Presenters: Bob Kilgore Matthew McReynolds Brenna Goode CHEMISTRY BUILDING RCX.

Slides:



Advertisements
Similar presentations
A CASE STUDY in actual energy conservation
Advertisements

Sustainable School Design Creating Healthy, High Performance School Facilities Presented by Stephen M. Koontz, Energy Services Leader, Tampa Bay Trane.
HVAC Basics Bin Yan HVAC – Heating, Ventilation, Air-conditioning.
Energy Efficient Heating Ventilating and Air Conditioning.
TESTING AND BALANCING IN HEALTHCARE FACILITIES. What is Test & Balance The art of establishing air and water flows to meet design criteria. Total System.
Improve Facility Operation through Commissioning-A Case Study Mingsheng Liu, Ph.D., P. E. University of Nebraska.
Intro to Enersol What is Retro-commissioning? Define Benefits of Retro-commissioning Define Retro-commissioning Process Discuss Retro-commissioning Findings.
HEALTHCARE BUILDING AUTOMATION
WebStat™ Programming and Configuration of Thermostats.
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
100% Outside Air and Dehumidification Management
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
KE2 Evaporator Efficiency
Innovative Air Distribution for Healthcare Facilities.
University of Iowa Indoor Practice Facility Outside-the-box HVAC Lincoln Pearce, PE – KJWW Engineering David Hahn – University of Iowa Chilled Water Plant.
Smart Devices. Smart Buildings. Smart Business The Potential for DCx Technology Enabled HVAC Operation Scot Duncan, P.E.
1.What is a Smart Lab 2.Background on Aircuity Advisor Services 3.Software requirements 4.Login and Navigation 5.Fume hood sash management 6.Next steps.
ASHRAE Club Project VAV Fumehood Retrofit - Engineering III Building Engineering III Building 40,000 gsf Completed 2002 Designed and constructed in two.
Energy Saving DDC Control Strategies
NARAGHI HALL 3 rd FLOOR VENTILATION MANAGEMENT IMPROVEMENT BEST PRACTICE AWARD HVAC DESIGN/RETROFIT 2014 CALIFORNIA HIGHER EDUCATION SUSTAINABILITY CONFERENCE.
Energy Management with the use of an Intelligent Building Management System.
Best Direction System Ltd.
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
 Install new air cooled high efficiency screw chiller (variable speed)  Install new fan coils with ECM motors and low temperature heating coils and proper.
MAXIMIZING DORM ENERGY SAVINGS WITH INTELLIGENT HVAC CONTROLS AASHE CONFERENCE, OCTOBER 11, 2011 AASHE CONFERENCE, OCTOBER 11, 2011.
Lecture 15: Air Primary Loops and Controls Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the.
PSU Building Thermal and Mechanical Systems Laboratory Environment A/E Kurt M. Shank, M.S. & Stanley A. Mumma, Ph.D., P.E. College of Engineering Department.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
Examples of Commissioning Cost Savings Commissioning for Sustained Building Performance September 29, 2011 Marriott Birmingham, AL.
Important variables Water: Air: Conversion:
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
Temperature Control Loop
Phoenix Convention Center Phoenix, Arizona Targeted E4 Re-Tuning at GSA Facilities Integrated Energy Low/No Cost Solutions through Building Automation.
Lindab Solus - Simply the natural choice.... lindab | comfort Chilled beam revolution! + Save up to 45 % cooling energy!* + Installation and investment.
MBCx Projects – Programs, Process, and Results Soda, Tan, Shields and Wurster David Jump, Ph.D., P.E., Matt Denny, P.E. Quantum Energy Services & Technologies,
Re-Commissioning of the Water Cooling System at Université de Sherbrooke Department of Buildings June 2008.
Sawyer Environmental Changes Mechanical Engineering Department Capstone Amy R. Dan H. Colby C. Brittany P. Richard G. 1.
VAV Box Control Loop The purpose of the VAV Box control loop is to adjust airflow through the box to maintain a space temperature. The difference between.
The key to comfort and reduced fuel use for all heating systems.
Lecture Objectives: Clarify issues related to eQUEST –for midterm project Learn more about various HVAC - economizer - heat recovery Discuss about the.
Using Technology to Manage Energy Bob Schoch-Director of Business Administration Tom Schneider-Supervisor of Operations.
How Facilities Can Help Commitment by facilities director Facilities energy committee Energy officer position Include conservation commitment in: Strategic.
October 2014 Rod Rabold Vice President, SERBCA Board of Directors SERBCA TECH TALK BAS Control Strategies for Energy Savings in Buildings SOUTHEAST.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Jesse A. Fisher Mechanical Option Spring 2005 Riverpark Corporate Center, Phase 1 Salt Lake City, Utah.
Objectives Talk about the final projects Guest Speaker Discuss HW2 and HW3 problems.
Test and Balancing Functional Performance Test Presented by: John Shelander and Dan Acri.
Objectives Propose residential system related final project –Compare VAV systems with DOAS systems.
Copyright © 2015 Optimum Energy LLC. All Rights Reserved. Proprietary & Confidential Incorporating Energy Conservation Strategies into University Research.
Michael Reilly, Jr. – Mechanical Option Advisor – James Freihaut, PhD & Dustin Eplee The Pennsylvania State University Nassau Community College Life Sciences.
The key to comfort and reduced fuel use for all heating and cooling The key to comfort and reduced fuel use for all heating and cooling.
AstraZeneca R&D Boston Waltham Energy Reduction Initiative 2016 Green Labs Symposium.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Integrate Lighting, Daylighting and HVAC Control in the Laboratory Room Duane Ranski Siemens Industry Inc.
Sean Weber Energy Engineer
The Data Center Challenge
Whole Building Retro-Commissioning at BU’s Photonics Center
Objectives Talk about the final projects Discuss HW2 and HW3 problems
Session 10 –roundtable – Labs and Controls Systems
By: John D. Villani, P.E., LEED AP, QCxP, CEM, GBE
Story of No-Cost Energy Savings at Ohio Union
HVAC Basics Arkan Arzesh HVAC – Heating, Ventilation, Air-conditioning.
Brian Wallingford, Applications Engineer
Chilled Beam Performance:
HCB 3-Chap 19A: All-Air Systems_Single Zone
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Objective Revie the Cooling Cycle Learn about air distribution systems
Presentation transcript:

Presenters: Bob Kilgore Matthew McReynolds Brenna Goode CHEMISTRY BUILDING RCX

Project History

The Challenge? PH 1 Starts PH 2 Ends FLOOD

Utility & Energy Use 5,827,190 kWh 7,945,346 kWh 26% Increase

Utility & Energy Use 36,467 MMbtu 40,956 MMbtu 11% Decrease

15,828 MMbtu 46,900 MMbtu 196% Increase Utility & Energy Use

37,268 MMbtu 46,900 MMbtu 26% Difference Due to Excess Flow Utility & Energy Use

How Did Chemistry Compare? PH 1 Starts PH 2 Ends FLOOD Labs21 Benchmark Data Utility & Energy Use

Fume Hood Testing Processes Over 250 Hoods Currently Operational Verify sash velocities at multiple positions Compared to most recent EHS testing reports Verify current hood use

AHU Testing It’s All about building trust Verify actuator extents and mid-point stroke positions Verify sensor installation and accuracy When we can trust the BAS to give us good data, we utilize the trends to analyze the systems for deficiencies and opportunities This is also the basis for a Continuous Commissioning program Processes

Improve Averaging Sensor Coverage T T T T ExistingRecommended Improvement Improves sensing and therefore control (adding temp sensors) Reduces risk of freezing coils (adding freeze stats) It’s pretty cheap insurance! Findings

Single point of control for heat recovery creates one satisfied AHU and three unsatisfied AHUs AHU Heat Recovery Control Findings

Chilled Water System Investigation Findings AHU Control Sequences AHU Coil Capacities Pumping Capacity Historical Weather Data

Chilled Water System Findings AHU Control Sequences Reduce Discharge Air Temperature Based on Return/Exhaust Humidity Level. +3°F 55°F 52°F 50°F 47°F

Chilled Water System Findings AHU Coil Capacities Modeling showed Air Handling Units are driven beyond coil capacity. Coils sized for 51.6 °F 89 °F / 78 °F Program Demands 47 °F 89 °F / 78 °F Coil Physically can’t meet DAT requirements

Chilled Water System Pumping Capacity Building Chilled Water Users Findings

Chilled Water System Historical Weather data Data From University of Iowa Chilled water Plant PI System Findings

Historical Weather data

AHU-NW Discharge Air Temperature Sensor Discharge air sensor was found to be reporting 5°F high. Resulting in Cooling Coil being overdriven and Heating Coil Under driven. Findings

Sensor Calibration Northwest AHU chilled water valve was consistently at 100% while the discharge air temperature struggled to maintain set point. Unit is running at approximately 60% full design capacity. Findings Unit is running at approximately 60% full design capacity.

ECM-11 Fix AHU-NW Discharge Air Temperature Sensor Recalibrate DAT sensor to read true value of conditioned air. This measure was implemented during study. Recommendations

Results ECM-11

Results

Recommendations

Uncertainty of purpose Unrealistic solutions Overly burdensome implementation Impact on research and instrumentation Impact on the instructional mission User Concerns

7 of 13 ECMs required coordination with building users and lab equipment: Recommendations

reduce the reheat load: reset the AHU Discharge air set points upward when dehumidification is not necessary ECM-4 Discharge Air Temperature set Point Reset Room NumberSpace Use Description Teaching Laboratory W254Lab Equipment Room W76Lab Analytical Room W182Research Lab W174Research Lab E127A-1Core Collegiate Lab W290AClassroom Projection Room E236Electrical Closet W338Lab Computer Server Room W344 Class Lab Preparation Room W428 W444Classroom Laboratory E303Research Lab (Dry) E309Research Lab (Dry) W436Collegiate - Special Procedures Individual spaces identified Majority of concerned spaces currently have supplemental cooling systems

ECM-6/ECM-12 Teaching Lab Occupancy Air Flow Reset User Discussion Modify Control Sequence to Reduce Ventilation and hood exhaust Rate Setpoints during Unoccupied Hours Reduce Minimum Room Airflow to 4 ACH and hood air flow to NFPA minimum

ECM-6/ECM-12 Teaching Lab Occupancy Air Flow Reset Minimum Turndown Capabilities of VAV’s Temperature Control Infrastructure Reviewed Viable Timeframes Confirmed through sample of Shop Drawings Add Controllers (Nae) Each Room Program Individually Modified Winter And Spring Break User Discussion

ECM-7 Reduce Minimum Laboratory Ventilation Rate During Occupied Hours Modify Control Sequence to Reduce Ventilation Rate Setpoints during Occupied Hours in Classroom Laboratories. Reduce Minimum Room Airflow to 6 ACH User Discussion

ECM-7 Reduce Minimum Laboratory Ventilation Rate During Occupied Hours Minimum Turndown Capabilities of VAV’s Temperature Control Infrastructure User Discussion

ECM-8 Decommission Unused Fume Hoods This measure identifies the savings potential of decommissioning Individual Fume Hoods Scope Would Include- 1.Shut off the exhaust VAV Terminal at Each hood 2.Fully close hood and Secure sash 3.Visually Identify Hood as being Decommissioned and cannot be used 4.Rebalance Room Airflows to maintain pressure requirements User Discussion

ECM-8 Decommission Unused Fume Hoods Five Rooms Identified E124W100W105W109W147E124W100W105W109W147 User Discussion

ECM-10 Decommission AHU Dehumidification Sequence Remove program to reset DAT down based on return air humidity. Impact To Building Occupants: Building humidity levels may increase from values currently seen when mechanical cooling is active (chilled water available). Spaces will remain within standards for thermal comfort. User Discussion

Impact To Building Occupants: Building humidity levels may increase from values currently seen. Spaces will remain within standards for thermal comfort. Risks Associated with Implementation: Areas requiring specific environmental humidity levels may need supplemental dedicated dehumidification equipment. Decommission Existing AHU Dehumidification Sequence User Discussion

Lower humidification set point from 30% to 20% RH Based on equipment environmental tolerances, this measure was not implemented. ECM-13 Reduce Humidification Set Point User Discussion

Engaged building participants; early and often Free-flow of information Responded quickly to concerns Took time to learn Actual Implementation

Questions?

Thank You