1 ASPE Presentation March 20, 2012 By David J. Thomas, MSCE, PE Fire Protection & Code Topics.

Slides:



Advertisements
Similar presentations
Sprinkler Systems and Standpipe Operations
Advertisements

Classroom Safety. Fire & Life Requirements as per State Education Dept The following list relates to the classrooms and adjacent areas. They are provided.
7 | Means of Egress (Life Safety Code)
Safety Training Safety First. EXITS All exit doors shall be maintained in operable condition. Exit doors shall not be locked, chained, bolted, barred,
Fire Protection Systems
Fire-Resistive Construction (2nd part)
International Mechanical Codes Scald Protection. – Where a combination potable water-heating and space-heating system requires water for space.
State Fire Marshal Question and Answer Session with the Louisiana Automatic Fire Alarm Association March 19, 1999.
Fire Precautionary Arrangements Presented by Mick Leadbetter Fire Safety Adviser.
Buildings and Structures 2 Fixed Installations Aim To provide students with information to allow them to recognise the types of fixed fire protection.
1 Lincolnshire Fire & Rescue Training Centre FIXED INSTALLATIONS DRY AND WET RISERS COMPETENCE STATEMENT 373.
Unit 3 Fire Suppression Section 1 Detection and Alarm Systems.
Wet Sprinkler Systems Identifying components of, and inspection and testing procedures.
Water Based Sprinkler Systems 2 major different types of water sprinkler systems Wet pipe system Dry pipe system.
Ted “Smitty” Smith  I have included in the following slides some key sections from each of the codes you will primarily encounter on the test. I recommend.
North Idaho Emergency Services Academy. Objectives Types of fire service laddersTypes of fire service ladders Ladder termsLadder terms Ladder raising.
Stairways and Ladders 1926 Subpart X - Stairways and Ladders
Accessibility.  A building code is a set of rules that specify the minimum acceptable level of safety for buildings. The main purpose of building codes.
High-Rise Hotels New Codes General Fire Safety Information Ted Erb Fire Prevention Officer Bellevue Fire Department April
Michigan Department of Licensing and Regulatory Affairs Bureau of Construction Codes.
N.F.P.A. 13R Justin Bohlmann FIR-204.
Elevators & Fire Alarm Systems: Understanding Interface Requirements Presented by: Antonio Torres- North Central Regional Sales Manager.
The Life Safety Surveyor Facility Tour
State of Kuwait 3rd Intl Fire & Safety Conference & Expo 4-6 March 2014 Building Performance for Emergency Response Incident Examination and Tactical Response.
Zone Valves.
FIRE SAFETY TRAINING THE LOSS PREVENTION UNIT OF THE OFFICE OF RISK MANAGEMENT.
Walking-Working Surfaces
Automatic Sprinkler System. Importance of Sprinklers First line of protection – small fires Enhanced protection Business protection – less interruption.
3-1 NFIRS 3 Structure Fire Module. 3-2 ObjectivesObjectives The participants will be able to: –describe when the Structure Fire Module is to be used.
WATER FOR FIRE PROTECTION (Chapter 26) Basic factors of fire – Rapid oxidation of combustible materials – A combination of oxygen, fuel, and heat is required.
Purpose of Standpipe and Hose Systems
 Familiarization of system  Locations of: Hydrants FDC Knox Box FACP Sprinkler Riser Room Liquid Oxygen  Unique Fire Protection Element Smoke Curtain.
Residential Fire Sprinkler Systems. Goal Provide entry level firefighters with an understanding of residential fire sprinkler system Provide entry level.
CVFD Training – Fire Protection Systems
Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National.
STEAM HEATING.
Module C Sprinkler systems (4-20)
State of Georgia BASIC FIRE FIGHTER TRAINING COURSE
Business Owners and Managers and the Fire Code
PERFORMANCE & CODE ANALYSIS TIMBer Inc. ·Brooke Fedder · Marie Rottschaeffer· Izzie Molinuevo· Tena Pettit·
© 2012 Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code and the.
Flammable and Combustible Liquids
Means of Egress Chapter 4.
Flammable and Combustible Liquids. Introduction !The two primary hazards associated with flammable and combustible liquids are explosion and fire !Safe.
CHAPTER 12 Copyright © 2007 Thomson Delmar Learning 12.1 Protective Systems.
Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
ID 308 Construction + Materials IV: Construction Documents Prof. Brody Endicott College Systems Coordination.
Fire Protection Systems Chapter 6. Fire Protection Systems Most of the time you will work with an electrical engineer or fire-protection designer to coordinate.
Fire Safety in the Theater By: Haley Patton Patti Ott Beaney Corral
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
Area of Refuge It’s the Law!
Means of Egress Part 3 Chapter 4.
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
Lab Safety and Emergency Procedures. The Number One Rule In All Emergency Situations Don’t Panic, Move Quickly and Quietly.
Mayor’s Office on Disability City and County of San Francisco Discussion of Common Design and Construction Errors.
Exercise #2 (part 2) Based on what you read in Chapter 4, determine if the corridors and exit doors meet the requirements for egress width, according to.
Flammable Liquids Directorate of Training and Education
Elevator Fire Service Mode Basic Operations Prepared by: Lt. Rob Fisher – L72C.
Safety Rule #1 Open flames are not allowed without first obtaining a permit. The exception to this rule is during a period of closely supervised instructions,
CEN 180: Civil Engineering Drawing II
Fire Alarm Systems for Emergency Operations of Elevators
Wilson Hall Fire Protection Features
ARCHITECTURAL SAFETY FEATURES –Exit Separations –Continuation of Exit Stairs from lower to upper floors –Discharge from Exits FIRE PROTECTION FEATURES.
NFIRS 3 Structure Fire Module
February 2019.
Area of Refuge It’s the Law!
Building standards Mr. Da Silva.
Bella Vista Fire Department Procedures on Sprinkled Buildings
Presentation transcript:

1 ASPE Presentation March 20, 2012 By David J. Thomas, MSCE, PE Fire Protection & Code Topics

2 Websites ons/pfm/pfm_main.htm ons/pfm/pfm_main.htm nty//permit/WIZ_APWELCOME.asp nty//permit/WIZ_APWELCOME.asp

3 Topics To be covered, per request from ASPE: Fire apparatus access Fire hydrant location with reference to FDC Fire fighter access Equipment/utility identification Elevators – sprinklers and alarms Sprinkler system – division/zoning Standpipe Systems – FHV location, FHV additional locations Gaseous Agent Suppression Systems/Pre-Action Sprinklers Exterior sprinkler alarms New Code Adoptions Equipment shutdown/fire alarm requirements

4 Access Fire apparatus access: To within 100 feet of main entrance (vehicle) FXCO PFM J(1). If > 5 stories or > 50 feet height of structure, then front and rear access required. PFM J(2). Premises numbers: on front, visible. IFC FXCO County Code 102

5 FDC FDC/Hydrant location: FDC on street front, address side of buildingPFM C(9), IFC NHS threadsIBC , NFPA 14-07:4.7 Covering hydrant within 100 feet of FDC PFM K Note: One Siamese per building, per given address. A building is what is between fire walls and has a particular address.

6 Typical FDC

7 Access Again Fire Fighter Access (to Equipment) Exterior doors accessibleIFC Stairway access to roof (> or = 4 stories w roof slope <4/12) IFC Equipment room identification IFC 509.1

8 Labels Equipment/utility identification Rated construction, shaftways: marking required IBC AC, sprinklers, mechanical rooms, signage IFC Electrical room labels, IFC Stairwell markings, IBC , FXCO Code Reference Package

9 Elevators IF NO SPRINKLERS IN BUILDING, THEN NO SHUNT TRIP. IF NOT A SPRINKLERED BUILDING, THEN NO SPRINKLERS IN EMR.

10 Sprinklers/Shafts IF combustible fluids (hydraulic), then one sprinkler, bottom of shaft <= 24” AFF. NFPA 13-07, If ASME A17.1 cab, then no sprinklers at top of shaft, unless, (If motor in hoistway, then sprinkler at top.)13-07,

11 Elevators/Sprinklers ASME A17.1 requirements: : risers and returns to be outside of hoistway Branch lines in hoistway to supply not more than one floor level : if sprinklers in machine room and/or hoistway, then shunt trip, except if only sprinklers in pit at < or = 24”AFF, then no shunt trip Smoke detectors not to be used for shunt trip.

12 Shunt Trip NFPA 72-07: : elevator shutdown – heat detectors within 2 feet of sprinkler head : shunt trip circuit to have power monitoring supervision : Heat detectors shall be connected to fire alarm system. See for recall, etc.

13 Sprinkler Systems: Zoning/Divisions See FXCO Code Ref Pkg.: Risers (sprinkler take offs) to be interconnected per floor). OSY, check, flow at each take-off (see NFPA72-07, , surges not to initiate alarms). Sprinkler zones = 52K square feet (light or ordinary hazard) Fire alarm zones = 22.5K square feet. Hence use two in one nesting. Sprinklers alarm by floor.

14 Sprinkler Take offs

15 Water Supply Water supply: can supply multiple buildings, but one address = one FDC = one building. FIRE DEPARTMENT RESPONDS TO AN ADDRESS.

16 Standpipes/FHVs IBC (all): DON’T LEAVE HOME WITHOUT IT. Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 1. In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, unless otherwise approved by the building official. 2. On each side of the wall adjacent to the exit opening of a horizontal exit. (See exception, IBC 905.4(3)) 3. In every exit passageway at the entrance from the exit passageway to other areas of a building.

17 IBC In covered mall buildings, adjacent to each exterior public entrance to the mall and adjacent to each entrance from an exit passageway or exit corridor to the mall. 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a hose connection located either on the roof or at the highest landing of stairways with stair access to the roof. An additional hose connection shall be provided at the top of the most hydraulically remote standpipe for testing purposes

18 IBC Where the most remote portion of a non-sprinklered floor or story is more than 150 feet ( mm) from a hose connection or the most remote portion of a sprinklered floor or story is more than 200 feet ( mm) from a hose connection, the building official is authorized to require that additional hose connections be provided in approved locations. The above is from IBC 2009.

19 Position of FHV: NFPA 14-07, : “At the highest intermediate landing …” FHV shall be located on the intermediate landing such that, when hose is moved upward to the floor level above, the hose does not cross the intermediate landing. This means that you have to show upward and downward directions on the stairs, with arrows, on the plumbing plans, or no one will be able to evaluate your plans.

20 Standpipes and Sprinkler Take Offs in Stairwells – At Intermediate landing –as above – Roof hydrant – what is this? If a flat roof, the FHVs on roof, on top of stair (standpipe extends through roof). If stair goes to roof, then dual FHVs at topmost landing. Note: 905.4(5) is expanded on at 14-00, 5-3.2(e): “on the roof where stairways do not access the roof.” – Both sides horizontal exit (see IBC 09 exception) – Topmost landing/remote location/dual valves – 200/150 foot coverage rule – Malls/entry areas

21 Standpipe Diagram

22 Intermediate Landing Issues – Can’t interfere with exit required width. Period. Swing stairwell required width arc on landing, stay out of arc. – Must be located in proper corner of landing. Looking down from floor landing above, you must see the FHV in the corner. Why? Hose must come up along wall to allow people to come down and exit the building along the guardrail side of the stair. This is critical. Operational need of fire department. Code Reference: NFPA 14-07,

23 Intermediate Landing Issues Sizing is critical. Check diameters of pipe. E.g. 6 inch schedule 10 pipe is actually inches outside diameter. FHV outlet usually projects about inches out from standpipe = out to end of FHV valve turning stem. Gloved hand needs 4-6 inches between valve itself and the wall for clearance. Overhead clearance. Have to have 80 inches per IBC Be careful here of pipe sprigs down the wall to get to the intermediate landing

24 Sprinkler Take Offs See NFPA 13 for sample take off at 13-07, Fig A (a). Note that we put a check valve after the indicating valve to avoid water flow flutter (water flow flutter is prohibited by NFPA 72-07, ). Note: Test valve, sight glass, orifice, drain pipe. Drain piping goes over to sectional drain which runs down alongside standpipe. If you have pressure reducing valves in the building, then the drain pipe has to be 3 inches in diameter to test those vales. This drain and its location can be critical in the space on a landing.

25 Sprinkler Take offs, again

26 Sprinkler Take Offs – Penetrations of the wall of the stair where the sprinkler pipe goes out to the floor – must be protected with through penetration fire stop. See IBC 713. – If sprinkler take off piped vertically (which it can be), then have both head room issues and projections into exit width issues. If piped horizontally, primary issue is headroom.

27 Other Issues FHVs in cabinets, etc. Sizing is the critical issue, plus compatibility with the wall rating in which the cabinet is placed. Most commercial cabinets will have proper sizing, but some show FHV piped with valve output horizontal. Valve output should be placed either vertically downward or at most at 45 degrees from the vertical. This is to prevent a failed coupling from injuring the firefighter or the public. Normal orientation for all FHVs in FXCO is straight down, for safety reasons.

28 Other Issues Cont. Anchors. These are important, if there are long runs of 2.5 inch pipe to the FHV (as in malls). Can also be important if FHVs in stairwells are run from the floor landing standpipe down to the intermediate landing. Interconnection of standpipes: IBC : In buildings where more than one standpipe is provided, the standpipes shall be interconnected in accordance with NFPA 14. (See NFPA 14-07, 7.5.1; IBC ).

29 Riser Control Valves 14-07, Valves shall be provided to allow isolation of a standpipe without interrupting the supply to other standpipes from the same source of supply. (This includes dry standpipes, as in garages) Listed indicating valves shall be provided at the standpipe for controlling branch lines for remote hose stations. Why ? You must be able to isolate portions of the system for maintenance without rendering the rest of the system inoperative. Supervision of standpipe valves. For dry standpipes (garages) have lock and chain. Otherwise, have tamper switches.

30 Risers/Alarms – Flow switches: NFPA 14-07, 5.6.1, Water flow alarms. FXCO requires at the base of each wet standpipe a flow switch. This identifies the location of water flowing to a fire in a combined system. – See diagrams of whole systems at NFPA 14-07, A.7.1

31 Gaseous Agents/Sprinklers Clean agents are for equipment. See NFPA , A See FXCO Code Ref Pkg: if a fully sprinklered building, then it remains so. We do not dump gas. Pre-action can be of any listed type. IBC is for telecommunications buildings only. A building with other tenants is not such a building.

32 Exterior Sprinkler Alarms: IBC One bell or horn on outside of the sprinkler room on exterior face of structure.

33 Code Editions The above has given the references for the USBC 2009 editions. As of March 1, 2012, the one-year grace period for use of IBC 2006 has ended and all plans must be IBC 2009.

34 EPOs/Shutoffs The only place where an EPO is required is NEC 645. Regular service disconnects at (NEC 2002). National Fuel Gas code states: Service Shutoff at 5.12, Emergency shutoff at (multiply fed systems). NFPA 13 requires “valve controlling water supplies.”