DEMAND SIDE MANAGEMENT IN UGVCL A K Verma IFS Managing Director
Energy sale & revenue 2006
Energy sale & revenue 2007
Energy sale & revenue 2008
Energy sale & revenue 2009 DSM in agricultural consumption was most needed.
Interventions Feeder separation : Jyoti Gram Yojana Around 576/ 2000 in Rs.350/1200 Cr. 24x7 power supply to villages 8 hrs. a day power supply to farm-sector Innovation of Special Design Transformers Establishment of Area Load Dispatch Centre Creation of Energy Management Centre
Regrouping of Ag- feeders Analysis of total load, peak & off peak demand Regrouping of ag-feeders: 16 to 35 to 59 A group to have about 50 MW of demand Range of Max m & Min m demand in MW changed 1993 & 1152 (Gap:801MW) to 2070 & 1687(Gap:383MW) Flattened load curve resulted
Load Curve
EMC Ag/ JGY-feeders load analysis Ag-metered consumption analysis Analysis of Z, F & L consumers DTR wise energy accounting Feeder Data Management
Energy Efficient Pumps Farmers free to buy pumps certified by GEDA In 2008,3 talukas included, 50% subsidy 6 talukas added & subsidy 2/3 of cost Scheme limited up to 100 HP Scheme applicable to flat tariff only 1 year guarantee & 3 years warranty Very few taker in the initial stage 407 in in
Subsidy Capacity in HPSS/Noril Impeller (Rs./HP) Bronze impeller (Rs./P)
Facts & figures Details / Total application16085 Pumps installed13336 Contracted load in HP Connected load in HP Load after replacement in HP HP reduction (15.6%) Consumer contribution in Rs. Crore2237 Total subsidy in Rs. Crore4281 Pay back period for the subsidy1.4 years Pay back period for the scheme2.1 years
A case study (Vijapur Division) feederHP Cons. EEPsContr. load Conn. load EEP load HP saved Unit saved Amp. Nov- Dec 2008 Amp. Nov- Dec 2009 Amp. saved Mandali Delwada Itadara Baramba Devipura Total
GEDA norms for EE Pumps Rating, HP Discharge LPHx1000 Declared overall Eff. Min. overall Eff. for field condition >57%>54.15% >61%>57.95% The above mentioned Overall Efficiency is minimum required for Field condition as per GEDA Norms.
IRMA Findings Only 21% of EE pumps of average age of 1 yr and 35% of average age of 3 months met with GEDA efficiency norms Increase in failure rate with age may be related to poor design efficiency of the pumps. EE pumps are more energy efficient (combined median 49.82%) than non EE Pumps (combined median 40.87).
On supply side: Providing LT capacitor Installation of APFC panels Feeder bifurcation: 893 feeders HVDS: 7439 Providing amorphous transformers DTRs of GIDC, Urban, Industrial & JGY feeders Load balancing of DTR Mass awareness programmes
Your comments are solicited Thanks a lot!