Protecting life, environment and property… 1 AutroFlame Detectors ID: AFLAME_X33_1_intro
Protecting life, environment and property… 2 The New Flame Detectors Family
Protecting life, environment and property… 3 Massive Regulatory Changes Factory Mutual DNV EN54 part-10
Protecting life, environment and property… 4 New Universal Features Dedicated Class I Div. I, EEx de wiring box Common housing for all technologies More outputs options –2 Alarm relays –1 Fault relay –4-20 mA and relay –Modbus / RS485 –Data logger –Addressable modules installed –Magnetic manual Oi activation switch
Protecting life, environment and property… 5 New Universal Features Temperature compensated heated optics –Heater will boost heat on cold startup and when the detector temperature is below zero Data event logger will record the detectors operating temperature –Record of over-temperature events in turbine enclosures
Protecting life, environment and property… 6 AutroFlame X33/1 Multispectrum IR
Protecting life, environment and property… 7 New Capabilities Same extended performance as the X33 Configurable auxiliary relay Form C alarm relay PowerLoop direct connection
Protecting life, environment and property… 8 AutroFlame X33/1 & Q9033B Mount
Protecting life, environment and property… 9 AutroFlame X33/1 Optical Integrity New sensor and Oi ring orientation Built in weather visor for improved water resistance Optical integrity ring modified to keep water off the check surfaces using a plastic metal bonded design Optical integrity consecutive check time adjustable for improved water and rain resistance
Protecting life, environment and property… 10 AutroSafe X33/1 Optical Integrity Automatic optical integrity test monitors for both loss of, and increased sensitivity in each sensor Manual optical integrity test verified to perform a calibrated test of the detector and system Like a Genie, magnetic Oi, no test lamp required!
Protecting life, environment and property… 11 AutroFlame X52 Ultraviolet/Infrared Detector
Protecting life, environment and property… 12 New Capabilities New high speed capability- 30 ms The best false alarm rejection for any UVIR detector Heated optics
Protecting life, environment and property… 13 AutroFlame X98 Infrared Detector
Protecting life, environment and property… 14 New Capabilities Heated optics Auxiliary relay
Protecting life, environment and property… 15 AutroFlame X22 Ultraviolet Detector
Protecting life, environment and property… 16 New Capabilities Same high level signal processing The best false alarm rejection for any UV detector Heated optics
Protecting life, environment and property… 17 New Vibration Free Mount Q9033B Mounting swivel with angle indicators
Protecting life, environment and property… 18 Weather Visor Flame Platform
Protecting life, environment and property… 19 AutroFlame X33/1 New air shield for adverse environments
Protecting life, environment and property… 20 AutroFlame X33/1 Replacement Module
Protecting life, environment and property… 21 Protectir Laser Aimer Q1201C
Protecting life, environment and property… 22 Connection to AutroSafe Com Fire N.O. Fire N.O. Fault Com Fault 2K BN-300 X33/1 Detector AutroFlame SS Exd w/built in BNB AutroFlame Alu Exd w/built in BNB-300
Protecting life, environment and property… 23 Typical Flame Detector Mounting
Protecting life, environment and property… 24 Detector Positioning
Protecting life, environment and property… 25 Flame Detector Testing Only method to confirm system performance is an actual fire test Not practical or allowable at most jobsites Videotape recording common High-speed UV system response timer available
Protecting life, environment and property… 26 Flame Detector Testing Complete system check-out with manual Oi is recommended (Calibrated System Check) Hand-held test lamp often required by customer Test lamps do not confirm detection system performance
Protecting life, environment and property… 27 New Applications Longer detection range requirements New false alarm requirements Class A fire materials Nasty environments Extreme cold environments