Testing Fiber Optic Media Lab Last Update 2014.07.25 1.1.0 Copyright 2013 - 2014 Kenneth M. Chipps Ph.D. www.chipps.com 1.

Slides:



Advertisements
Similar presentations
How to Use a Fluke DTX Cable Tester Last Update
Advertisements

111 © 2002, Cisco Systems, Inc. All rights reserved. Finish Phase Overview Testing Troubleshooting Certification Documentation.
JED Microprocessors Pty Ltd Presenting the JED T430 low-cost Projector Controllers Nov 22nd, 2009.
Session 4: Termination and Splices. 2 FO Connectors Specifications Specifications Loss Repeatability Environment (temp, humidity, vibration, etc.) Reliability.
Copyright 2008 Kenneth M. Chipps Ph.D. How to Terminate a Corning Unicam Connector Last Update
Copyright Kenneth M. Chipps Ph.D. FLSM Last Update
Demarc Last Update Copyright Kenneth M. Chipps Ph.D. 1.
Copyright Kenneth M. Chipps Ph.D. How to Use a Spectrum Analyzer Wi-Spy Version Last Update
Copyright Kenneth M. Chipps Ph.D. Testing Copper Media Last Update
Pursuit of Better testing Instrument Let's go in the grandway......
Copyright 2014 Kenneth M. Chipps Ph.D. Network Management Using Sensors to Monitor Network Equipment Rooms Last Update
Fiber Optics BASIC FIBER OPTIC LINK.
Optical Interfaces Lab Last Update Copyright 2014 Kenneth M. Chipps Ph.D. 1.
ATM Frame Last Update Copyright 2011 Kenneth M. Chipps Ph.D. 1.
1 Telecom Cabling Testing and cable certification.
111 © 2002, Cisco Systems, Inc. All rights reserved. Trim out phase steps Cutting cables to length Labeling cables Dressing cables Terminating cables Installing.
Copyright 2014 Kenneth M. Chipps Ph.D. Live Streaming Lab Last Update
Fiber Optic Cable Installation Indoors Last Update Copyright Kenneth M. Chipps Ph.D. 1.
TESTING MULTIMODE FIBER
1 Fiber Optic Measurement Technique Piotr Turowicz Poznan Supercomputing and Networking Center Training Session Kiev 9-10 October.
Static Routing Last Update Copyright Kenneth M. Chipps Ph.D.
1 Fiber Optics FIBER OPTIC PATCH PANELS. 2 Fiber Optics Just like our copper cable plant the fiber cable plant incorporates many of the same hardware.
Thick v Thin Access Points Lab Last Update Copyright 2014 Kenneth M. Chipps Ph.D.
Chapter 8 Basic System Design.
Testing Fiber Optic Media Last Update
The OSI and TCP/IP Models Last Update Copyright 2009 Kenneth M. Chipps Ph.D.
Fiber Optics MECHANICAL SPLICES.
How to Build a CAN Last Update Copyright Kenneth M. Chipps PhD 1.
1 Fiber Optics FIBER PERFORMANCE. 2 Fiber Optics The purity of optical fiber is critical for the best transmission of an optical signal inside a fiber.
NETE 0510 Presented by Dr.Apichan Kanjanavapastit
Link Budget Calculation
Poznan Supercomputing and Networking Center
Fiber Optics LINK LOSS BUDGET.
Copyright 2010 Kenneth M. Chipps Ph.D. How To Pass the CCNA Test Last Update
Wireless Media Last Update Copyright Kenneth M. Chipps Ph.D. 1.
Copyright Kenneth M. Chipps Ph.D. 1 How To Do VLSM Last Update
Copyright 2008 Kenneth M. Chipps Ph.D. How to Use the 3M Mechanical Splice Tool Last Update
Cisco 1 - Networking Basics Perrine. J Page 19/3/2015 Chapter 3 Which of the following correctly describes the type of signal that the network media carries?
Copyright Kenneth M. Chipps Ph.D. Data Link Layer Last Update
Terminating Wireless Media Last Update Copyright Kenneth M. Chipps Ph.D. 1.
Chapter 2.  Types of Network  Circuit Switched & Packet Switched  Signaling Techniques  Baseband & Broadband  Interference  Transmission Medium.
Lab How to Use WANem Last Update Copyright 2011 Kenneth M. Chipps Ph.D. 1.
Powerline Distribution Last Update Copyright Kenneth M. Chipps Ph.D. 1.
Hosted Virtualization Lab Last Update Copyright Kenneth M. Chipps Ph.D.
O ptical R eturn L oss testing using KI 7340 series Loss Tester Kingfisher International PTY LTD V
Chapter 8 Basic System Design. System factors for designing from scratch: Design Verification FactorAvailable choices Type of fiberSingle mode, multimode,
The Routing Table Last Update Copyright Kenneth M. Chipps Ph.D.
Physics 2225: Working With Electronic Equipment Purpose  Learn how to use basic electronic equipment: Digital multi meter Oscilloscope Function generator.
1 Module 3 TERAWAVE CONFIDENTIAL – DO NOT COPY Terawave Communications, Inc. Network Planning Course Module 3 PON Physical Network Engineering.
Copyright 2008 Kenneth M. Chipps Ph.D. Controlling Flow Last Update
How to Build a MAN Last Update Copyright Kenenth M. Chipps PhD 1.
Disk Interfaces Last Update Copyright Kenneth M. Chipps Ph.D. 1.
Copyright Kenneth M. Chipps Ph.D. Ethernet Frame Format Last Update
COPPER AND FIBER REVIEW
Dark Fiber Last Update Copyright Kenneth M. Chipps Ph.D. 1.
Attenuation is the loss of signal strength, for example, when cables exceed a maximum length. This means that a 1 bit voltage signal loses amplitude as.
Update on Optical Fibre issues Rainer Schwemmer. Key figures Minimum required bandwidth: 32 Tbit/s –# of 100 Gigabit/s links > 320, # of 40 Gigabit/s.
Day 13 Intro to MANs and WANs. MANs Cover a larger distance than LANs –Typically multiple buildings, office park Usually in the shape of a ring –Typically.
Optical Interfaces Last Update Copyright Kenneth M. Chipps Ph.D. 1.
Example of a LAN Last Update Copyright 2009 Kenneth M. Chipps Ph.D.
How to Build a LAN Last Update Copyright 2007 Kenneth M. Chipps PhD 1.
INTRODUCTION TO NETWORK CABLING
More stuff to know… MODULE 10
Chapter 7 Basic System Design.
Hubs Bridges Switches Last Update
Introduction to Computers
Chapter 7 Basic System Design.
Copyright 2008 Kenneth M. Chipps Ph.D.
Guidelines for Fiber Optic Design and Installation
Characterizing FOX Demonstrator Test Setups for LArDPS to FEX Modules at CERN RuthAnn Gregory.
Presentation transcript:

Testing Fiber Optic Media Lab Last Update Copyright Kenneth M. Chipps Ph.D. 1

Testing Fiber Optic Media The basic test of a fiber optic cable based link is loss or attenuation This loss can be measured automatically by using a calculated loss limit or manually by just observing the power measured at the end of the cable Copyright Kenneth M. Chipps Ph.D. 2

Testing Fiber Optic Media The automatic method requires an OLTS with this capability built-in such as the Fluke DTX CableAnalyzer and SmartRemote set The manual method requires an OLTS with a power source and a power meter The Fluke DTX CableAnalyzer and SimpliFiber set does this Copyright Kenneth M. Chipps Ph.D. 3

Loss Limit Let’s first look at how the acceptable loss is calculated Many fiber optic cable testers such as the Fluke DTX will calculate the maximum loss that could occur for the link to still work For example in this test report the Loss Limit is 1.67 Why is that Copyright Kenneth M. Chipps Ph.D. 4

Test Report Copyright Kenneth M. Chipps Ph.D. 5

Loss Limit In this case as the test report shows the length of the cable is 156 feet The standard loss for 62.5 multimode fiber optic cable is 3.5 dB per kilometer which is dB of loss per foot 156 feet times dBs per foot comes to.17 dB of loss due to attenuation in the cable Copyright Kenneth M. Chipps Ph.D. 6

Loss Limit It is assumed in this case by the DTX that there will be two connectors in the path since the test method selected was Method B Method B assumes two connectors The standard maximum loss for a 62.5 multimode fiber optic cable connector is.75 dB, which as we will see is a very high value Copyright Kenneth M. Chipps Ph.D. 7

Loss Limit For two connectors this is 1.50 dBs.17 plus.75 plus.75 is 1.67 So the computed limit of loss that can be tolerated for this link to pass is 1.67 If the measured loss is found to be higher than this, we need to find out why and fix it Copyright Kenneth M. Chipps Ph.D. 8

Loss Limit Now if we actually calculated this Loss Limit using these standard values for each part of the link under test in this example the Loss Limit would be 4.67 dBs broken down this way DTX Main – 1 Meter Patch Cable – 150 Roll of 62.5 Fiber Optic Cable – 1 Meter Patch Cable – DTX Remote The link looks like this Copyright Kenneth M. Chipps Ph.D. 9

Loss Limit Connector.75 MainOutputPatchFiber.0035 Connector.75 Connector.75 Roll of FiberFiber.17 Connector.75 Connector.75 RemoteInputPatchFiber.0035 Connector.75 Total Loss4.67 Copyright Kenneth M. Chipps Ph.D. 10

Loss Limit If we put a basic light source at the other end of the link instead of the SmartRemote, and then measure the received power for this link we find it is This means the real loss is.82 Why would there be such a large difference between the expected loss of 4.67 and the actual loss of.82 Copyright Kenneth M. Chipps Ph.D. 11

Loss Limit It seems the standard loss figures for connectors are way too high Corning for example states that the loss one should expect from a connector such as this is.1 as seen here Copyright Kenneth M. Chipps Ph.D. 12

Loss Limit Copyright Kenneth M. Chipps Ph.D. 13

Loss Limit Copyright Kenneth M. Chipps Ph.D. 14

Loss Limit If we adjust the table for these specification figures the Loss Limit now looks like this Copyright Kenneth M. Chipps Ph.D. 15

Loss Limit Connector.1 MainOutputPatchFiber.0035 Connector.1 Connector.1 Roll of Fiber150 Feet62.5Fiber.17 Connector.1 Connector.1 RemoteInputPatchFiber.0035 Connector.1 Total Loss.77 Copyright Kenneth M. Chipps Ph.D. 16

Loss Limit Now this is much closer to the value we measured of.82 The difference between the realistic Loss Limit calculated using the published specifications for these components and the loss actually found in the link is.05 Regardless of what caused the difference it is so small a value it can be ignored as insignificant Copyright Kenneth M. Chipps Ph.D. 17

Loss Limit This is likely due to measurement error, more loss somewhere than the specifications state, dirt on end faces, or gaps between one or more of the connection ends Copyright Kenneth M. Chipps Ph.D. 18

So What The next question you should be asking yourself is - is this amount of received power good, bad, or what Further, just how sloppy can I really be in the installation Just how much loss can I measure without it causing a problem Copyright Kenneth M. Chipps Ph.D. 19

So What To answer this we must look at the specifications of the receiving port at the far end of the link How much power must it receive at a minimum to receive data Copyright Kenneth M. Chipps Ph.D. 20

Power Budget The power budget is the difference between the Launch or Transmit Power which is the energy level of the light as it leaves the transmitter and the Receive Sensitivity or Power of the receiving device which is the minimum energy required for the fiber receiver to detect an incoming signal Copyright Kenneth M. Chipps Ph.D. 21

Power Budget The Power Budget then is simply the result of subtracting the Receive Sensitivity from the Launch Power For example for a Cisco SFP being used on each end of a link such as this –GLC-SX-MM SFP –WS-G5484 –For 1000BASE-SX –Using 850 nm Copyright Kenneth M. Chipps Ph.D. 22

Power Budget Minimum Transmitter Power -3 Minimum Receiver Sensitivity -17 Power Budget of -3 minus –17 or 14 dB Copyright Kenneth M. Chipps Ph.D. 23

So What Why do we care The Power Budget is just a term used to describe the total amount of light energy available for a certain link The Power Budget serves as a useful estimation to determine if sufficient optical power will remain on the receiver side of an optical link Copyright Kenneth M. Chipps Ph.D. 24

So What Why might sufficient optical power not be received at the far end of a link The Power Budget then also tells us how much loss we can tolerate in the link’s components such as the fiber attenuation, connector induced loss, dirt on end faces, and so on Copyright Kenneth M. Chipps Ph.D. 25

So What So in this case for a link of unknown length with an unknown number of splices and connectors and an unknown amount of dirt we have 14 dBs in our pocket to spend on this sort of stuff In our example above for a link made up of DTX Main – 1 Meter Patch Cable – 150 Roll of 62.5 Fiber Optic Cable – 1 Meter Patch Cable – DTX Remote Copyright Kenneth M. Chipps Ph.D. 26

So What We measured the real loss as.82 We then have some 13 dBs to spend on adding more splices, connectors, dirt, a longer cable to extend the link, and so on For a typical installation we are unlikely to add anything to this link as why would we have calculated the expected loss at.77 in the first place if we expected to add devices later Copyright Kenneth M. Chipps Ph.D. 27

So What What we can spend these 13 dBs on is for junk on the end faces of the various connectors in the link In this case 6 connectors or end faces For each one of these we could tolerate an average of 1.11 dBs of crud covering the core Just how dirty does a end face need to be to produce 1.11 dBs of loss Copyright Kenneth M. Chipps Ph.D. 28

So What Dirt and other crud is commonly mentioned as causing loss but no one ever provides sample loss numbers for the various types of crud that could block the signal Copyright Kenneth M. Chipps Ph.D. 29

So What Cisco says in one document that a 1micrometer dust particle on a single- mode core can block up to 1% of the light based on 0.05 dB of loss Fluke in a BICSI presentation says the EPA says that typical dust particles in the office are from 2 to 10 microns in size Copyright Kenneth M. Chipps Ph.D. 30

So What 62.5 fiber is going to be able to still connect with a lot of dust particles if the loss for each one on singlemode fiber is.05 dB as 62.5 end faces are going to have a lot more surface area available to handle these particles Copyright Kenneth M. Chipps Ph.D. 31

So What If we just use the singlemode loss factor per dust particle of.05 dB we have at least room for 134 of these pesky little dust particles spread among six connectors before the link fails In short keep the connections clean and tight, but do not obsess over it Copyright Kenneth M. Chipps Ph.D. 32

The Test Let’s now perform a test to see how this is done We will do two types of tests –Automatic test using the DTX CableAnalyzer and SmartRemote –Manual test using the DTX CableAnalyzer and SimpliFiber light source Copyright Kenneth M. Chipps Ph.D. 33

Select the Link Type Regardless of whether the automatic or manual test is used the type of link being tested must be setup in the CableAnalyzer Copyright Kenneth M. Chipps Ph.D. 34

Select the Link Type In this case to do this select Setup Select Fiber Loss –In Tab 1 Select Fiber Loss Press enter to select the Test Limit –Select TIA568C Backbone MM Select the Fiber Type –Select Multimode 62.5 MBW=200 Select the Remote End Source –Select SmartRemote Copyright Kenneth M. Chipps Ph.D. 35

Select the Link Type –In Tab 2 Select Test Method Method B –Select Number of Adaptors 2 –As we will be plugging into the link for the actual test –Thus there will be 6 adaptors in total –Two are accounted for at each end by setting the Test Method to Method B –The other 2 - one at each end of the link under test - are accounted for here Copyright Kenneth M. Chipps Ph.D. 36

Select the Link Type Copyright Kenneth M. Chipps Ph.D. 37

Select the Link Type Copyright Kenneth M. Chipps Ph.D. 38

Select the Link Type Copyright Kenneth M. Chipps Ph.D. 39

Automatic Test The two steps for an automatic test are –Set the reference –Perform the test Copyright Kenneth M. Chipps Ph.D. 40

Set the Reference What color boot goes to which input or output depends on how the patch cables are made In this lab we are using a green patch cable at the CableAnalyzer end and a blue patch cable at the SmartRemote end The boots of these are both color coded so that red goes to red and black goes to black Copyright Kenneth M. Chipps Ph.D. 41

Set the Reference Regardless of the color of anything it does matter where the mandrels are They are always at the output port of each unit Therefore, in this lab connect the two units to each other in this manner Copyright Kenneth M. Chipps Ph.D. 42

Set the Reference Copyright Kenneth M. Chipps Ph.D OUTPUT INPUT REMOTE MAIN GRAY MANDREL GRAY MANDREL INPUT

Set the Reference With the cables connected as shown, on the CableAnalyzer select Special Functions Select Set Reference Press Enter Verify the connections Press Test Copyright Kenneth M. Chipps Ph.D. 44

Set the Reference Copyright Kenneth M. Chipps Ph.D. 45

Set the Reference Copyright Kenneth M. Chipps Ph.D. 46

Set the Reference Copyright Kenneth M. Chipps Ph.D. 47

Set the Reference The result as displayed on the screen is Copyright Kenneth M. Chipps Ph.D. 48

Set the Reference Copyright Kenneth M. Chipps Ph.D. 49

Set the Reference Press Ok Copyright Kenneth M. Chipps Ph.D. 50

Automatic Test To perform the automatic test Move the switch to AutoTest In Room 227 connect the cables as shown next DO NOT disconnect the output port cables from the OLTS Copyright Kenneth M. Chipps Ph.D. 51

General Connection Diagram Copyright Kenneth M. Chipps Ph.D. 52

Room 227 Fiber Optic Cable Backbone Loss Test Connection Diagram INPUT OUTPUT INPUT WALL PORTPATCH PANEL PORT REMOTE MAIN Copyright Kenneth M. Chipps Ph.D. 53

Room 227 Setup Copyright Kenneth M. Chipps Ph.D. 54

Room 227 Setup Copyright Kenneth M. Chipps Ph.D. 55

Room 227 Setup Copyright Kenneth M. Chipps Ph.D. 56

Room 227 Setup Copyright Kenneth M. Chipps Ph.D. 57

Room 227 Setup Copyright Kenneth M. Chipps Ph.D. 58

Automatic Test Press Test See if the test passed or failed A pass will look like this Copyright Kenneth M. Chipps Ph.D. 59

Room 226 Test Result Copyright Kenneth M. Chipps Ph.D. 60

Room 227 Test Result Copyright Kenneth M. Chipps Ph.D. 61

Manual Test Let’s see next how to do the manual test where a known amount of power is sent into a link, and then at the far end of the link the power received is measured If as discussed above this received level is high enough for the fiber modules to send and receive data then the link as installed can be considered to have passed Copyright Kenneth M. Chipps Ph.D. 62

Manual Test For this test we will use a 150 foot roll of 62.5 fiber optic cable We will need to calculate the actual expected loss before running the test so that we can compare it to the test results It will be up to us to then decide if the link passed or failed For this calculation we can just pull the figures from above down here Copyright Kenneth M. Chipps Ph.D. 63

Loss Limit Connector.1 MainOutputPatchFiber.0035 Connector.1 Connector.1 Roll of Fiber150 Feet62.5Fiber.17 Connector.1 Connector.1 RemoteInputPatchFiber.0035 Connector.1 Total Loss.77 Copyright Kenneth M. Chipps Ph.D. 64

Loss Limit As the table shows the loss we expect to find for this link is.77 dB We are now ready to measure the actual loss of this link Copyright Kenneth M. Chipps Ph.D. 65

Manual Test The two steps for a manual test are –Set the reference –Perform the test Copyright Kenneth M. Chipps Ph.D. 66

Set the Reference What color boot goes to which input or output depends on how the patch cables are made In this lab we are using a blue patch cable only to set the reference and then both the green and blue cables for the test Copyright Kenneth M. Chipps Ph.D. 67

Set the Reference Regardless of the color of anything it does matter where the mandrel goes It is always at the output port of each unit Therefore, in this lab connect the two units to each other in this manner since the only power source is the remote end SimpliFiber unit Copyright Kenneth M. Chipps Ph.D. 68

SimpliFiber Copyright Kenneth M. Chipps Ph.D. 69

SimpliFiber Copyright Kenneth M. Chipps Ph.D. 70

SimpliFiber Copyright Kenneth M. Chipps Ph.D. 71

SimpliFiber Select CW – Continuous Wave using button 3 Mode The red light will stay lit Select 850 nm using button 7 mode Copyright Kenneth M. Chipps Ph.D. 72

Set the Reference INPUTOUTPUTOUTUTINPUT SIMPLIFIBER MAIN GRAY MANDREL Copyright Kenneth M. Chipps Ph.D. 73

Set the Reference Connections Change the Remote End Setup from Smart Remote to Far End Source Copyright Kenneth M. Chipps Ph.D. 74

Set the Reference Copyright Kenneth M. Chipps Ph.D. 75

Set the Reference Copyright Kenneth M. Chipps Ph.D. 76

Set the Reference With the cables connected as shown on the CableAnalyzer select Special Functions Select Set Reference Press Enter Verify the connections Press Test Copyright Kenneth M. Chipps Ph.D. 77

Set the Reference Copyright Kenneth M. Chipps Ph.D. 78

Set the Reference The result as displayed on the screen is Copyright Kenneth M. Chipps Ph.D. 79

Set the Reference Copyright Kenneth M. Chipps Ph.D. 80

Set the Reference Press Ok Copyright Kenneth M. Chipps Ph.D. 81

Manual Test When using the SimpliFiber each cable must be tested one at a time To carry out the test connect the cables in this manner Copyright Kenneth M. Chipps Ph.D. 82

Manual Test Copyright Kenneth M. Chipps Ph.D INPUTOUTPUTINPUT SIMPLIFIBER MAIN GRAY MANDREL OUTPUT

Manual Test The AutoTest function of the CableAnalyzer can be used just as it was for the automatic test or the Power Meter function of the CableAnalyzer can be used This is what we will do in this case Copyright Kenneth M. Chipps Ph.D. 84

Manual Test Select Monitor Select Power Meter Select Test Select 850 nm Press Test The result is a real time display of the power level received by the CableAnalyzer The received power is dB Copyright Kenneth M. Chipps Ph.D. 85

Manual Test Now compare this received power level of to the expected power level which is minus.77 or So in this case we have.45 dB of unexpected and unexplained loss Do we need to worry about this.45 dB Copyright Kenneth M. Chipps Ph.D. 86

Manual Test To determine this we first need to see what level of power the device at the end of the link needs to receive in order to send and receive data over this link As we saw above in this example that value is -17 So we have enough room as there is a difference of 1.82 Copyright Kenneth M. Chipps Ph.D. 87

Manual Test Copyright Kenneth M. Chipps Ph.D. 88

Manual Test Copyright Kenneth M. Chipps Ph.D. 89

Manual Test Copyright Kenneth M. Chipps Ph.D. 90

Fiber Optic Cable Testing In this lab we have seen how to perform both an automatic and a manual test of multimode cable such as would be used for a backbone link Copyright Kenneth M. Chipps Ph.D. 91