DESIGN OF STRUCTURAL MEMBERS

Slides:



Advertisements
Similar presentations
1 Design and drawing of RC Structures CV61 Dr. G.S.Suresh Civil Engineering Department The National Institute of Engineering Mysore Mob:
Advertisements

2.2 STRUCTURAL ELEMENT BEAM
2.2 STRUCTURAL ELEMENT Reinforced Concrete Slabs
WORKSHEET 7 AXIALLY LOADED MEMBERS. Q1 Are tension structures or compression structures more efficient when loaded axially ? tension structures tension.
Axial Members WORKSHEET 11 to answer just click on the button or image related to the answer.
Chp12- Footings.
Gable Roof BCGCA3007B.
Beams Extremely common structural element
ONE-WAY SLAB. ONE-WAY SLAB Introduction A slab is structural element whose thickness is small compared to its own length and width. Slabs are usually.
Wall Form Design Example (Continued)
Design of Tension Members
Design of Tension Members
Designing for Stiffness
1 Design and drawing of RC Structures CV61 Dr. G.S.Suresh Civil Engineering Department The National Institute of Engineering Mysore Mob:
DESIGN OF TRUSS ROOF Chapter 7
BEARING OR CRUSHING Bearing Stresses (Compression Perpendicular to the Grain) Allowable stresses for compression perpendicular to the grain are available.
Copyright © 2011 Pearson Education South Asia Pte Ltd
Reinforced Concrete Design II
COLUMNS.
LRFD-Steel Design 1.
DESIGN OF TRUSS ROOF Chapter 7
FOUNDATION DESIGN.
ERT352 FARM STRUCTURES FOUNDATION DESIGN
Footings.
University of Sydney – Structures SECTIONS Peter Smith & Mike Rosenman l The size and shape of the cross- section of the piece of material used l For timber,
Chapter 10 Web splice.
COLUMNS. COLUMNS Introduction According to ACI Code 2.1, a structural element with a ratio of height-to least lateral dimension exceeding three used.
Beam Design.
WORKSHEET 2 FAILURE, STRESS AND STRAIN
SHEAR IN BEAMS. SHEAR IN BEAMS Introduction Loads applied to beams produce bending moments, shearing forces, as shown, and in some cases torques. Beams.
Umm Al-Qura University Department of Civil & Structural Engineering 1 Design of reinforced concrete II Design of one-way solid slabs Lecture (1)
University of Palestine
Plain & Reinforced Concrete-1 CE-313
Reinforced Concrete Design
ERT352 FARM STRUCTURES TRUSS DESIGN
BEAMS AND COLUMNS PRESENTED BY K.ROSHIN RUKSHANA.
1.
FOOTINGS. FOOTINGS Introduction Footings are structural elements that transmit column or wall loads to the underlying soil below the structure. Footings.
WORKSHEET 4 BEAMS.
Session 15 – 16 SHEET PILE STRUCTURES
Tulkarem Multipurpose Sport Hall Prepared by: Moatasem Ghanim Abdul-Rahman Alsaabneh Malek Salatneh Supervisor: Dr. Shaker Albitar.
©Teaching Resource in Design of Steel Structures IIT Madras, SERC Madras, Anna Univ., INSDAG 1 COMPOSITE FLOORS - II.
ME31B: CHAPTERTHREE INTRODUCTION TO STRUCTURAL DESIGN.
Lecture 15 - Timber Wall Framing Example
6- Calculation of shear stress at composite interface: A)Under service load: Strain and stress distributions across composite beam cross- section, under.
BEAMS: Beams are structural members that can carry transverse loads which produce bending moments & shear force. Girders: Main load carrying members into.
Beam Design Beams are designed to safely support the design loads.
SANKALCHAND PATEL COLLEGE OF ENGINEERING,
AR362 - Structural Systems In Architecture IV Lecture : Foundations
ERT352 FARM STRUCTURES BEAM DESIGN
Dr Badorul Hisham Abu Bakar
ERT352 FARM STRUCTURES TRUSS DESIGN
62323: Architectural Structures II
Design of Beams for Flexure
Outline: Introduction: a ) General description of project b) Materials
Lecture - Design of Columns
FOR 5TH SEMESTER DIPLOMA IN CIVIL ENGINEERING
Mahesh Dhakal Stud Wall Design Mahesh Dhakal
Design of Reinforced Concrete
DESIGN OF TRUSS ROOF Chapter 7
Design Ribbed and Flat Slabs
Structure II Course Code: ARCH 209 Dr. Aeid A. Abdulrazeg.
EAT 415 :ADVANCED STEEL BUILDING DESIGN PLATE GIRDER
2.2 STRUCTURAL ELEMENT Reinforced Concrete Slabs
ROOFS.
Reinforced concrete column
Chapter 13 Concrete Form Design.
Graduation Project Bracing system for deep excavation.
Structural Design I Course Code: CIVL312 Dr. Aeid A. Abdulrazeg.
Presentation transcript:

DESIGN OF STRUCTURAL MEMBERS ME31B: CHAPTER FOUR DESIGN OF STRUCTURAL MEMBERS

DESIGN OF MEMBERS IN DIRECT STRESS: Structural members under direct stress are mainly ties, cables, and short columns.

Solution Concluded

Design of Short Columns

Example A square concrete column(pier) which is 0.5 m high is made of a nominal concrete mix of 1:2:4, with a permissible direct stress of 5.3 N/mm2. What is the required cross-sectional area if the column is required to carry an axial load of 300 kN?  Solution: Area = Force/stress = 300 x 103 N = 56600 mm2 5.3 N/mm2 ie. the column should be minimum 240 mm square. 

Note Maximum compressive stress (fc) occurs in the section where the bending moment is maximum. In the design of simple beams, section modulus (Z) should be selected such that fc does not exceed the allowable value. Allowable working stress values can be found in building codes or Engineering handbooks. For safe bending, fw > f = Mmax/Z where fw is the allowable bending stress; f is the actual stress and Mmax is the maximum bending moment.

b)     Deflection of Beams Excessive deflections cause cracking of plaster in ceiling and can lead to jamming of doors and windows. Most building codes limit the amount of allowable deflection as a proportion of the member's length ie. 1/180 , 1/240, or 1/360 of the length.

4.2.1 Steps in the Design of Simple beams a) Calculate loading on the beam b) Calculate the bending moment, shear forces, etc. c) For the maximum bending moment (Mmax), provide a suitable section: Z = Mmax/fw , fw is allowable stress (from tables). d) Check for shear stress, deflection and buckling of web if necessary.

Example Consider a floor where beams are spaced at 1200 mm and have a span of 4000 mm. The beams are seasoned cypress with the following properties: fw = 8 N/mm2 , E = 8400 N/mm 2 , density = 500kg/m3 . Loading on floor and including floor is 2.5 kN/m2 . Allowable deflection is L/240. Design the beam. Allowable shear stress is 0.7 N/mm2

4.2.2 Bending Moment Caused By Askew Loads When the resulting bending moment on a beam is not about one of the axis, the moment need be resolved into components acting about the main axis. The stresses are then calculated separately relative to each axis and the total stress is found by adding the stresses caused by the components of the moment.

Roof Truss Showing Purlin

Example Design a timber purlin, which will span rafters 2.4 m on centre. The angle of the roof slope is 30 ° and the purlin will support a vertical dead load of 250 N/m and a wind load of 200 N/m acting normal to the roof. The allowable bending stress(fw ) for the timber used is 8 N/mm 2 . The timber density is 600 kg/m3

Forces in the Purlin

Solution Assume a purlin cross sectional size of 50 x 125 mm i) Find an estimated self load w = 0.05 m x 0.125 m x 600 kg/m3 x 9.81 = 37 N/m Total dead load = 250 + 37 = 287 N/m ii) Find the components of the loads relative to the main axes wx = 200 N/m + 287 N/m cos 30 ° = 448.5 N/m wy = 287 N/m sin 30 ° = 143.5 N/m

Solution Contd. iii) Calculate the BM about each axis for a udl. The purlin is assumed to be a simple beam Mmax = w L 2 /8 Mmax x = wx L2 = 448.5 x 2.42 8 8 = 323 x 103 N mm Mmax y = wy L2 = 143.5 x 2.42 8 8 = 103 x 10 3 N mm

Solution Contd. iv) The actual stress in the timber must be less than the allowable stress. f = Mmax x + Mmax y < fw Zx Zy v) Try the assumed purlin size of 50 x 125 mm Zx = b d2 = 50 x 1252 = 130 x 10 3 mm3 6 6

Solution Concluded

4.2.3 Design Using the Universal Steel Beams

Example A steel beam used as a lintel over a door opening is required to span 4.5 m between centres of simple supports. The beam will carry a 220 mm thick and 3.2 m high brick wall, weighing 20 kN/m3 . Allowable bending stress is 165 N/mm2. Assume allowable shear stress of 100 N/mm2, E is 2 x 105 N/mm2. Assume self weight of the beam as 1.5 kN.

With Z = 221 cm3 and I = 2070 cm4 , From SDM, choose a UB 254 x 102 x 22 with Z = 225 .4 cm3 and I = 2863 cm4 Check for shear stress: Shear stress = Qmax D. t From Table 4.4. Q max = W /2 = 32.43 kN Shear stress = 32.43 x 103 N = 22.01 N/mm2 254 mm x 5.8 mm Since 22.01 N/mm2 < the allowable shear stress of 100 N/mm2 , ie. Beam is very satisfactory. USE UB 254 x 102 x 22

Composite Beams

4.3 DESIGN OF COLUMNS Columns are compression members but the manner in which they tend to fail and the amount of load which causes failure depend on: i) The material of which the column is made eg. a steel column can carry a greater load than timber column of similar cross-sectional size. ii) The shape of the cross-section of the column. A column having high c/s area compared to the height is likely to fail by crushing rather than by buckling.

Columns Contd. iii) The end conditions of the column. To account for buckling of slender columns, the allowable compressive strength is reduced by a factor k , which depends on the slenderness ratio and the material used. Pbw = k . cw . A where Pbw is the allowable load wrt buckling; k is the reduction factor which depends on the slenderness ratio and A is the cross-sectional area of the column.

4.3.2 Slenderness Ratio Slenderness ratio can be defined as: = k L = l r r  Where is slenderness ratio; k is effective length factor whose value depends on how the ends of the column are fixed; L is the length of the column; r is the radius of gyration (r = I/A and l is the effective length of the columns (k. l)

4.3.3 Types of End Conditions of a Column: Columns can either be (a) fixed in position nor direction (the weakest condition); (b) fixed in position but not in direction (pinned); (c) fixed in direction but not in position (d) fixed in position and in direction

4.3.4 Design of Axially Loaded Timber Columns Timber columns are designed with the following formulae: = k L and Pbw = k . cw. A r NB: In some building codes, a value of slenderness ratio in case of sawn timber is taken as l/b instead of l/r  

Example Design a timber column which is 3 m long with a compressive load of 15 kN. Allowable compressive stress ( cw) for the timber is 5.2 N/mm2, kp is 1.00

Note Actual load/allowable load = 15 kN/16.9 kN = 0.89 This ratio is all right and shows that the section is economical. A ratio of 0.85 to 1.00 is acceptable.

4.3.5 Design of Axially Loaded Steel Columns The allowable loads for steel with respect to buckling can be calculated in the same manner as for timber. The relationship between the slenderness ratio and the reduction factor ( k ) is slightly different (see Table 4.6).

Solution Concluded

4.3.7 Axially Loaded Concrete Columns Most building codes allow the use of plain concrete (no reinforcement) only in short columns ie. where the l/r ratio is < 15 . For l/r between 10 and 15, the allowable compressive strength must be reduced. The tables of figures relating to l/b in place of a true slenderness ratio are only approximate, since radii of gyration depend on both b and d values in the cross section and must be used with caution.

Example A concrete column, with an effective length of 4 m has a cross section of 300 x 400 mm. Calculate the allowable axial load, if a nominal concrete mix is 1:2:4 is to be used. Solution: Slenderness ratio, l/b = 4000/300 = 13.3 Hence Table 4.7, gives Pcc = 3.47 N/mm2 by interpolation. Pw = Pcc . A = 3.47 x 300 x 400 = 416.4 kN

4.3.8 Plain & Centrally Reinforced Concrete Walls Walls are designed in the same manner as columns, but there are a few differences. A wall is different from a column by having a length which is more than five times its thickness. Plain concrete walls should have a minimum thickness of 100 mm.

Plain and Reinforced Concrete Walls Contd. Where the load is eccentric, the wall must have centrally placed reinforcement of at least 0.2 % of the cross section if the eccentricity > 0.20. This reinforcement may not be included in the load carrying capacity of the wall.

Example Determine the maximum allowable load per metre of a 120 mm thick wall, with an effective height of 2.8 m and made from concrete grade C 15: (a) when the load is central and (b) when the load is eccentric by 20 mm.

4.4 DESIGN OF ROOF TRUSSES

Roof Trusses Contd. Steel and timber trusses are usually designed assuming pin-jointed members. In practice, timber trusses are assembled with bolts, nails or special connectors and steel trusses are bolted, riveted or welded. These rigid joint impose secondary stresses which are negligible and therefore not used in design.

4.4.2 Steps in Designing a Truss a) Select general layout of truss members and truss spacing b) Estimate external loads to be applied including self weight of truss, purlins and roof covering, together with wind loads. c) Determine the critical (worst combinations) loading. It is usual to consider dead loads alone, and then dead and imposed load combined.

Steps in Designing a Truss Contd. d) Analyse framework to find forces in members. e) Select material and section to provide in each member a stress value which does not exceed the permissible value.

4.4.2.1 Spacing and Layout Roof trusses should as far as possible be spaced to achieve a minimum of weight and economy of materials used in the total roof structure. For spans up to 20 m, the spacing of steel trusses is likely to be about 4 m, and in case of timber, 2m.

Spacing and Layout Contd. Short spans up to 8 m should have pitched timber rafters or light weight trusses either pitched or flat. Medium spans of 7 to 15 m or 16 m require truss frames designed of timber or steel. Long spans of over 16 m should if possible be broken into small units or the roofs should be designed by specialists.

Pitch or Slope of a Roof

Estimation of Roof Loads

Example Determine the critical forces for design for each of the members in the left hand of the truss shown above. Assume the following: Trusses are spaced 4 m on centres. The roof deck is of galvanised sheet weighing 6 kg/m2 . All purlins weigh 22kg/m. Openings constitute 20% of the wall surface. Calculate the panel loads.

Solution (a) Dead load i) Determine the panel area supported by one purlin = Distance between the purlins x spacing of trusses = 3.2 m x 4 m = 12.8 m2 ii) Calculate the roof deck load supported by one purlin = 12.8 m 2 x 6 kg/m 2 x 9.81 = 753.4 N = 0.75 kN. iii) Weight of each purlin = 22 kg/m x 4 m x 9.81 = 863.28 N = 0.86 kN

Solution Contd. Total dead load to be carried by truss = 0.75 + 0.86 kN = 1.61 kN iv)Estimate total truss weight per panel as 10 % of the total load to be carried = 0.16 kN v) Total dead load per panel point , P = 1.61 + 0.16 = 1.77 kN

Solution Contd.

Final Design Diagram

4.5 FOUNDATIONS AND FOOTINGS DESIGN 4.5.1 Introduction: Foundation is the part of the structure through which the load of the structure is transmitted to the ground. A combination of footing and foundation distributes the load on the bearing surface (the soil) and keeps the building level and plumb and reduces settling to a minimum. Footing and foundation are normally made of concrete, no matter the construction material.

Footing and Foundation Contd. Before design of footing and foundation can be made, the total load from the building as well as soil bearing characteristics should be determined.

Soil Bearing Capacity Strength of the soil required to resist the loads resting in it. This is after the top soil has been removed (See Table 5.6, FAO book for values of soil bearing capacities). Detailed investigations of the soil is not usually required for small scale buildings

Soil Bearing Capacities

4.5.3 Foundation Footings 4.5.3.1 Description: A footing is an enlarged base for a foundation designed to distribute the building load over a larger area of soil and to provide a firm, level surface for constructing the foundation wall. Foundation wall Footing

Footings and Foundation Contd. The footing is wider than the foundation wall because the soil's bearing stress is less than that of the material (concrete) of the wall e.g. concrete has a strength of about 1000 kN/m2 . A 1 : 3 : 5 ratio of cement, dry sand, and gravel is suggested for footings with 31 litres of water per 50 kg sack of cement.

Note Unlike the continuous wall footings, the pier and column footings are heavily loaded. It is very important to correctly estimate the proportion of building load to be carried by each pier or column. If wall footings are very lightly loaded, it is advisable to design any pier or column footings required for the building with approximately the same load per unit area. If any settling occurs, it should be uniform throughout.

Example For the building below, the loads are as follows: a) The roof framing plus the expected wind load = 130 kN b) The wall above the foundation is 0.9 kN/m c) The floor will be used for grain storage and will support as much as 7.3 kN/m2 . The floor structure is an additional 0.5 kN/m2 The foundation walls and piers are each 1 m high above the footing. The wall is 200 mm thick and the piers 300 mm square. The soil on the site is compacted clay in a well drained area. Find the size of the foundation and pier footing that will safely support the loads. Assume that the weight of the mass 1 kg approximately equals 10 N. The mass of concrete is 24 kN/m3.

Solution Note that each pier(column) carries 4/32 ie. 1/8 of total floor load. Each wall carries 7/32 of floor load ie. {(2 x 3) + 1/2 + 1/2} 1) The division of load on each foundation wall is as follows: a) Roof load = 50 % on each wall i.e. 50 % of 130 kN = 65 kN b) Wall load = for each side: 16 m x 0.9 kN/m = 14.4 kN c) Floor load = each side of wall carries 7/32 Total floor load = (7.3 + 0.5) x 16 x 8 = 998.4 kN i.e. floor load carried by each wall = 7/32 x 998 kN = 218.4 kN

Solution Contd.