Lecture Notes 4 Per Unit System

Slides:



Advertisements
Similar presentations
EE 369 POWER SYSTEM ANALYSIS
Advertisements

Advanced Power Protection Lecture No.2
ENERGY CONVERSION ONE (Course 25741)
TRANSFORMERS. TRANSFORMER PARAMETERS Turns Ratio (n) It is defined as the ratio of the number of turns in the secondary winding (N sec ) to the number.
ECE 4411 Voltage Regulation. ECE 4412 Voltage Regulation (continued) E nl = no-load output voltage –Measure with a voltmeter when no load is connected.
Today’s Topics 1- The per unit system 2-Transformer Voltage Regulation
Transformer Voltage Regulation Fact: As the load current is increased, the voltage (usually) drops. Transformer voltage regulation is defined as:
Per Unit Representation Load Flow Analysis Power System Stability Power Factor Improvement Ashfaq Hussain.
Announcements Be reading Chapter 3
Power Factor and Power Factor Correction
Lecture 8 Transmission Lines, Transformers, Per Unit Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Power Triangle.
Transformer with open secondary.
Transformers.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Transformer with open secondary.
Elec467 Power Machines & Transformers
Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.
Power in AC Circuits ELEC 308 Elements of Electrical Engineering
Single Phase Transformer
Kazi Md. Shahiduzzamna, EEE, NUB
1.6 Real Single-Phase Transformer.
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems
Announcements For lectures 8 to 10 please be reading Chapter 3
Announcements Please read Chapter 3 H4 is 4.34, 4.41, 5.2, 5.7, 5.16
Announcements Please read Chapter 3; start on Chapter 6
Power Factor Improvement Lecture 9. Normally, the power factor of the whole load on a large generating station is in the region of 0·8 to 0·9. However,
EET 103 Transformer Chapter 5 1. A transformer is a device that changes ac electric energy at one voltage level to ac electric energy at another voltage.
1 Department of Electrical & Communication Engineering CHAPTER 1 Per Unit Calculations 1.Power System Representation Power Component SymbolPower ComponentSymbol.
Modeling of Power Transformers A Static Device. Transformers The transformer enables us to utilize different voltage levels across the system for the.
Induction Machine The machines are called induction machines because of the rotor voltage which produces the rotor current and the rotor magnetic field.
Announcements For lectures 9 and 10 please be reading Chapter 3
EXAMPLE A pole mounted 100kVA distribution transformer has the following characteristics R 1 = 1.56  R 2 =  X 1 = 4.66  X 2 =  Volts Ratio.
EET 221 Synchronous Machines Rafiqi.
BASIC ELECTRICAL TECHNOLOGY DET 211/3 Chapter 6: Single Phase Transformer (Continued)
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
Instructor :Kashif Mehmood
ELECTRICAL MACHINE DET 204/3 JIMIRAFIZI BIN JAMIL Transformer CHAPTER 1.
Lecture 09Electro Mechanical System1 Chapter 11 Special Transformers.
Transformer A transformer is a static piece of equipment used either for raising or lowering the voltage of an a.c. supply with a corresponding decrease.
Per-Unit System.
EEK260 -Electrical Machines
GANDHINAGAR INSTITUTE OF TECHNOLOGY Electrical Power System
SMJE 2103 Electrical Power System 3- Ph Power Apparatus.
Parul Institute Of Technology Name Of Subject:-Electrical Machines Name Of Faculty:-(1) Suresh Sahoo (2) Yogendra Tiwari E&C 3 rd Sem. Prepaid By :- Sr.No.NameEnrolment.
Power System Protective Relaying-Part Two
Transformers. Single Phase Transformers Principles of Operation – Single Phase.
Lesson 12: Parallel Transformers and Autotransformers ET 332b Ac Motors, Generators and Power Systems 1 Lesson 12_et332b.pptx.
TRANSFORMERS.
Lesson 10: Transformer Performance and Operation
Lesson 9: Practical Transformer Model and Calculations
ECE 476 POWER SYSTEM ANALYSIS
B4.2 Power System One-Line Diagrams
Subject :ELECTRICAL POWER SYSTEM - I( )
BASIC ELECTRICAL TECHNOLOGY DET 211/3
Module B4 Per Unit Analysis
Per-Unit System.
SWAMI VIVEKANAND COLLEGE OF ENGINEERING,INDORE(M.P)
Transformers.
Lesson 23: Synchronous Alternator Voltage Regulation
Transformers. Transformer An A.C. device used to change high voltage low current A.C. into low voltage high current A.C. and vice-versa without changing.
EE1 PEEE Refresher Class Power Part 1 notes by T. Ernst
EET 503 Power System Protection (Instrument transformer )
TRANSFORMER.
Exercise Session 2 Power systems.
Module B4 Per Unit Analysis
Transformers.
Chapter 32 Transformer. Chapter 32 Transformer.
Electrical Machines (EELE 3351)
Exercise 9 Power systems.
Presentation transcript:

Lecture Notes 4 Per Unit System EE212 Passive AC Circuits Lecture Notes 4 Per Unit System

Per Unit (p.u.) System Computations related to power systems involving machines and transformers are often carried out in p.u. system. In p.u. system, power system quantities (such as V, I, R, X, VA, P and Q) are expressed as decimal fractions of chosen base values. p.u values are sometimes expressed in percentage (beween 0 to 100%). Any value can be taken as the Base Value. However, it is chosen to make computation easy. It is usually taken equal to the rating of a machine/transformer in the power circuit. Power equipment impedance ratings are usually given in p.u. (expressed in %) based on their rated voltage and VA.

Advantages of the p.u. System p.u. values of circuit parameters are the same on either side a transformer. We don’t have to worry about circuit parameters being referred to one side or the other. Machines and transformer constants (e.g. resistance, leakage/transient/sub-transient reactance, excitation current, etc.) lie within a narrow range of values when expressed in p.u. We can therefore guess reasonable values for approximate calculations, or easily estimate their correctness. e.g. Leakage reactance of autotransformers lie within 0.01 – 0.04 p.u. (or 1% - 4%).

Applying the p.u. Method Choose base values for 2 quantities, VA and V. Other base quantities (i.e. Ibase and Zbase) are determined from the chosen VAbase and Vbase. Choose one VAbase for the entire system under study. Usually VAbase is the rated VA of the transformer or generator in the system. Divide the system into sub-systems whenever a transformer is encountered. Choose a different Vbase for each sub-system. The ratio of the Vbase on each side of a transformer must be equal to the transformation ratio. Note the single line drawing of the circuit.

Applying the p.u. Method… 4. Determine Ibase and Zbase for each sub-system. Ibase = Zbase = = 5. Calculate the p.u. values of the system quantities. Carry out circuit analysis with computations in p.u. Obtain the actual values of the desired quantities using the equation:

Example: p.u. Method A 50-kVA, 2400/240-V transformer has a leakage impedance of 1.0+j3.61 Ω referred to HV side. Show that the p.u. values are the same on either side of the transformer. For entire system, VAbase = 50,000 VA

Example: p.u. Method… A 50-kVA, 2400/240-V, 60-Hz transformer, with a leakage impedance of 1.42+j1.82 Ω on the HV side, is used to step down the voltage at the load end of a feeder whose impedance is 0.3+j1.6 Ω. The voltage at the sending end of the feeder is 2400 V. Find the voltage at the secondary terminals of the transformer when the connected load draws rated current at a p.f. of 0.8 lagging. 2400 V 0.3+j1.6 Ω FL, 0.8 p.f. lagging For entire system, VAbase = 50,000 VA Vbase = 240 V Zbase Ibase Vbase = 2400 V Zbase Ibase

Example: p.u. Method… Feeder sub-system: Vbase = 2400 V

Example: p.u. Method…

Example: p.u. Method… A 50-kVA, 2400/240-V transformer has a leakage impedance of 1.0 + j3.61  referred to HV side. Calculate the voltage regulation at 0.85 p.f. lagging. VAbase = 50,000 VA

Change of Base Power equipment impedance ratings are usually given in p.u. (expressed in %) based on their rated voltage and VA. When chosen base values are different from the equipment rated values, the rated impedance (in p.u.) of the equipment must be converted to the chosen base values.

Change of Base Example: An 80-MVA, 220/75-kV transformer has a leakage reactance of 3%. Calculate the p.u. reactance when 100 MVA and 72 kV are chosen as the base values.

Change of Base Example T1 20 kVA 2400/240 V ZT1 = 0.01+j0.03 p.u. T2 50 kVA 3300/2400 V ZT2 = 0.01+j0.03 p.u. VAbase (for the entire system) = 50 kVA (change for T1) 232 V 10 kW, p.f.=1 Vbase taken same as equipment ratings (no change)