providing place outside of ice for the scoop

Flood Damage Prevention Raise Sheetrock off floor during construction.

Excretions/Secretions/Waste Everyday concern May contaminate environment Staff safety concern Red bag waste is costly to manage

Your Choice? Q: Are toilets required everywhere?

Technology Infrastructure Nurse call, documentation, patient education and diversion/recreation Computer cabling and device location Other controls - access hatches Water filtration Environmental disinfection technology

Patient Handling and Movement Assessment (PHAMA) Needs assessment to identify appropriate equipment for the service area. Definition of space and structural and other design requirements to accommodate this equipment –Prevent hallway clutter –Adequate outlets –Assure safe patient handling

Supply Storage Provide supplies within work flow while minimizing risk of cross contamination Just outside the patient room Outside to inside access

Staff Support Areas

Patient/Family Space For patients and families Match needs of functional program and care delivery model Assess length of stay/needs –Example: If you offer washer/dryer, then consider clothes storage space –CLUTTER PREVENTION

Carpeting Pleasant, inviting appearance (at least when new) Comfort and warmth underfoot Sound deadening properties No solid evidence that carpeting is linked to increased risk of HAI under normal circumstances Wet carpet is a risk for Aspergillus Gerson, SL et al. Aspergillosis Due to Carpet Contamination, ICHE 1994: 15(4) 221-3

Finishes Easily cleanable with hospital disinfectants Not prone to soiling with extensive use (e.g. vinyl upholstery vs. cloth) Skid-resistant No crevices for dust

Furnishings Cleanable/rust resistant Designed to reduce clutter Support patient mobility/independence Bed bug ‘resistant’ (limit crevices, assure no tears in upholstery)

Fixtures

Fixtures (Cont’d)

Antimicrobial Surfaces Copper Surfaces –Passive continuous activity; need info on exact alloys and application method; long term efficacy Curtains – become contaminated again shortly after cleaning (within 1 week) –Antimicrobial curtains may delay contamination (to 2 weeks in recent study) –May be more effective vs certain pathogens –Consider alternatives (e.g. smartglass) Schweizer M et al. ICHE2012 Nov;33(11):1081-5, Trillis F et al. ICHE 2008 Nov;29(11):1074-6, Ohl M et al. AJIC 2012 Dec;40(10):904-6 Otter JA et al JHI 2007 Oct;67(2):182-8 Bearman G et al ICHE 2012 Mar;33(3): Salgado CD et al. ICHE 2013:34(5) Schmidt, MG et al. ICHE 2013:34(5) O’Gorman J & Humphreys H JHI in Press

Summary Attention to detail at all levels ICRA is not just a permit for dust control during construction Design is something you will live with for years Don’t forget the fixtures and finishes –Thank You!

2010 FGI Guidelines ICRA Recommendations Based on the results of the initial stage of the ICRA, the owner shall provide the following recommendations for incorporation in the functional program: (1) Design recommendations generated by the ICRA (2) Infection Control Risk Mitigation Recommendations (ICRMRs)

Determining Dust Control Measures STEP 1: Type of Construction STEP 2: Identify the Risk Group STEP 3: Project Class  How big is the construction project?  How ill/frail are the patients?  Non-patient area?  Ambulatory Patient / Patient access area?  In-patient area/ High risk ambulatory?  Minor repair?  Major renovation?

ICRA Compliance  Infection Control Risk Mitigation Recommendations (ICRMR)  Monitoring Plan  Daily/weekly checklist to verify described methods are in place  Plans which describes specific methods by which transmission of contaminates will be avoided  Barriers, negative pressure, sticky mats, HEPA filters, etc  Communication  Report checklist findings to Infection Control/Safety Committee Compliance Elements ICRA Documentation This written record shall remain an active part of the project documents for the duration of the construction project and through commissioning.

Dust Control Measures Patient placement Barriers and other protective measures Protection from demolition Training Debris and traffic flow Bathrooms and food for construction workers Infection Control Risk Mitigation ICRMR Planning Infection control mitigation recommendations (ICRMRs) shall be prepared by the ICRA team and shall, at a minimum, address the following:

Barrier For Dust Control Tight to ceiling and walls Door Closed

Barrier For Dust Control Zipper closed Tight to ceiling and walls Sticky mat

Barrier For Dust Control

STICKY MATS

Debris Removal Use Of Coveralls During Demolition

Sealed Air Ducts

Mobile Dust Control Devices

Instructions to Contractors Guidelines for Reduction of Infection Risk During Construction & Renovation  Infections associated with hospital renovations are a concern due to the vulnerability of patients who are near the construction activities. The control of infection risks (primarily airborne) during these periods is essential.  Dust containment is a critical component in the control of fungi in patient areas as well as the prevention of irritation and illness in patients, visitors and staff. It is the policy of NYP that whenever work creates an open space between construction areas and other dust or possible fungi containing areas, EHS, the Department of Epidemiology and Facilities will conduct a careful evaluation of these areas. The degree to which the project will require dust abatement measures is determined by completing an Infection Control Risk Assessment (ICRA). EHS, Epidemiology and the NYP/PM will monitor compliance with the procedures described in this policy.  Although each project is unique in items of required construction, and the location and vulnerability of nearby patients, certain general precautions are prudent. The purpose of these guidelines and the ICRA is to enhance the prevention of illness in patients who may be immune-compromised and susceptible to fungal infections and others who may be sensitive or otherwise allergic to materials found in or carried by dust.  These guidelines apply to all activities in the hospital that may create dust, aerosolize fungal spores, or generate other antigenic or irritating materials that will cause illness or discomfort and obligates EHS, Department of Epidemiology and Facilities to evaluate and monitor all such activities. All GC/CM staff are expected to comply with these requirements.

Educational Material for Construction Workers

Staff Education

Dust Control Plan

Air Flow in Construction Sites  Location of exhaust discharges  Cleaning of existing building systems  Visible display of airflow in high risk areas  Pressure differential of at least 0.03 inch water gauge A Ventilation of the construction space Airflow into the construction zone from occupied spaces should be maintained by means of a dedicated ventilation/exhaust system for the construction area.

CREATING NEGATIVE PRESSURE Construction Site Entrance Window with exhaust fan Construction Site Construction Dust

CREATING NEGATIVE PRESSURE Construction Site Entrances Construction Site (top view) Construction Dust Ante Room HEPA Filter

Creating Negative Pressure

Exhausting HEPA filtered air

Creating Negative Pressure Exhausting HEPA filtered air

Checking HEPA Air Scrubbers

Air Flow Indicator

Continuous Monitoring of Negative Pressure

Vivian and Seymour Milstein Family Heart Center Construction

Exterior Demolition

Creating Negative Pressure

Radiation Oncology Plan

Radiation Oncology Site

Watering Down Excavation

Quick Set Up Dust Barrier

Mobile Dust Control Devices VS

Reusable Dust Control Barriers VS

QUESTIONS?