COLORADO SPRINGS FIRE DEPARTMENT 2009 International Fire Code – Major Changes and Proposed Amendments Kris Cooper Deputy Fire Marshal September 22, 2010.

Slides:



Advertisements
Similar presentations
Facilities Management and Design Chapter 4 Safety and Security systems.
Advertisements

NFPA 72 and NFPA 101 Supervised Automatic Sprinkler System Overview
DEPARTMENT OF DEVELOPMENT SERVICES BUILDING DIVISION Ronald L. Lynn, Director/Building Official Gregory J. Franklin, Assistant Director Neil Burning, Manager.
Fire Protection Design for Healthcare Facilities: Beyond Building Code Compliance Scott Voelkerding, PE, CFPS Fire Protection Engineer September 16, 2010.
Ted “Smitty” Smith  I have included in the following slides some key sections from each of the codes you will primarily encounter on the test. I recommend.
 Please mute your line to reduce background noise  Do not put us on hold if you have background music on your hold line.  At the end of the presentation.
FCIA CODE EFFORTS FCIA Spring Conference 2003 By William E. Koffel, P.E. Koffel Associates, Inc.
Enhancements  Expanded fire safety and evacuation plan requirements  Periodic testing and inspection for sprinkler, standpipe and fire alarm systems.
High-Rise Hotels New Codes General Fire Safety Information Ted Erb Fire Prevention Officer Bellevue Fire Department April
Michigan Department of Licensing and Regulatory Affairs Bureau of Construction Codes.
N.F.P.A. 13R Justin Bohlmann FIR-204.
Doug Hohbein Chief Plans Examiner Nebraska Fire Marshal Agency
January 16, 2014 Brad Keyes, CHSP Changes to the 2014 Acute Care & Critical Access Hospital Manuals on Life Safety Compliance.
Assisted Living Communities: Changes & Challenges November 20, 2014 Central Georgia Technical College Macon, GA.
Capital City Fire/Rescue Fire Marshal’s Office. Sprinkler System Plans (Submit 3 sets of plans) Fire Suppression Systems Review apparatus and emergency.
2012 International Fire Code Adopted as the minimum fire safety standard by the State of Wyoming City of Sheridan must adopt the minimum standard to retain.
FALAR Part 3 – Post Construction  Compilation of  Maintenance records of fire protection/life safety equipment  Test records of fire protection/life.
Child Care Fire Safety Program North Carolina Fire Prevention Code 2000 International Fire Code with NC amendments. North Carolina Building Code Council.
WELCOME DBI & SFFD Meet the Pros October 11, 2007.
Emergency Action Plans
EGRESS AND FIRE PROTECTION
Health Facilities Planning Seminar Plan Review Division Irvin J. Poke, AIA, Chief Todd Y. Cordill, NCARB, Assistant Chief Providing for Michigan’s Safety.
Business Owners and Managers and the Fire Code
Church Administrators & Emergency Planning
PERFORMANCE & CODE ANALYSIS TIMBer Inc. ·Brooke Fedder · Marie Rottschaeffer· Izzie Molinuevo· Tena Pettit·
© 2012 Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code and the.
Building Codes and Interior Design
Governmental Constraints on Construction Chapter 2.
© 2008 Delmar, Cengage Learning Property Security, Emergency Response, and Fire Protection Systems Chapter 13.
Safety Training Presentation
Maximum Allowable Quantities and the Fire Hazard Analysis
State of Virginia’s Adoption Uniform Statewide Building Code –Adopts model codes by reference Family of I Codes 2003 edition NEC 2002 edition –Statewide.
Fire Safety By Alicia Civile and Alexandra Fernandez.
MINNESOTA CHAPTER AUTOMATIC FIRE ALARM ASSOCIATION Requirements of the 2003 Minnesota State Fire Code relating to Group R Occupancies September 14, 2006.
© 2008 Delmar, Cengage Learning Fire Protection Systems and The Model Code Process Chapter 2.
Add name of trust / organisation in box 1 and name of trainer in box 2. Delete THIS box.
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
Agenda SDFD – CEDMAT Program & Staff 2013 CA Fire Code
Area of Refuge It’s the Law!
Means of Egress Part 3 Chapter 4.
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
What you will learn in this session 1.The characteristics of fire, smoke and toxic fumes 2.Fire hazards involved in the working environment 3.Significant.
Work Area Method Level 3 Alterations – Chapter 9 prescribes requirements. 50% of Building Area Rule.
Means of Egress Don Ebert- Risk Manager (509)
Presented by John Lewandowski and Mike Larabel Inspection, Testing, and Maintenance of Kitchen Hood Systems Michigan Fire Inspectors Society Winter Educational.
KEK, 04/28/061 Safety Plan Assumptions Break out of fire in the Beam Tunnel is negligible Cables in the Service Tunnel is main fire load They are combustible.
Exercise #2 (part 2) Based on what you read in Chapter 4, determine if the corridors and exit doors meet the requirements for egress width, according to.
Public Safety Committee New Construction Dallas Fire Rescue Inspection and Life Safety Education Section Chief James Adams June 13, 2016.
NFPA Codes and Standards Contents 01 Introduction Who is the NFPA Making of NFPA Code or Standard 02 Development Process The Codes and Standards.
Carbon Monoxide Detection: Code and Legislation Updates
Fire Protection Systems Chapter 9 IBC 9th Edition Amendments
Hazardous materials: What to look for
2009 IBC Egress Issues in Commercial Buildings, May 25, 2011
Proposed Changes to the 2009 International Building & Fire Codes
CIHQ - All Rights Reserved 2017
THE IMPORTANCE OF DEVELOPING A FIRE STRATEGY FOR ANY PROJECT
City of Healdsburg Construction Codes Amendments & Adoption: 2016 Building Standard Codes Title 24 Parts 1 Thru International Property Maintenance.
Table of Contents for Subpart E Coverage and Definitions
Wilson Hall Fire Protection Features
ARCHITECTURAL SAFETY FEATURES –Exit Separations –Continuation of Exit Stairs from lower to upper floors –Discharge from Exits FIRE PROTECTION FEATURES.
Building and Fire Codes
Brad Keyes, CHSP HFAP Engineering Advisor Jamie Crouch, BSBM, MHA
General Requirements of NFPA 101
Ambulatory Health Care vs. Business Occupancy
Area of Refuge It’s the Law!
City Council Meeting November 14, 2016
Code Development & Adoption
National Fire Protection Association Update
Fire Alarm Practice Drill # 11 Denver Fire Department Journeyman Installer License Test © Ted Smith 2017.
Bella Vista Fire Department Procedures on Sprinkled Buildings
Presentation transcript:

COLORADO SPRINGS FIRE DEPARTMENT 2009 International Fire Code – Major Changes and Proposed Amendments Kris Cooper Deputy Fire Marshal September 22, 2010 "Protecting life and property today - creating a safer tomorrow"

Overview  Introduction to ICC Code Cycle  2009 IFC – Major Changes  2009 IBC – Major Changes of Interest to CSFD  CSFD Proposed Amendments  THIS PRESENTATION IS NOT ALL EMCOMPASING, IT IS ONLY A SUMMARY OF HIGHLIGHTS OF THE IFC, IBC AND PROPOSED AMENDMENTS.

ICC Code Cycle – 3 Years  Call For Committees  Proposed Changes Public Proposal Form  Code Development Hearings  Reports of Hearings  Final Action Hearings  Final Action Results

Local Code Cycle  Regulatory Agencies Review Codes  PPRBD and CSFD Meet  Review Committees Established CSFD Staff  Proposed Amendments Proposal Forms  Public Process  City Council Adoption

 IFC Significant Changes

Section 202, ,  Defines Ambulatory Health Care Facilities Group B occupancies used for outpatient surgery and similar activities that render patients incapable of self preservation Requires Sprinkler and Automatic Fire Detection Throughout

Section  Dangerous Building Placards  Information placards for fire fighters to identify hazards associated with vacant structures

311.5 continued Structural or Interior Hazards Exist Normal Structural Conditions Major Structural or Interior Hazards Exist, Exterior Operations Only Additional Markings: R/O Roof Opening, S/M Stairs Missing, F/E Fire Escapes, H/F Holes in Floor

Section  Requires crowd managers for assemblies or events where more than 1,000 people congregate. 1 crowd manager to every 250 occupants Assist with evacuation procedures Not intended to require dedicated staff

Section 404  Code now includes provisions for occupants who need assistance with evacuation. Previous CSFD amendment for “special needs occupants” Applies to emergency plans

Section  Lockdown plans for schools Required to be included in Fire and Life Safety Plans Required to be approved by the fire code official  CSFD is not going to require approval of the fire and life safety plans (amendment).

Section 508  Fire Command Center Room size increased from 96 square feet to 200 square feet with a minimum dimension of 10’ Layout must be approved by CSFD See for required features

Section 510 & Appendix J  Emergency responder radio coverage ALL buildings shall have approved radio coverage for emergency responders.  May require bi-directional amplifiers  This item is still being discussed.

Section  Portable Outdoor Gas-Fire Heating Appliances 5’ clearance to buildings and other combustibles Also see Section 307 for clearances of outdoor burning (50’), recreational fires (25’) and portable outdoor fireplaces (15’).

Outdoor Heating Appliances 5’ or manufacturer’s specifications15’ or manufacturer’s specifications

Section 607.3,  Fire Service access elevators Buildings greater than 120’ Adjacent to exit enclosure (stairway) Driven by 9/11

Section 608  Stationary battery systems Expended battery types  Lithium – Ion  Lithium Metal Polymer  Nickel cadmium  Nonrecombinant  Recombinant

Section  Frequency for Inspection of Kitchen Hoods – Table High Volume Cooking – 3 months  24 hour cooking operations Low Volume Cooking – 12 months  Churches, seasonal businesses Solid Fueled Cooking – 1 month  BBQ pits, smokers All Other Cooking Operations – 6 months

Section  E (Educational) Occupancies Reduces sprinkler threshold from 20,000 square feet to 12,000 square feet

Section  Requires sprinklers for the display and sale of upholstered furniture in M Occupancies, regardless of size of fire area No Specified Threshold Huge Implications for Plan Review Driven by Charleston Fire

Section 907  Complete re-write of the section  No major changes Side note: 2010 NFPA 72 now the National Fire Alarm and Signaling Code  Recognizes other alarm functions  Fire Alarm not necessarily priority signals  Mass Notification Systems

Section 909  Smoke Control Systems CSFD had previously amended this section to be more restrictive. Accepting code as written with this adoption.

Section  Protection of Fire Pump Enclosures Dedicate rooms High Rise  2 hour separation Non-High Rise  1 hour separation

Section  Minimum Egress Width No longer have different design width for sprinkled vs. non-sprinkled structures 0.3 inches per occupant for stairs 0.2 inches per occupant for all other means of egress Loss of any one means of egress shall not reduce the available egress width to less than 50% of required capacity.

Section , , &  Areas of Refuge Not required in buildings protected throughout with sprinklers Elevators now approved for occupant evacuation as a means of egress Two-way communication required for areas of refuge and evacuation elevators

Section  Electromagnetically locked egress doors Clarifies the use of magnetic locks on egress doors

Section  Exit Signs Electrically Powered Self-luminous Photo-luminescent  Must comply with UL 924 – Emergency Lighting and Power Equipment.

Section 1024  Luminous Egress Path Markings High Rise Structures Required in exit enclosures of new and existing buildings  CSFD not adopting retroactive application Required on hand rails, stair treads and landings

Luminous Egress Path Markings

Section  Provides requirements for dispensing Alcohol Blended Fuels Specific listing of equipment Signage requirements for facility identification Alcohol Blended Fuels: Including those containing 85% ethanol and 15% unleaded gas (E-85). Flammable liquids consisting of ethanol or other alcohols blended greater than 15% by volume

Chapter 24  Now treats tents, canopies and membrane structure the same Reasoning: Canopies can have walls added to become tents 2,400 square foot permit threshold (amendment)

Chapter 46  Combines requirements for existing buildings into one chapter Look at this closely as it contains significant retroactive requirements CSFD has amended this section with lots of deletions.

International Building Code  The following code sections are from the 2009 IBC These are fire related items or CSFD has a specific interest in them.

Section 419  Guidance on live work units Classified as R-2 Non-residential use up to 50%

Section  Marking and identification of fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions  Allows for easy identification of rated assemblies

Marking and Identification

Section  Stairwells can be pressurized or built with a vestibule Design will impact standpipe valve locations.

Section  Dead End Corridors Increase from 20’ to 50’ in B, E, F,I-1, M, R-1, R-2, R-4, S and U occupancies Must have NFPA 13 sprinkler system

Section  Elevator cars must be sixed to accommodate a 24” x 84” stretcher

Local Amendments  Local changes made to the code during the adoption process as a means to clarify, comply with City Code and/or Charter, or modify code requirements.  Based upon local practices, polices, procedures or interpretations.  Less is more approach

Chapter 1 - Administration  Changes made in order to be consistent with The Code of the City of Colorado Springs. Administrative Powers Penalties Fire Board of Appeals

Permits  Permits as listed in the code maintained as written Modified some hazmat permit threshold amounts Added permit amounts for electrolytes Added Work at Risk Permits

– Fire Lanes  Added a new permit for the construction of Fire Lanes Applies to alternative methods  Grass Pave  Gravel Pave

Alternative Fire Lanes

Fees  Reinspections Fees Cleaned up language where fees may apply to routine fire inspections  Subsequent review fees Added a provision for the collection of fees where plans are revised and or updated and require additional reviews beyond the initial approval

Section  Allows MSDS to be in electronic format  CSFD amendment to specify format and storage on thumb drive in Knox Box Microsoft Word 2000 or newer PDF

Section  Approved Contractors Going with 3 rd party testing Will include fire alarm, fire alarm monitoring contractors, water based fire suppression, portable fire extinguishers, special hazard systems and fire hydrants New state law for testing for all fire sprinkler installers  Unknown impact from state law

 Kitchen Fire Suppression Systems Added requirement to cut off power to any appliances under the hood or any power source that could be used to supply power to an appliance under the hood.

 Kitchen Hood Ventilation Added a new code section to require the exhaust to start and/or stay on upon activation of the fire suppression system. Prevents heat roll out from the hood that might activate sprinklers.

905.4  Standpipe Connections in Stairways Provides guidance where the standpipe valve will be located when the stairway is built with a vestibule per the IBC.

 Helistops and Heliports Added additional language to require design and construction to NFPA 407 and 418 in addition to the IBC.

 Medical Gas Systems Must be installed by Credentialed installers  ASSE 6010, 6015, 6020 & 6030

Chapter 47  NFPA Standards All NFPA Standards referenced in Chapter 47  Automatically adopted on January 1 of the year following the affective date of the standard.

Residential Sprinklers  International Residential Code Requires sprinklers in all dwelling units, to include 1 and 2 family dwellings Colorado Springs is not proposing adoption of this section  Each jurisdiction may evaluate this separately.

Timeframe  Mid September - October Public Process  November Present to City Council  January 1, 2011 Effective Date