Fire Requirements For Foam Plastic Insulation and WRBs in Exterior Walls Presented to By Jesse J. Beitel July 31, 2012.

Slides:



Advertisements
Similar presentations
BUILDING CONSTRUCTION
Advertisements

Contents: Cover
Fire-Resistive Construction (2nd part)
Summary of NFPA 101 Interior Finish Requirements
Continuous Insulation for Code- Compliant, High-Performance Walls pima.org.
“Do not take anyone’s advice as to how this building should be assembled.”
Building Enclosure Moisture Management Institute (BEMMI)
FCIA CODE EFFORTS FCIA Spring Conference 2003 By William E. Koffel, P.E. Koffel Associates, Inc.
Building Construction A fire resistive rating (FRR) is given in minutes or hours and relates to how long it takes to burn through a given material. Expressions.
Emerging Standards and their effect on Exterior Continuous Insulation in Commercial Wall Construction.
IBC 2006 Chapter 5 Building Height and Areas After determining occupancies, the code analysis determines what height and areas are allowable for the occupancy.
Heat Loss & Gain Calculations 1. How Heat Moves in Homes Conduction is the transfer of heat through solid objects, such as the ceilings, walls, and floors.
Interior construction Harvard Graduate School of Design.
Structural.
Fire.
Building science.
1 Foundation Moisture Control and Energy Performance.
Flash and FOIL® Frame Wall Insulation. Module 1 Masonry Wall Insulation Hybrid Spray Foam and Reflective Insulation System – Fi-Foil® Company Introduces…
CONTINUOUS INSULATION PRIMER. PART 1 – Continuous Insulation Definition (ASHRAE 90.1)ASHRAE 90.1 Applications: Roof, Wall, and Foundations.
Chapter 27 Insulating Structures. Objectives After reading the chapter and reviewing the materials presented the students will be able to: List the ways.
Effective for applications submitted on September 16 th.
Architectural Design Construction of a Wall Section Upon completion of this assignment, you will be able to accurately and neatly draw, to scale and limits,
1 Expertly Engineering Safety From Fire EVALUATION OF DRAFTSTOPPING WITHIN TYPE V COMBUSTIBLE CONCEALED ATTIC SPACES Prepared by: Steve Welsh June 27,
Introduction to Building Codes © 2010 Project Lead The Way, Inc.Civil Engineering and Architecture.
Occupancy Classification Under NFPA 13 Examine the proposed facility and make recommendation on the Occupancy Classification Used to classify fuel loads.
Phoenix Convention Center Phoenix, Arizona Air Barrier Technologies Energy TechnologiesWindows and Building Envelope Technologies Diana Hun, PhD Oak Ridge.
© 2006 ITT Educational Services Inc. CD230 Architectural Design & Drafting: Unit 10 Slide 1 Unit 10 Commercial Construction.
Building Codes. Codes  Building Code –Regional  BOCA, SBCCI, CABO, UBC, CITY OF DALLAS, –National  IBC  Fire Code –NFC, UFC, NFPA, Life Safety 101.
Fire-Related Properties of Materials Chapter 7. Mehta, Scarborough, and Armpriest : Building Construction: Principles, Materials, and Systems © 2008 Pearson.
Attending the ICC Conference in Detroit this September or know someone who is?
Fire Inspection and Code Enforcement, 7 th Edition Chapter 4 — Construction Types and Occupancy Classifications Inspector I.
Chapter 44 Building Codes and Commercial Design. 2 Links for Chapter 44 Building Codes Design Categories Using the Codes Related Web Sites.
Construction Type of Buildings
Engineering Analysis of NFPA 285 Tested Assemblies
Chapter 28 Structural Components of Framed Construction.
Construction Types Chapter 3.
SELECTING INSULATION MATERIALS  Insulation can serve as more than just an energy barrier, providing fire resistance, humidity control, and noise reduction.
Finish & Furniture Selection ID 234 Chapter 9 What is Regulated by Codes: Walls & Ceilings – Class A, B, C (flame spread/smoke) Floors – Class I & II.
Fire Resistance Rated Truss Assemblies Educational Overview.
EXPLANATION OF FOOTNOTE H. R2ci ≠ R5ci – “Footnote h” The application of an earlier version of a footnote to the R- value table was stretched beyond its.
Precast Concrete Panel Group 6 Alex Cooper Yadir Avila Erjan Kadrakunov.
Plumbing Radiant Heating & Cooling Turf Conditioning Permafrost Ice and Snow Melt Ecoflex ® SupportSustainabilityEngineered PolymerCommercial SystemsIntroductions.
Building Construction
Land Use and Development Regulations © 2010 Project Lead The Way, Inc.Civil Engineering and Architecture Our object in the construction of the state is.
Building Resource Inc. Sustainable Durable Buildable Cost Effective
Fire Retardants and Truss Design Overview. Introduction Fire retardant treatments (FRT) were developed to be applied to building materials, such as dimension.
NFPA 285: Assembly Test of Exterior Walls with Combustible Components.
Fire Blocking Requirements For All Buildings;
Energy Codes and the Building Envelope
OBJ: SWBAT create a CAD Rendering of a Utility shed.
FRT Lumber Use in Type III-A Buildings
Truss Heel Heights and Energy Code Requirements
House Bill 535 : 2016 Florida Legislature
Continuous insulation primer
Warm-up 9/19/16 What template are we using?
NFPA 600, INDUSTRIAL FIRE BRIGADE Module : 11 BUILDING CONSTRUCTION.
Land Use and Regulations
Educational Overview Revised 6/13/2017
Building Construction
Introduction to Building Codes
Wildfire Development Permit UPdate
Energy Codes and the Building Envelope
Land Use and Development Regulations
Water-Resistive Barriers: Assuring Consistent Assembly Water Penetration Resistance Educational Overview Revised August 31, 2018.
Summary and conclusion
Common Components of a Traditional Wood Framed Building
Floor Truss Ribbon Board Load Path
- Strictly Confidential -
Above Grade ICF Walls Interim Summary - Details & Water Management Strategies Building Green With Concrete October 22, 2015 Presented by Brian Hubbs, P.
Presentation transcript:

Fire Requirements For Foam Plastic Insulation and WRBs in Exterior Walls Presented to By Jesse J. Beitel July 31, 2012

Learning Objectives n Code requirements for foam plastic in exterior walls n History of NFPA 285 Fire test n Other Fire tests required n Code requirements for Water-Resistive Barriers n Applicability and Use of NFPA 285

Continuous Insulation (CI) Concept n ASHRE 90.1 – Commercial n IECC (Energy Code) – Commercial & Residential n Concept – Wrap building w/ insulation outboard of studs n Helps with thermal conduction, dew point, etc. n Creates high R-value walls 3

Insulation In Exterior Walls n Location in walls – CI / Cavity / Both n Can use noncombustible or combustible non-foam plastic insulation u Fiberglass, Mineral wool u Cellulose, others u Minimal fire requirements n Can use combustible foam plastic insulation u Many types – XPS, EPS, Polyiso, SPF, etc. u Characteristics different u Regulated the same u Fire requirements for walls and foam plastics vary based on Type of Construction, etc. 4

Fire Requirements Vary Fire Requirements Vary n One & Two Family Dwellings – Exterior walls - IRC regulates n Type V – Exterior walls - combustible – IBC regulates n Types I, II, III, IV – Exterior walls to be noncombustible unless allowed – IBC regulates 5

IRC (2012) Fire Requirements n Non-foam plastic insulation u Noncombustible or if combustible then FSI ≤25 & SDI ≤450 n Foam plastic insulation u Labeled u FSI ≤75 & SDI ≤450 u Protected by 15-minute Thermal Barrier u Gable ends in attics – Protect with ignition barrier n Fire Resistance of exterior walls 6

IBC (2012) – Type V Fire Requirements n Non-foam plastic insulation u Noncombustible or if combustible then FSI ≤25 & SDI ≤450 n Foam plastic insulation (Chapter 26) u Labeled u FSI ≤75 & SDI ≤450 u Protected by 15-minute Thermal Barrier u Gable ends in attics – Protect with ignition barrier n Fire Resistance of exterior walls 7

IBC (2012) - Fire Requirements For Type I, II, III or IV – Part 1 n Noncombustible Insulation - OK u Fiberglass u Mineral wool n Non-foam plastic combustible insulation nCellulose Insulation, etc. nFSI ≤25 & SDI ≤450 n Fire Resistance of exterior walls 8

IBC - Fire Requirements For Type I, II, III or IV – Part 2 n Foam Plastic Insulation u Regulated by § u Applies to exterior walls of Type I – IV construction u Applies to buildings of any height u Exceptions: Type V buildingsType V buildings Cold Storage – 1 story & meets other reqm’tsCold Storage – 1 story & meets other reqm’ts 9

IBC - Fire Requirements For Type I, II, III or IV – Foam Plastic n Meet the requirements of NFPA 285 n For each combustible component - FSI ≤25 & SDI ≤450 (ASTM E84) n Maintain fire resistance rating (ASTM E119) n Foam separated from interior of building by a Thermal Barrier u Gable ends in attics – Protect with ignition barrier n Limits on amount of foam (btu/ft 2 ) (mJ/m 2 ) n No ignition when tested via NFPA 268 (Radiant heat exposure test) 10

11 History - Fire Test/Code Development n In mid 1970’s – use of foam plastic on or in noncombustible exterior walls was proposed. u EIFS & Steel/Foam/Steel Panels n Problems with use: u Exterior walls of Type I, II, III or IV Construction must be noncombustible construction. u Foam plastic is combustible u Issues raised over potential for vertical and horizontal fire spread due to the combustible foam plastic insulation

History (continued) n SPI began work in Codes and testing. n Discussions w/ Code & Fire Officials. n Drafting of Code language. n Testing program u Testing was to determine efficacy of proposed wall systems to resist flame spread.

Multi-Story Fire Test n Can the wall covering, insulation & assembly resist: u Flame propagation over face of the wall covering u Vertical flame propagation within the combustible core or components u Flame propagation over interior surface from one floor to the next u Lateral Flame propagation to adjacent compartments n Does not address floor-line joint per se. 13

14 UBC 17-6 / UBC 26-4 Test In Progress

15 Fire Test/Code Development n Test program completed in late 1980 n Code change to Plastics Section adopted in 1988 UBC n Versions adopted by NBC and SBC n Full-scale test was also adopted as UBC Used by all ESs. n In 1994 edition of UBC – reorganization moved plastics to Chapter 26 and test method became UBC 26-4.

Fire Test/Code Development (Cont’d) n In early 1990’s a “reduced-scale” fire test was developed. n New test adopted as UBC 26-9 in 1997 edition. n Test submitted to NFPA Committee on Fire Tests and it was adopted as NFPA 285 in n NFPA 285 “Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non- load-bearing Wall Assemblies Containing Combustible Components” n ICC IBC specifies NFPA 285 n Code requirements basically the same since 1988 UBC 16

NFPA 285 Test In Progress 17

IBC - Fire Requirements For Type I, II, III or IV – Foam Plastic n Meet the requirements of NFPA 285 n For each combustible component - FSI ≤25 & SDI ≤450 (ASTM E84) n Maintain fire resistance rating (ASTM E119) n Foam separated from interior of building by a Thermal Barrier u Gable ends in attics – Protect with ignition barrier n Limits on amount of foam (Btu/ft 2 ) (MJ/m 2 ) n No ignition when tested via NFPA 268 (Radiant heat exposure test) 18

19 ASTM E84 Test Apparatus

ASTM E119 Wall after fire test 20

Thermal Barrier Requirement n Code requires that foam plastic must be separated from the interior of the building by a 15-minute thermal barrier. n Applies to any foam plastic application. n Thermal barrier is typically 0.5 in. (12.7 mm) thick gypsum wallboard or meets NFPA 275. n Thermal barrier retards heat transmission to the foam and delays its ignition. 21

Ignition Barrier Requirement n Applies to foam plastic insulation in attics & crawl spaces n Only where entrance is made to service utilities n Prescriptive ignition barriers provided in Code: wood, mineral fiber, gypsum wallboard or steel n Not a thermal barrier n Alternative assemblies by special testing 22

NFPA 259 Potential Heat Test n Code requires that the “potential heat” (calculated on areal basis) of the foam plastic not exceed that which is tested via NFPA 285 n Uses NFPA 259 – Measures amount of heat released when burned in pure O 2 n Data from test expressed in Btu/lb (MJ/kg) n Convert this to Btu/ft 2 (MJ/m 2 ) using thickness and density of foam plastic. n Allows calculation for different densities/thickness combinations 23

NFPA 268 Test 24

WRB Definitions n My definition = Weather-resistive barriers include: u Air barriers u Vapor barriers u Water barriers u ???? Barriers n IBC: u Water-resistive barrier

WRB Code Requirement 2012 IBC Vertical and lateral flame propagation. Exterior walls on buildings of Type I, II, III or IV construction that are greater than 40 feet ( mm) in height above grade plane and contain combustible water-resistive barrier shall be tested in accordance with and comply with the acceptance criteria of NFPA 285.

Exteriorveneer Cavity air space Interior wall membrane Steel stud Sheathing Foam insulation WRB Insulation in stud cavity Potential Variations of Wall Systems

How Do WRBs Meet NFPA 285? n There is no one test or test assembly to qualify a WRB for use in all assemblies n Perform NFPA 285 test – WRB is one of several materials in assembly n Limited engineering analysis based on NFPA 285 tests in conjunction w/ small- scale tests.

Engineering Analysis n Use WRB X in a successful NFPA 285 test n Develop fire performance parameters for WRB X (ASTM E1354 Cone Calorimeter) n Develop fire performance parameters for WRB Y n Compare fire performance parameters – if same or better, then maybe substitute Y for X in tested assembly

Applicability of NFPA 285 n 285 is a test of a complete wall assembly n 285 test results apply only to the tested construction – similar to ASTM E119 n Substitutions of one material for another can cause different test results n Addition of combustibles (insulation, WRBs, etc.) can cause different test results 30

Applicability of NFPA 285 (Continued) n Changes in configurations (air gaps, attachment systems, etc.) can cause different results n Wall systems made of a number of previously NFPA 285 tested materials does not ensure a successful NFPA 285 test n Tests are required for many various veneers and other combustible wall components – insulation, WRBs 31

Applicability of NFPA 285 WRBs n Use of WRBs can cause different results n Substitution of WRBs can cause different results n Even tested WRBs cannot necessarily be applied to other foams, veneers, etc. n Same issues as with other NFPA 285 tests – materials, configuration., etc.

Summary n Insulation in exterior walls is regulated. n Amount of regulation / tests for exterior insulation and/or insulated exterior walls depends on: u Code u Type of Construction u Type of insulation u WRBs 33

Summary - Continued n NFPA 285 provides a determination of vertical fire performance of exterior wall assemblies. n NFPA 285 tested systems reduce the potential for vertical flame spread by exterior walls. n NFPA 285 data/results must be used in an appropriate manner. 34

Thank You andQuestions? Jesse J. Beitel Senior Scientist/Principal Hughes Associates, Inc.