Field Challenges with DCV Systems Dr. Andrey Livchak, Derek Schrock and Jimmy Sandusky Halton Group Americas www.halton.com.

Slides:



Advertisements
Similar presentations
TOUR OF NIST MANUFACTURED RESEARCH HOUSE Andy Persily, Steve Nabinger, Steve Emmerich, Cindy Howard Reed Building and Fire Research Laboratory National.
Advertisements

Restaurants Can Take a Bite Out of Energy Costs a.
Energy Savings Impacts of the Advanced Energy Design Guide: Small Office Buildings Bing Liu, P.E. Research Engineer Pacific Northwest National Laboratory.
Carrier Controls Demand Controlled Ventilation. Comfort = Temperature + Ventilation Comfort Is More Than Just The Right Temperature… Ventilation Control.
Controlling the amount of ventilation to a space based on demand Reset based on occupancy: Use carbon dioxide sensors to track space CO2 levels and raise.
100% Outside Air and Dehumidification Management
Demand Ventilation Control Systems for Commercial Kitchens NEBB February 24, 2012 Presented By: Mike Dean.
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
Learning Outcomes Upon completion of this training one should be able to: Identify open loop and closed loop campus-type hydronic water system applications.
University of Iowa Indoor Practice Facility Outside-the-box HVAC Lincoln Pearce, PE – KJWW Engineering David Hahn – University of Iowa Chilled Water Plant.
1 Modeling of HVAC System for Controls Optimization Using Modelica Wangda Zuo 1, Michael Wetter 2 1 Department of Civil, Architectural and Environmental.
T OPPORTUNITIES FOR ENERGY EFFICIENCY AT TRIBAL GAMING FACILITIES.
EARLIER KITCHENS PRESENT DAY KITCHEN Common misconceptions of kitchen ventilation. In a commercial kitchen the prime concern of the owners, designers,
Engineer Presentation
Energy Saving DDC Control Strategies
NARAGHI HALL 3 rd FLOOR VENTILATION MANAGEMENT IMPROVEMENT BEST PRACTICE AWARD HVAC DESIGN/RETROFIT 2014 CALIFORNIA HIGHER EDUCATION SUSTAINABILITY CONFERENCE.
Energy Recovery System Hadi Fattah Chris Korkuch Scott Lacey Ryan Neary Colin O’Neill.
Energy Management with the use of an Intelligent Building Management System.
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Blower Door Basics WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY.
UTSW Thermal Energy Plants, Power Generation and Electrical System What do we do to meet the Emission Reduction, Energy usage Reduction and Electrical.
Optimal Fan Speed Control for Thermal Management of Servers UMass-Amherst Green Computing Seminar September 21 st, 2009.
Lecture Objectives: Learn about automatic control Use life-cycle cost analysis integrated in eQUEST.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
© American Standard Inc Fan Pressure Optimization The Trane Company.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee November 16, 2011 Mira Vowles, P.E., CEM.
Energy Auditing Techniques for Small Commercial Facilities 2011 Ryan Stroupe, Pacific Energy Center Jim Kelsey P.E., kW Engineering Sean Harleman, kW Engineering.
EvergreenEcon.com Heat Pump Water Heater Model Validation, Market Progress Assessment, and Process Evaluation RTF HPWH Sub-Committee Meeting October 15,
Constant Volume Regulators
SDB Demand-Controlled Ventilation: Preliminary Experiments Jay Taneja Software Defined Buildings Kickoff January 11 th, 2013.
Improved Precision Leading to Improved Energy Efficiency Edward Decker AE 790 – Intelligent Buildings June 6, 2006.
November 2004 Low Hanging Fruit Low Cost Energy Efficiency Opportunities in Cleanrooms.
EvergreenEcon.com ESA 2011 Impact Evaluation Draft Report Public Workshop #2 August 7, 2013 Presented By: Steve Grover, President.
Energy Trust of Oregon Small Commercial HVAC Pilot Program Stellar Processes December 15, 2009.
Sawyer Environmental Changes Mechanical Engineering Department Capstone Amy R. Dan H. Colby C. Brittany P. Richard G. 1.
RTU Savings Research Project RTU Savings Research Project: Findings and Recommendations Regional Technical Forum February 3, 2009 Mark Cherniack Howard.
PRESENTED BY: J.MIKE TYSON S.RAVIKUMAR S.SAKTHI M.SATHISHKUMAR.
VAV Box Control Loop The purpose of the VAV Box control loop is to adjust airflow through the box to maintain a space temperature. The difference between.
1 Lamp operating factor Published lumen output is based on laboratory conditions Voltage  Rated at line voltage of 115V Standard reactor ballast  Electromagnetic.
Grocery VSD Measure Deemed Savings Reid Hart, PE & Ken Anderson September 28, 2010.
Energy Plus & Open Studio Class
Objectives Finish DOAS Control Terminology Types of controllers
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
VRF Applications in PNW RTF RTUG Meeting October 26, 2011 Kevin Campbell Reid Hart, PE Technical Research Group.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Performance Tested HVAC Presentation to the RTF January 5, 2010.
Optimum Performance of Radiator Space Heating Systems Connected to District Heating Networks via Heat Exchangers Patrick Ljunggren, Janusz Wollerstrand.
Lecture Objectives: Define the final project Deliverables and Grading policy Analyze factors that influence accuracy of our modeling study Learn about.
HVAC – Air Handling Unit Heating Ventilating AC =Cooling HVAC – Basic Terms hQ = 200,000 Btu/h CO2 20 cfm/ pers 50 people 1000 cfm cQ assume to = 20 tr.
All content in this presentation is protected – © 2008 American Power Conversion Corporation Row Cooling.
Copyright © 2015 Optimum Energy LLC. All Rights Reserved. Proprietary & Confidential Incorporating Energy Conservation Strategies into University Research.
7/15/2002PP.AFD.09 1 of 43 Yaskawa Electric America Variable Frequency Drives In HVAC Applications.
Heat Pump Water Heaters: Interior, Ducted Installations Presentation to the Regional Technical Forum December 13, 2011 Ben Larson, Ecotope
Combustion Control based on Flame Ionization Application in Condensing Heating Appliances by: Martin Kiefer 07 June 2012 Venue: EF5.B: WOC5 Gas Quality.
Group 31 Presented by: Yanlin Zhou &Yueqi Ni ECE 445 Senior Design May 1, 2016.
Location: Rockler Headquarters, Medina, MNRTUs: 1 Founded in 1954, Rockler Woodworking & Hardware is a specialty store dedicated to bringing woodworking.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Wega & Wega Power chilled beams
Welcome to the Colorado Restaurant Association Pikes Peak Chapter Energy Efficiency in the Restaurant Industry.
Halton reference / Hilton Bucharest
Lesson 23 Appendix C Exhaust Calculation
STEAMERS GROEN.
Lecture Objectives: Finish with HVAC systems
Chilled Beam Performance:
HCB 3-Chap 19A: All-Air Systems_Single Zone
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Exhaust Hood and Makeup Air Optimization
Manual D Duct Sizes Room Cooling CFM % Total CFM Heating CFM Kitchen GR Dining Bed Bed 3.
Weather and Your Restaurant’s Operational Costs
Minimizing Heating & Cooling Costs
Presented by Mike Zacharias
Presentation transcript:

Field Challenges with DCV Systems Dr. Andrey Livchak, Derek Schrock and Jimmy Sandusky Halton Group Americas

Overview One of the key challenges of implementing DCV systems in the field is to ensure that the hoods are operating at capture and containment (C&C) airflows when the appliances are in a cooking mode. Data is presented on how different appliances can require additional detection methods to ensure that the hood is running at a proper airflow. Secondly, a case study is presented on the design challenge of how to incorporate a DCV system in a restaurant which has a combination of hoods with dedicated exhaust fans and hoods that share exhaust fans; and how to optimize the energy consumption of these systems.

DCV Testing with Appliances Testing conducted with a range of appliances installed under a hood with various simulated DCV control schemes: – Exhaust Temperature + Cooking Activity Sensor – Exhaust Temperature Only (Operating on a Curve) – Exhaust Temperature Only (Operating at a Fixed Exhaust Set-Point)

DCV with cooking activity sensor Two types of cooking activity sensors are available on the market: – one uses infrared light beam across the hood to detect visible smoke or stream associated with the beginning of cooking process – another uses infrared temperature sensors to continuously monitor surface temperature of appliances under the hood

DCV Control Details Temperature + Cooking Activity Sensor (system with infrared temperature sensors was used in this study) – A curve was utilized to vary exhaust airflow rate proportional to exhaust temperature. – A secondary sensor was installed to detect the onset of cooking process and override temperature signal to drive exhaust fan to 100%. – Minimum exhaust fan speed defaulted to 40% of design exhaust airflow.

DCV Control Details Temperature Only – Two Configurations: Curve Based Constant Exhaust Temperature Set-point. – 90, 100 and 130°F – Minimum exhaust fan speed defaulted to 80% of design exhaust airflow for systems with constant set-point.

DCV Control Details Temperature Curve Utilized in DCV Control Algorithms

DCV Testing Configuration Exhaust Hood – 72” Canopy Hood, Mounted at 80” AFF. – Exhaust Temperature Sensor Mounted in Collar

DCV Testing Configuration Appliances & Food Product ApplianceFuel SourceLoadingDesign airflow Open-Vat Fryer, Single Fat Natural GasFrozen French Fries 1000 cfm Griddle, Thermostatically Controlled Natural GasFrozen Hamburger Patties 1000 cfm Char-BroilerNatural GasFrozen Hamburger Patties 1800 cfm Pressure Fryer, Single Vat ElectricityFrozen Chicken Patties 1000 cfm Re-Thermalizer, Dual Vat Natural GasFrozen Taco Meat 1000 cfm

Open Vat Fryer Testing

Griddle Testing

Rethermalizer Testing

Pressure Fryer Testing

Char-Broiler Testing

System Response Time Comparison

DCV Testing Comparison of time to reach design airflow. Appliance Time from start of cooking (seconds) when design airflow reached Temp + Cooking Activity Sensor Temperature Only Curve Constant Temperature, SP=90°F Constant Temperature, SP=100°F Constant Temperature, SP=130°F Open Vat Fryer23NA297NA Griddle35174NA181NA Rethermalizer26NA Pressure fryer28NA Char-Broiler23NA

DCV Case Study Evaluated Site Configuration – Four canopy hoods attached to single exhaust fan – Demand control ventilation installed – Design Exhaust Airflow = 11,290 CFM – Balancing dampers installed on each hood to independently regulate exhaust proportional to demand

DCV Case Study Monitored Data

DCV Case Study System Simulated without Dampers or Other Means to Independently Regulate Exhaust for Each Hood when one of the hoods was cooking mode, the whole system was at design airflow – Minimum Airflow Rate Assumed to be 80% of Design.

DCV Case Study Energy Impacts System Estimated Savings Heating [Therms] Cooling [kWh] Exhaust Fan [kWh] Supply Fan [kWh] DCV w/ Dampers 1,307 7,425 38,075 12,692 DCV w/o Dampers 436 2,475 15,705 5,235 Difference 871 4,950 22,370 7,457 Location: Seattle, WA Operating Hours: 24/7 Heating EFF: 90% COP: 2.93

Conclusions 1.Secondary cooking activity sensors are needed in addition to exhaust temperature to minimize hood spillage  Ideally DCV controller receives signal directly from cooking appliances’ controllers 2.Response time from exhaust temperature only systems is over 2 minutes for fryer and griddle resulting in hood spillage. 3.Set-points for temperature only systems need to be calibrated for a given application (appliance combination). They need to be reset for winter and summer to account for variation in kitchen space temperature unless space temperature sensor is used for automatic reset 4.Systems that couple multiple hoods to a single exhaust fan need a means of independently regulating exhaust airflow for each hood to maximize energy savings

Questions? Derek Schrock