Faults on DC Microgrids

Slides:



Advertisements
Similar presentations
CONDITIONS FOR SUCCESSFUL INTERRUPTION:
Advertisements

Fuel Cell Simulator System Martin Ordonez, Masters Candidate Supervisors: Dr. M. Tariq Iqbal Dr. John E. Quaicoe Faculty of Engineering and Applied Science.
WP3 High Availability Drives Electrical Machines and Drives Research Group University of Sheffield Dr. Georges El Murr
Project 1.3 Status Monitoring, Disturbance Detection, Diagnostics, and Protection for Intelligent Microgrids Dr Wilsun Xu C. Jiang,
Supercapacitor Energy Storage System for PV Power Generation
TestDrive Demo Electric Ship Onboard Power System OPAL-RT TECHNOLOGIES Montreal, Quebec, Canada EMS Rev. 001, March, 2009.
Effects of high penetration levels of photovoltaic generation Observations from field data Amir Toliyat, Alexis Kwasinski and Fabian Uriarte The University.
Transformer Testing Station Determining Sensitivity of a Relay to Inter-turn Faults on an Energized Power Transformer Sponsored by: Schweitzer Engineering.
Logic-level outputs can’t drive a motor directly. Solution: Relays –Relays allow one circuit to switch a second circuit –isolates circuit from potentially.
Conversion of energy from one form to another Creating useful energy for a certain task Can use any type of energy.
The Mechatronics Design Lab Course at the University of Calgary Presented June 2, 2003.
1 Lab Equipment. 2 TopicSlides DC Power Supply3-4 Digital Multimeter5-8 Function Generator9-12 Scope – basic controls13-20 Scope – cursors21-24 Scope.
EET Survey of Electronics Chapter 13 - Parallel Circuits.
1 © Alexis Kwasinski, 2012 Energy Storage In the past 2 classes we have discussed battery technologies and how their characteristics may or may not be.
Chapter 7 SYSTEM PROTECTION
Greenbench: A Benchmark for Observing Power Grid Vulnerability Under Data-Centric Threats Mingkui Wei, Wenye Wang Department of Electrical and Computer.
1 © Alexis Kwasinski, 2012 Introduction Field Excitation Q Synchronous generators Input: Mechanical power applied to the rotor shaft Field excitation to.
1 Fly-back Converter fall Basic Topology of a Fly-back Converter.
2012 Advisory Panel Oil and Gas Applications Ray Zowarka Center for Electromechanics The University of Texas at Austin 12/4/2012.
1 11 A review of wind energy technologies part two. Adviser : Dr. Yuan-Kang Wu Student : Po-Kai Lin Date :
EPR ‘Fundamentals of Calculation of Earth Potential Rise in the Underground Power Distribution Cable Network’ by Ashok K. Parsotam (1997) available free.
AFCI Reaction to Utility Events. CenterPoint Energy 35 KV Distribution Capacitor Bank – Switched through an automated system.
North East Pacific Time-series Underwater Networked Experiment (NEPTUNE): Power System Design, Modeling and Analysis Aditya Upadhye.
ELECTRICAL ENGINEERING: PRINCIPLES AND APPLICATIONS, Third Edition, by Allan R. Hambley, ©2005 Pearson Education, Inc. Chapter 16 DC Machines.
Motor Testing (Motor Only)
Smart Grid- An Introduction
Parallel dc Circuits.
EE 462L dc and ac Power Distribution Systems Fall 2008.
POWER QUALITY.
Lateef Taiwo, Biju Shrestha (PhD Candidate), P. Novak (PhD Candidate), and David Wetz, Ph.D Department of Electrical Engineering, The University of Texas.
New proposed BU circuit and control logic design University of Washington.
MUEV Phase III By: Kevin Jaris & Nathan Golick. Introduction Petroleum is a finite resource. Demand for clean energy is driving the increase in the production.
Cells in Series and Parallel (page 310) Cells in Series and Parallel Dry cells can be connected together into two basic types of circuits: series.
1 Critical Mission Support Through Energy Security Susan Van Scoyoc Concurrent Technologies Corporation 16 August 2012 Energy Huntsville Meeting Huntsville,
Neptune BU Switching Circuit diagram and operations.
Rate in the Electrical System. 1. What is the prime mover in the electric system? - voltage 2. What is electric rate? - amount of charge that flows through.
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Lab 1 Breadboard and Measurement Techniques Tom Rebold.
Tchuidjan Roger, PhD Electrical Engineer 1 Connection of disturbing loads in micro-grids National Advanced Polytechnique Institute of Yaounde - Cameroon.
The Probe: Measurement Accuracy Begins at the Tip  Attenuation –The ratio of the probe’s input signal amplitude to the output signal amplitude..  Bandwidth.
1. Capacitor and Voltage Doubler 2 Basic construction of capacitor 3.
NEPTUNE Power Low Voltage Circuit Fall 2003 Quarterly Meeting Tim McGinnis Sept 11-12, 2003.
What is Mechatronics? The portmanteau "Mechatronics" was first coined by Mr. Tetsuro Mori, a senior engineer of the Japanese company Yaskawa, in 1969.
Electrical Current and Circuits How Electricity Gets To Where It Is Going.
Closed Circuits In applications requiring the use of current, electrical components are arranged in the form of a circuit. A circuit is defined as a path.
Control Engineering. Introduction What we will discuss in this introduction: – What is control engineering? – What are the main types of control systems?
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
Power Electronics and Switch Mode Power Supply
MVDC Collaboration MVDC Issues and Viability of Red Demo in Philadelphia.
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
MVDC Research at The University of Texas Presented by: A. Ouroua For ESRDC Team members at The University of Texas at Austin Philadelphia, September 17,
Protection and Relay Schemes
Sub Station.
Lab I Critique Theory section should provide basis for all calculations Comparison of theory to measurement – do the math Present results & sample calculations.
The Clutch Control Strategy of EMCVT in AC Power Generation System
IG BASED WINDFARMS USING STATCOM
PSCAD models.
MECH 373 Instrumentation and Measurements
What is meant by ‘Preventive Monitoring’?
Chapter 7 System Protection
Bernie Lesieutre UW-Madison
A Simulation Model for Crowbarring Thyristor Devices
From Lecture1 vi , ii vo , io Power Processor Controller Source Load
Energy Cluster.
آشنائی با کوره های قوس الکتريکی DC و مقايسه آن با کوره های AC
Lab For the following simple switch mode power supply:
Agenda Introduction of Protective Relays
Energy Cluster.
Electrical Current & Circuits
Bernie Lesieutre UW-Madison
Presentation transcript:

Faults on DC Microgrids -Hunter Estes, graduate PhD student, NSF Fellow The University of Texas at Austin Department of Electrical & Computer Engineering Research Advisors: Dr. Alexis Kwasinski & Dr. Robert Hebner Research Group: Center for Electromechanics http://www.utexas.edu/research/cem/dcmicrogridfaultexperiments.html

Background The ONR’s next-generation, AES (all-electric ship) platform can be viewed as an isolated microgrid. Many terrestrial microgrids are DC-based, and DC is one of the voltage platforms currently being evaluated by the ESRDC. While DC microgrids offer many advantages, a prime area of concern relates to faults. Thus, quick fault recognition, identification, and control strategy / fault management are a key research focus. The end-goal for DC systems is quick fault remediation and/or branch isolation of an affected circuit, while impact on the remaining system (ride through) is minimized. DC systems will likely need more intelligence built into their system for successful fault management (i.e. DC smart grid)

Microgrid Fault Study A microgrid was constructed in Center for Electromechanics power lab to meet such testing protocol. This will allow for both connected & island-mode operation for the purposes of testing. The key component of fault testing was the design of a horizontal fault mechanism. This allows for controlled separation or connection through the use of an isolated stepper motor or a pneumatically-driven actuator.

Fault Testing Focus The focus of this research is to experimentally determine the characteristics of horizontal series & parallel faults in DC systems, and to explore the effects they have in terms of local and system disturbances. Note: Faults will also be studied in AC systems, as a basis for comparison Study: DC (280 – 750V) vs. AC systems of “quasi-equivalent” parameters Monitor: AC & DC fault currents, gap voltages, arc fault transients, power dissipated, bus disturbances, duration, re-strikes, loading effects Resolution: 50 – 0.5 μs data capture rates, 12 bit resolution Goals: DC arc modeling, arc fault detection, fault clearing strategies, equipment designs, & safety recommendations

Series Fault Test Results DC horiz. series fault transients AC horiz. series fault transients

DC Parallel Fault Test Results (preliminary) DC horizontal parallel fault transients

Discussion For series faults, DC systems did not show many fast-acting transients (i.e. spikes) as compared to AC systems. However, DC series faults were an order of magnitude longer in duration, and often damaged electrode structures, locally. DC series arcing faults are difficult to detect, for their voltages and currents are very similar to pre-arcing conditions. However, equation modeling for dynamic, DC series faults has been accomplished. AC series faults dissipated within a few cycles from the point of electrode discontinuity. However, re-ignitions were possible. Additionally, fast-acting transients were observed in both the gap voltage and current waveforms. With magnitudes up to four times the bus voltage, these spikes may be cause for alarm as this would exceed voltage ratings for various passive components within system power electronics. DC parallel faults seem to show some disturbances at lower levels. However, testing will continue to higher thresholds to observe such effects in more detail. These will also be compared to AC systems.