Current Transformers: A Tester Survival Guide Bryan Shannon ABB Inc. Coral Springs, FL.

Slides:



Advertisements
Similar presentations
Digital Current Transformer Reporter
Advertisements

CURRENT TRANSFORMERS AND VOLTAGE TRANSFORMERS
Chapter 12 Transformers. Chapter 12 Transformers.
Electrical Safety Basic Electrical Safety Rafael Coll, Environment Safety and Health Section Health& Safety Group Ext Pager: (630)
Understanding GFCIs Developed by NEMA Ground Fault Personnel Protection Section (5PP) Developed by NEMA Ground Fault Personnel Protection Section (5PP)
NFPA ELECTRIC VEHICLE SAFETY FOR EMERGENCY RESPONDERS Module II : Basic Electrical Concepts And Hazards Module II : Basic Electrical Concepts And Hazards.
By: Aseem Aggarwal. Causes of Electrocution Fatalities Contact with Overhead Power lines Contact with Live Circuits Poorly Maintained Extension Cords.
ELECTRICAL SAFETY Safety Training for the Non-Qualified.
20.3 Electric Circuits Key Concepts What is included in a circuit diagram? How do series and parallel circuits differ? How do you calculate electrical.
Proposed Design and the Operation of a Disconnecting Device for Small EG Installations Prepared by Hendri Geldenhuys.
Combined Selective Systems :-
The Association of Electrical and Medical Imaging Equipment Manufacturers Understanding GFCIs Developed by the NEMA 5PP Personnel Protection Technical.
NFPA ELECTRIC VEHICLE SAFETY FOR EMERGENCY RESPONDERS Module II : Basic Electrical Concepts And Hazards Module II : Basic Electrical Concepts And Hazards.
Physiological Effects of Electricity on Human Body by Mohd Yusof Baharuddin.
Safety Training For The Non-Qualified
Area of Study 2: Electricity
To bring electric current into a building, an electrician installs wiring. In a house, all of the wires usually come from one main box.
Ignition System.
 Four Components of a circuit  Power supply  Conductor  Load device  Controlling device  Power Supply  Generator  Line source (wall outlet)  Transformer.
Electrical Installation 2
Communication Signals Electrical Safety Fox Valley Technical College Appleton, WI, USA.
Instrument Transformers
Radian Research, Inc. Radian Research, Inc. an employee owned company Power and Energy Measurement Specialists 3852 Fortune Drive.
Grounding, bonding, and ground fault currents
Connections of a CT and a PT to supply, load and relay.
20.3 Electric Circuits
Basic Electrical Safety
MAINS ELECTRICITY. Specification Electricity Mains electricity understand and identify the hazards of electricity including frayed cables, long cables,
DEVICES TO PROTECT AGAINST ELECTRICAL HAZARDS
HVACR416 - Design Electrical Safety. Safety and Hazard Prevention Current is the killing factor in electrical shock Human bodies has resistance If voltage.
Lesson 6 Voltage Do we need to MEASURE it? OR Do we need to DETECT it?
SAFETYSAFETY. Overview ●Introduction to Safety ●Potential Electronic Mishaps ●Safe Work Practices.
Protection of Microgrids Using Differential Relays
Limiting Maximum Current of the Power Supply. Which Meter has almost zero resistance? Current meter R i  0  e.g.,  R i 
ELECTRICAL SAFETY OUTLINE  The basic effect of electricity on human body  Ventricular Fibrillation  Electric shock  Electric Shock – Treatment  Important.
1 HVACR317 – Core for Refrigeration Safety and Hazard Prevention.
3200 Electrical Test Equipment Calibrator The Total Solution to Electrical Test Equipment Calibration.
ELECTRICAL SAFETY FOR INSTRUMENTS SECTION. Electrical measurement safety Understanding hidden hazards and new safety standards.
Grounding.
CURRENT, VOLTAGE & RESISTANCE. Learning Goals ■I will be able to explain the difference between voltage, current and resistance. ■I will be able to explain.
Electrical Safety Electricity Electricity is a flow of along a wire which is also called a. Electricity can be supplied from either a or from the. The.
Protection of Power Systems
Instrument Transformer Electrical Measuring Instruments & Instrumentation 3rd SEMESTER ELECTRICAL ENGG.
D.C. Machine & Transformer Topic: Instrument Transformer Electrical:-1 presented by: Jill Chauhan ( ) Chirag Agarawal ( )
1 :. Introduction These are special type of transformers used for the measurement of voltage, current, power and energy. As the name suggests, these transformers.
BASIC ELECTRICITY AND MAGNETISM
DC Machine & Transformer
Electrical Safety Basic Electrical Safety. Electrical Safety  Course not designed to teach you to work on electrical equipment. Basic Electrical Safety.
GUIDED BY- Mr. Bipin saxena PRESENTED BY – Giri Pankajkumar Shyamkant ENROLLMENT NO Patel Harsh Mukesh bhai ENROLLMENT NO
Part Three – Relay Input Sources
Sensor presentation.
Circuit Protection Unit 9.
Basic Electricity.
Limiting Maximum Current of the Power Supply
Basic Electrical Safety
Sensor presentation.
ACTIVE LEARNING ASSINGNMENT
Subpart K Electrical Long recognized as a serious hazard.
WORKSHOP PRACTICE WEEK-5 OBJECTIVE OF LAB-5 Introduction to digital multimeter and its measuring method. To be familiar with the connections of.
Instructor: Sujood Alazzam
THREE-PHASE GROUND-FAULT BASICS
Electrical Safety in the Home
What Is to Be Covered? Electrical Shock - Why Have GFCIs?
Safety Meeting Topics Standby Generator Safety
Basic Electrical Safety
Basic Electrical Safety
MAINS ELECTRICITY.
Basic Electric Principles
Presentation transcript:

Current Transformers: A Tester Survival Guide Bryan Shannon ABB Inc. Coral Springs, FL

Current is Stepped Down [by primary and secondary windings] Exciting Impedance is the primary source of error. [By design Zo, Zi or Xm is very high to reduce Ie as much as possible] During Open CT Condition. A very high voltage is developed at CT terminals. [all secondary current flows through Xm] Current Transformer: Equivalent Circuit

Why Relay Accuracy CTs? Under short circuit conditions, a small core that might be adequate for metering applications would “fill up” and be unable to carry the magnetic flux required to transform the current. Under short circuit conditions, a small core that might be adequate for metering applications would “fill up” and be unable to carry the magnetic flux required to transform the current. When this happens, the current transformer might be unable to induce a voltage high enough to maintain proper current flow in the secondary side. This could result in very serious errors. When this happens, the current transformer might be unable to induce a voltage high enough to maintain proper current flow in the secondary side. This could result in very serious errors. Protection CTs require linearity in a wide range of currents Protection CTs require linearity in a wide range of currents

Calculated or Tested Accuracy According to IEEE standards (C57.13), current transformers are given an accuracy rating with a “C” or a “T” According to IEEE standards (C57.13), current transformers are given an accuracy rating with a “C” or a “T” “C” indicates calculated accuracy and “T” indicates tested accuracy. “C” indicates calculated accuracy and “T” indicates tested accuracy. Using this system, current transformer with rating T100 would have to be tested to verify that it could sustain a voltage of 100 volts within normal accuracy limits. Using this system, current transformer with rating T100 would have to be tested to verify that it could sustain a voltage of 100 volts within normal accuracy limits. “C” type are transformers which are constructed so that the effects of leakage fluxes on its performance are negligible, such as bushing current transformers with uniformly distributed windings. “C” type are transformers which are constructed so that the effects of leakage fluxes on its performance are negligible, such as bushing current transformers with uniformly distributed windings.

Maximum Burden Current transformers for relay applications are rated in the terms of the maximum secondary volts that can be induced on a twenty times short circuit rating – with error of current transformation limited to 10%. Current transformers for relay applications are rated in the terms of the maximum secondary volts that can be induced on a twenty times short circuit rating – with error of current transformation limited to 10%. For example, a current transformer rated 5 amperes secondary current, might be given a relay accuracy rating at 200 volts (C200). For example, a current transformer rated 5 amperes secondary current, might be given a relay accuracy rating at 200 volts (C200). This would indicate that the current transformer could sustain relaying accuracy – at 100 amps – as long as the secondary voltage IZ did not exceed 200 volts. This would indicate that the current transformer could sustain relaying accuracy – at 100 amps – as long as the secondary voltage IZ did not exceed 200 volts. In this case, the maximum burden that could be used would be calculated as follows: In this case, the maximum burden that could be used would be calculated as follows: Z (Burden)= E/I ( voltage rating / 20 times rated current of 5 amps) Z (Burden)= E/I ( voltage rating / 20 times rated current of 5 amps) = 200 volts / 100 amps = 2 ohms (Includes wiring and relays) = 200 volts / 100 amps = 2 ohms (Includes wiring and relays)

Benefits of Test Switches Test switches provide a quick and safe means of testing relays. Test switches provide a quick and safe means of testing relays. Test switches are especially important wherever secondary current transformer circuits may need to be temporarily reconfigured to facilitate testing or where the relay must be temporarily disconnected from service. Test switches are especially important wherever secondary current transformer circuits may need to be temporarily reconfigured to facilitate testing or where the relay must be temporarily disconnected from service. Accidental opening of a CT secondary circuit can result in extremely high voltage and arcing, creating a dangerous hazard. Accidental opening of a CT secondary circuit can result in extremely high voltage and arcing, creating a dangerous hazard. Test switches eliminate this possibility by diverting the secondary current to an alternate path before opening the connection to the relay. Test switches eliminate this possibility by diverting the secondary current to an alternate path before opening the connection to the relay. This sequenced operation is inherent to the design of the current-shorting poles of a test switch. This sequenced operation is inherent to the design of the current-shorting poles of a test switch.

Circuit Design for Testing

Facilitate Simpler and Quicker Testing Allows Access to Connections from Front of panel Assures correct testing procedure sequence (Make before break of CTs) But, an Open CT can still occur.

Reasons for In-Service Testing Competitive Electric Utility Market Competitive Electric Utility Market –More power wheeling/power needs –Control of supply chain resources –Requires reliable power delivery –Equipment availability Deregulation of Electric Power Deregulation of Electric Power –GENCO to TRANSCO separation –ISO activity requires metering –Need to use existing ITs Bottom-line Focused Bottom-line Focused –Billing and current swings –Must verify performance of ITs

In Service Measurements – What could go wrong Accidental Opening of current transformer due to: Accidental Opening of current transformer due to: -Blown Fuse -Accidentally disconnected leads -Defective leads -Defective equipment -Incorrect Connections -Incorrect meter mode selected

Open CT Current goes to zero until condition is restored Every half cycle high voltage transients occur

Open Circuit Voltages Because the open circuit voltage is limited by saturation of the core, the RMS value measured by a voltmeter may not appear to be dangerous. As the current cyclically passes through zero, the rate of change of flux at current zero is not limited by saturation, and is very high indeed. This induces extremely high peaks or pulses of voltage. Voltage transients up to 15Kv could be possible. Because the open circuit voltage is limited by saturation of the core, the RMS value measured by a voltmeter may not appear to be dangerous. As the current cyclically passes through zero, the rate of change of flux at current zero is not limited by saturation, and is very high indeed. This induces extremely high peaks or pulses of voltage. Voltage transients up to 15Kv could be possible. These high peaks of voltage may not register on the conventional voltmeter, but they can break down insulation and are dangerous to personnel. Current transformers are insulated to withstand, for emergency operation, secondary peak voltages up to 3500 volts These high peaks of voltage may not register on the conventional voltmeter, but they can break down insulation and are dangerous to personnel. Current transformers are insulated to withstand, for emergency operation, secondary peak voltages up to 3500 volts

Current Dangers Human Reaction (at 60Hz) Current (milliamperes) Perception Threshold 1 mA Painful Sensation 3-10 mA Can’t Let GO (paralysis or arms) 10 mA Can’t Breathe (Paralysis of chest Muscles) 30 mA Fibrillation Threshold (Affects Heart- Could be fatal) 65 mA Heart Paralysis 4A Tissue Burning. 5A A value of 1500 ohms is commonly used as the resistance from arm to arm of the human body.

What Level is a Dangerous Voltage? Human Reaction (at 60Hz) Voltage Required (Arm to Arm) Perception Threshold 1 mA Painful Sensation 3-10 mA Can’t Let GO (paralysis or arms) 10 mA Can’t Breathe (Paralysis of chest Muscles) 30 mA 45V Fibrillation Threshold (Affects Heart- Could be fatal) 65 mA 97.5V Heart Paralysis 4A Tissue Burning. 5A OSHA says 50Vac is a hazard [ (a)(1) and (I)(1)] IEC (International Electrotechnical Commision): 30Vac Rms, 42Vac Peak, or 60Vdc

Consequences of Open CT High voltage and shock hazard High voltage and shock hazard Signal discontinuity to relay and controls could lead to incorrect operations and outages. Signal discontinuity to relay and controls could lead to incorrect operations and outages. Potential magnetization of the CT leads to incorrect secondary output. This can cause error in readings, revenue metering calculations, incorrect operations long after the open CT condition is resolved. Potential magnetization of the CT leads to incorrect secondary output. This can cause error in readings, revenue metering calculations, incorrect operations long after the open CT condition is resolved.

Typical In-Service Testing Test Switch

Solution to existing problems Prevents Shock Hazards [Created by human error, and other causes] Prevent Blackouts [Created by human error, and other causes] Prevents CT erroneous reading (Avoid Magnetization) Test Plug with Open CT Protection Test Switch

How it works? Detects rate of change of voltage and internal circuitry shorts CT LED would indicate open CT condition present Maintains signal to relay/IED Eliminates possibility of false trip Test Plug with Open CT Protection Test Switch

Open CT Protection Current signal integrity to relay maintained. [Prevents incorrect operations] Voltage spikes limited to first occurrence Voltage spikes limited to 35 Volts [Eliminates Shock Hazards]

Current waveform in Open CT with New Test Plug Minimizes distortion or signal discontinuity to protective devices, eliminating false trips and potential blackouts

User Exposure Comparison Maintains voltage to safe levels and reduces user exposure, thus increasing safety and eliminating equipment damage

Conclusions Open CT conditions are a very likely event as more in-service testing is required Open CT conditions are a very likely event as more in-service testing is required Open CT condition leads to Shock Hazard, Outages Open CT condition leads to Shock Hazard, Outages Open CT could lead to incorrect readings long after condition is eliminated due to magnetization Open CT could lead to incorrect readings long after condition is eliminated due to magnetization Test Switches are recommended for installation with Current Transformers Test Switches are recommended for installation with Current Transformers Proposed test plug device eliminate risks due to operator error, incorrect equipment or risks arising due to normal testing practices and procedures. Proposed test plug device eliminate risks due to operator error, incorrect equipment or risks arising due to normal testing practices and procedures.

Questions?