Critical Environments

Slides:



Advertisements
Similar presentations
Chapter 3. HVAC Delivery Systems
Advertisements

HEALTHCARE BUILDING AUTOMATION
Hot Water Temperature Maintenance
Airflow and BSC Biosafety and Biosecurity Awareness Training
HVAC CONTROLS (See section 18.9)
Objectives Control Terminology Types of controllers –Differences Controls in the real world –Problems –Response time vs. stability.
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
TYPES OF MECHANICAL SYSTEMS
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
Learning Outcomes Upon completion of this training one should be able to: Identify open loop and closed loop campus-type hydronic water system applications.
Innovative Air Distribution for Healthcare Facilities.
Variable Frequency Drives VFD Basics
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY. “Air conditioning is the control of the humidity of air by either increasing or decreasing its moisture content.
Engineering Controls and Laboratory Design Session 4 Laboratory Safety Training.
Engineered Products Make-Up Air for Heating and Cooling.
Break Out Session 3: Group A: Ventilation and Air Quality Chris Cosgrove, Cosgrove FDS, Inc.
Lab Energy Management Big Ten Mechanical & Energy Conference October
Digital Celeris Integrated System Patient Room Isolation Room Programmable Controllers Local Display & Command Unit.
Presenters: Bob Kilgore Matthew McReynolds Brenna Goode CHEMISTRY BUILDING RCX.
Providing services that help make The University of Memphis a safe and healthful place to learn and work Environmental Health and Safety.
When Do Variable Flow Fume Hoods Save Energy? Implications for lab design and behavior modification Michael Gevelber, Robert Choate, Kevin Sheehan, Brian.
Siemens Building Technologies, Inc. ED&G 100 Design Project Fume Hood Face Velocity Control Spring 2004.
1 FUME HOOD SAFETY Environmental Energy Technologies Division Safety Topic July 12, 2012.
1 Meeting ASHRAE Fundamentals, Standard 55 & 62.1 with Chilled Beams Displacement Ventilation.
Engineer Presentation
Energy Saving DDC Control Strategies
Lindab Pascal - Simplified VAV solution with full potential...
VARIABLE GEOMETRY VAV SYSTEMS: SYSTEM AND DUCT DESIGN CONSIDERATIONS.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Sean Kalman – Hays Fluid Controls
September 18, 2009 Critical Facilities Round Table 1 Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure.
An intelligent VAV zoning system
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By Klas C. Haglid, P.E., R.A., CEM 1.
ENERGY CONSERVATION BUILDING CODE – 2006 PRESENTATION BY VP GUPTA PRINCIPAL CHIEF ENGINEER (ELECTRICAL), BSNL CHENNAI.
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
Best Practices in HVAC Design/Retrofit
Important variables Water: Air: Conversion:
Temperature Control Loop
HVACR416 - Design IAQ / Ventilation / Pathways. Ventilation Most air handling units distribute a mix of outdoor air and re-circulated indoor air. Some.
Improved Precision Leading to Improved Energy Efficiency Edward Decker AE 790 – Intelligent Buildings June 6, 2006.
Chemical Engineering 3P04 Process Control Tutorial # 6 Learning goals 1.Learn basic principles of equipment in a control loop 2.Build understanding of.
Sawyer Environmental Changes Mechanical Engineering Department Capstone Amy R. Dan H. Colby C. Brittany P. Richard G. 1.
VAV Box Control Loop The purpose of the VAV Box control loop is to adjust airflow through the box to maintain a space temperature. The difference between.
1 Lamp operating factor Published lumen output is based on laboratory conditions Voltage  Rated at line voltage of 115V Standard reactor ballast  Electromagnetic.
Control Theory Control System Objectives  Establish a final condition  Provide safe operation  Eliminate the human element  Assure economical operation.
New Product Developments World Leaders in Combustion Management Solutions Mk7 Expansion PCB Mk7 Expansion PCB.
Roof Top Unit Overview (MAGNUM) Visit us at Revision- 12/17/2015.
CUE – Make Any Pump an E-Pump
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Control Loops Tune a Fish. Control Loops Tuning of a control loop involves selecting loop parameters to ensure stable control under all operating conditions.
Advanced control strategies. CONTROL SYSTEMS The process parameters which are measured using probes described in the previous sections may be controlled.
BASIC AUTOMATIC CONTROLS UNIT 16 ADVANCED AUTOMATIC CONTROLS
Announcements Next class is the course evaluation
WSHP Systems 1.
Wega & Wega Power chilled beams
CHAPTER 8 Ventilation.
Session 10 –roundtable – Labs and Controls Systems
Energy Efficiency in District Coiling System
Roof Top Unit Overview (MAGNUM)
HCB 3-Chap 19A: All-Air Systems_Single Zone
تهیه و تنظیم: مهندس همت جو
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY
The key to comfort and efficiency for heating and air-conditioning
Manual D Duct Sizes Room Cooling CFM % Total CFM Heating CFM Kitchen GR Dining Bed Bed 3.
Excess Air Management Overview
Presentation transcript:

Critical Environments Laboratory Control Basics and Room Control Strategies Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Insert Agenda slide Laboratory customers and goals Laboratory environment Safety Comfort Experiment integrity Energy efficiency Room pressurization control Constant Volume Direct pressure Flow tracking, a.k.a. “Airflow Tracking” or “Volumetric Offset” Flow tracking with pressure feedback VAV control types Temperature control Laboratory control Copyright© 2006 TSI Incorporated

Laboratory Customer Types Universities Teaching labs Research labs High Schools/Middle Schools Hospitals Copyright© 2006 TSI Incorporated

Laboratory Customer Types Government Facilities USDA FDA GSA & ATF CSI Copyright© 2006 TSI Incorporated

Laboratory Customer Types Industry Technology companies Pharmaceutical manufacturers Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Goals Safety Containment Primary: fume hood containment Secondary: Directional room airflow-net negative airflow labs Ventilation (dilution) Comfort Temperature Ventilation Sound Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Goals Experiment Integrity Protection of research Uniform airflow, reduce drafts Stable room pressurization Energy-efficiency Current energy costs (Q1,2006): $7.50/cfm; 1000 cfm hood costs $7,500/yr) Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Goals Concerning your past involvement in lab controls: Has there been any other laboratory goals or needs that you were asked to address or meet? Copyright© 2006 TSI Incorporated

Laboratory Environments Use determines Requirements Animal Research Clinical labs Analytical Chemistry Teaching labs Biocontainment Forensic labs Nanotechnology Copyright© 2006 TSI Incorporated

Laboratory Environments Ideal laboratory configuration Designed to meet specific requirements for a given application or task Chemical lab will have different needs than a pharmaceutical lab or vivarium Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated See App Note LC-125 for More Information! Laboratory Safety Minimize long-term exposure to chemicals and fumes Primary Containment Fume hood Laminar flow bench BSC Snorkels Secondary Containment Laboratory itself Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Safety Objectives of Lab Ventilation A laboratory is built to accommodate materials and processes that contaminate air which may pose a health risk to the occupants Lab exhaust devices capture contaminants Lab exhaust system removes contaminants Lab ventilation system provides dilution air 100% Outside Air (4-12 air changes per hour) No Recirculation 24 hours/day, 7 days per week See App Note LC-125 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Safety Ventilation rate examples OSHA 4-12 ACPH Prudent Practices 6-12 ACPH ASHRAE Laboratory Ventilation 6-10 ACPH NFPA Minimum of 4 ACPH Typically greater than 8 ACPH when occupied See App Note LC-125 for More Information! Copyright© 2006 TSI Incorporated

Calculate Air Exchange Rate (ACPH) Air Changes Per Hour To calculate air exchanges per hour, use the following formula: L= Length W= Width H= Height CF= Cubic Feet (of lab space) ACPH = Air Changes (or exchanges) Per Hour Measure your room and work the following equation: L’ x W’ x H’ = CF (ex: 10’ X 12’ X 8’ = 960 CF with 180 cfm) 180 cfm / 960 CF = .1875/m .1875/m x 60m/h = 11.25 ACPH Copyright© 2006 TSI Incorporated

Examples of Air Changes per Hour Lab Space ACH OA Chemistry (standard Wet Lab) 10 100% Biological (Tissue Culture, DNA) 12 Special Lab (High Odor Generation) 30 Chemical Storage & Distribution Analytical Lab (Instrument Room) Equipment Room (autoclaves, centrifuges, freezers) 15 Computer server or dry electronics lab 12 to 60 20 cfm/person Animal rooms ISO Class 4 Clean room 660 ISO Class 5 Clean room 600 ISO Class 6 Clean room 200 ISO Class 7 Clean room 70 ISO Class 8 Clean room 20 Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Comfort Maintain space temperature More challenging with VAV Maintain ventilation Normally covered by ACPH for a given lab application Limit infiltration from sources other than HVAC system Reduce drafts or odd airflow patterns Minimize noise Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Experiment Integrity Protection of research and personnel is accomplished with: Laminar flow bench BSC Fume hoods Chemical storage Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Energy-Efficiency Exhaust as little air as possible without impacting safety or comfort Using less air is the most promising tactic VAV system Occupied and unoccupied modes Recover the heat Move air more efficiently Increased initial cost Saves operating expenses in the long-term Copyright© 2006 TSI Incorporated

Room Pressurization Control To maintain directional airflow by controlling supply and exhaust air flows in order to pressurize or depressurize the room relative to an adjacent space and to maintain a comfortable, non-fluctuating air temperature. Primary containment Laboratory fume hoods Biological safety cabinets Snorkels Secondary containment Laboratory room itself Copyright© 2006 TSI Incorporated

Room Control Strategies Constant Volume (CV) Control and/or balance supply & exhaust flows Monitor pressure only Constant Volume (CV) – Two Position Variable Air Volume (VAV) Control supply & exhaust flows under varying loads Monitor critical parameters NOTE: CV and VAV also used on lab hoods NOTE: Dampers and flow stations or Venturi valves can be used for either CV or VAV systems Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Constant Volume May monitor ΔP No ΔP Control Simple Read only 8635-M 8610/12,8650-MON CVV (Venturi Valve) Temp by others Requirements Closed door Low Traffic Stable reference 8635-M 8650-MON Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Constant Volume Use Constant Volume when Low hood density (large room with one hood) Low concern regarding energy usage Room ventilation rates of 10 ACPH or more Advantages Easy to design Minimizes cost of controls Few controls to maintain Disadvantages Equipment sized for full flows High initial and operating costs Difficulties arise when relocating equipment Limits future expansion Wastes energy Copyright© 2006 TSI Incorporated

Variable Air Volume (VAV) Use a Variable Volume System when High hood density If fume hood energy usage exceeds lab ventilation or thermal requirements Advantages Reduced energy costs less air conditioned supplied and exhausted air vary depending on loads Use of unoccupied mode with reduced flows saves energy Applying diversity factors Sizing equipment based on expected flows as opposed to maximum flows Pressure-independent VAV controls adapt to system changes Maintain constant face velocity regardless of sash position Modulate supply and exhaust based on room ΔP or temperature demand Disadvantages Reduced airflows and energy usage are dependent on good hood user sash position management Increased HVAC system complexity Higher installation costs Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated VAV Control Types Direct pressure Measure room pressure differential Maintain it Flow tracking Measure supply and exhaust air flows Maintain an offset between supply and exhaust flows Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated VAV Control Types Flow tracking with pressure monitoring Measure supply and exhaust air flows Monitor pressure differential Maintain an offset between supply and exhaust flows Flow tracking with pressure reset (AOC) Measure pressure differential Adjust offset between supply and exhaust flows based on pressure measurement Copyright© 2006 TSI Incorporated

VAV Control Type Features   Direct Pressure Control Flow Tracking Flow Tracking with ΔP monitoring Control with ΔP feedback Measures room ΔP X Modulates supply and exhaust flows Measures supply and exhaust flows Fixed flow offset Adjusts flow offset to meet room ΔP set point Copyright© 2006 TSI Incorporated

Factors to consider in Determining Control System Strategy Number of hoods Room volume Energy costs Room Ventilation Rates Hours of Operation (occupied/unoccupied hours) Heat generation in labs Number of researchers Type of lab work being performed Open or closed lab Tightness of constructed envelope Complexity of cleanliness requirements Speed of disturbances and response Duct conditions for flow measurement Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated VAV Control Loops Direct pressure Closed loop on pressure Flow tracking Closed loop on flow Open loop on pressure Flow tracking with pressure monitoring Flow tracking with room pressure feedback Copyright© 2006 TSI Incorporated

Open Loop on Pressure – Closed Loop on Flow Copyright© 2006 TSI Incorporated

Closed Loop on Pressure – Closed Loop on Flow Copyright© 2006 TSI Incorporated

Direct Pressure Control Model 8636 8650 Copyright© 2006 TSI Incorporated

Direct Pressure Control Measure room pressure differential with thru-the-wall sensor Modulate supply and exhaust to maintain room pressure differential set point Measure the supply flow to set minimum ventilation rate and to determine ACPH Copyright© 2006 TSI Incorporated

Direct Pressure Control Closed loop on pressure Adjusts supply and exhaust to maintain room pressure differential and reheat Easy to implement Safest Copyright© 2006 TSI Incorporated

Direct Pressure Control Requirements Closed door with low traffic Stable reference Fluctuations in reference space will cause disturbances within the lab Supply flow measurement is required for ventilation control and to determine ACPH TSI Models 8635, 8636 Copyright© 2006 TSI Incorporated

Direct Pressure Control Used In Labs where containment is critical Small closed labs Low cost is key Copyright© 2006 TSI Incorporated

Direct Pressure Control Most engineers / consultants understand Works very well when properly applied ΔP guaranteed Copyright© 2006 TSI Incorporated

Direct Pressure Control Sequence of Operations If fume hood flow increases and makes space more negative, then … Controller senses an increased exhaust flow Controller gradually closes the general exhaust damper to minimum if required If ΔP set point is still not achieved … Controller gradually opens supply until ΔP set point is achieved Copyright© 2006 TSI Incorporated

Direct Pressure Control Sequence of Operations If fume hood flow decreases and makes space more positive, then … Controller senses a decreased exhaust flow Controller gradually opens the general exhaust damper to maximum if required If ΔP set point is still not achieved … Controller gradually closes supply until ΔP is achieved Copyright© 2006 TSI Incorporated

Direct Pressure Control Sequence of Operations If the door to the lab opens, then … Controller senses the room ΔP go toward neutral Controller quickly closes supply to minimum if required If ΔP set point is still not achieved … Controller quickly opens the general exhaust damper to maximum if required until ΔP is achieved Copyright© 2006 TSI Incorporated

Direct Pressure Control Sequence of Operations If the lab temperature increases, then … Controller senses temperature increase Controller closes reheat valve If, after 3 minutes, the lab is still too warm … Controller gradually increases supply Controller senses ΔP decrease Controller increases general exhaust to meet ΔP set point Copyright© 2006 TSI Incorporated

Direct Pressure Control Sequence of Operations If the lab temperature decreases, then … Controller senses temperature decrease Controller opens reheat valve If, after 3 minutes, the lab is still too cold … Controller gradually decreases supply Controller senses ΔP increase Controller decreases general exhaust to meet ΔP set point Copyright© 2006 TSI Incorporated

Direct Pressure Controller Components 8635-C, 8636 8635-C includes: 800199 Controller Output Cable, 4-cond., 25 ft. 800224 SureFlow Room Pressure Controller 800326 SureFlow Room Pressure Sensor w/ Cable 800420 24-VAC Transformer with Cable 8636 includes: 800199 Controller Output Cable, 4-cond., 25 ft. 800326 SureFlow Room Pressure Sensor w/ Cable 800420 24-VAC Transformer with Cable 800775 8636 SureFlow Room Pressure Controller Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Flow Tracking Control 8681 8650 Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Flow Tracking Control Measure supply and exhaust air flows Exhaust flow is more than supply flow (negative lab) Difference is referred to as “offset” air Determine an offset between supply and total exhaust flows Total exhaust includes fume hoods, general exhaust, snorkels, plus other exhaust devices Offset value is generally listed on the room schedule Determined by the number of doors or other penetrations into the lab space If unknown, use 10% of maximum exhaust Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Flow Tracking Control Modulate supply and exhaust flows to maintain offset Once lab is completed, offset value may be adjusted to sufficiently create a negative space Measure the supply flow to set minimum ventilation rate and to determine ACPH Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Flow Tracking Control Controls flows to numerical set points Exhaust flow greater than supply flow (labs) Difference is referred to as offset Closed-Loop on Flow Measure and control supply and exhaust flows Open-Loop on Pressure Differential pressure set point not guaranteed Requirements All flows are measured Stable air flows TSI Models: 8680, 8681 & 8682 Copyright© 2006 TSI Incorporated

Flow Tracking Control, Calculating Offset Flow Measured fume hood flows = 1400 cfm Measured snorkel flows = 150 cfm Measured general exhaust + = 350 cfm Total exhaust = 1900 cfm “Offset” requirement per schedule - = 200 cfm Supply air flow rate set to = 1700 cfm Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Flow Tracking Control The only option for open labs or labs with no suitable reference space Labs where containment is not critical Labs designed around competition Remember Doesn’t measure or guarantee room differential pressure Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Flow Tracking Control Engineers/Consultants understand ΔP not guaranteed Copyright© 2006 TSI Incorporated

Flow Tracking Control Sequence of Operations If fume hood flow increases and makes space more negative, then … Controller senses an increased exhaust flow Controller gradually closes the general exhaust damper to minimum if required If offset is still not achieved … Controller gradually opens supply until offset is achieved Copyright© 2006 TSI Incorporated

Flow Tracking Control Sequence of Operations If fume hood flow decreases and makes space more positive, then … Controller senses a decreased exhaust flow Controller gradually opens the general exhaust damper to maximum if required If offset is still not achieved … Controller gradually closes supply until offset is achieved Copyright© 2006 TSI Incorporated

Flow Tracking Control Sequence of Operations If the door to the lab opens, then … Controller does nothing since it cannot sense the loss of room ΔP Copyright© 2006 TSI Incorporated

Flow Tracking Control Sequence of Operations If the lab temperature increases, then … Controller senses temperature increase Controller closes reheat valve If, after 3 minutes, the lab is still too warm … Controller gradually increases supply Controller gradually increases general exhaust to offset ΔP unknown Copyright© 2006 TSI Incorporated

Flow Tracking Control Sequence of Operations If the lab temperature decreases, then … Controller senses temperature decrease Controller opens reheat valve If, after 3 minutes, the lab is still too cold … Controller gradually decreases supply Controller gradually decreases general exhaust to offset ΔP unknown Copyright© 2006 TSI Incorporated

Flow Tracking Controller Components 8681-NS, 8682-NS 8681-NS includes: 800420 24-VAC Transformer with Cable 800776 8681 SureFlow Adaptive Offset Controller 8682-NS includes: 800420 24-VAC Transformer with Cable 1203217 TYPE 1 NEMA Hinged Box 800416 DIM COMM cable, shielded 2-wire, 25 ft. 800228 8682 SureFlow Digital Interface Module 800235 8682 SUREFLOW DDC CNTL W/O LON Note: All damper/actuators and flow stations must be added separately. Adaptive offset and flow tracking controllers require the addition of factory start-up. Copyright© 2006 TSI Incorporated

Flow Tracking with Pressure Monitoring Measure supply and exhaust air flows Maintain an offset between supply and exhaust flows Monitor pressure differential Differential pressure may vary Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Formerly referred by TSI as Adaptive Offset Control (AOC) Combines Direct Pressure and Flow Tracking controls Measures supply and exhaust air flows Measures room pressure differential Maintains an offset between supply and exhaust flows, more exhaust than supply Adjust offset between supply and exhaust flows to ensure differential pressure set point Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Closed loop on Flow Measures and controls supply and exhaust flows Closed loop on Pressure Measures room differential pressure Differential pressure measurement is used to adjust offset to maintain room pressure set point Models: 8680, 8681, 8682 Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Safety of direct pressure with stability of flow tracking Requires suitable reference pressure Maximum offset limits configurable Not used for Open labs Labs without suitable reference space NOTE: Controls on flow first Pressure is slow reset back to set point Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Engineers/Consultants don’t understand TSI is unique to this type of control strategy Need to sell value of this strategy Used to lock-out competition Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Sequence of Operations If fume hood flow increases and makes space more negative, then … Controller senses an increased exhaust flow Controller gradually closes the general exhaust damper to minimum if required If offset is still not achieved … Controller gradually opens supply until offset is achieved Controller adjusts offset to meet ΔP set point Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Sequence of Operations If fume hood flow decreases and makes space more positive, then … Controller senses a decreased exhaust flow Controller gradually opens the general exhaust damper to maximum if required If offset is still not achieved … Controller gradually closes supply until offset is achieved Controller adjusts offset to meet ΔP set point Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Sequence of Operations If the door to the lab opens, then … Controller senses low ΔP Increases offset to meet ΔP set point Controller gradually opens the general exhaust damper to maximum if required Controller gradually closes supply to minimum if required Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Sequence of Operations If the lab temperature decreases, then … Controller senses temperature decrease Controller opens reheat valve If, after 3 minutes, the lab is still too cold … Controller gradually decreases supply Controller gradually decreases general exhaust to offset Controller adjusts offset to meet ΔP set point Copyright© 2006 TSI Incorporated

Flow Tracking with Room Pressure Feedback Sequence of Operations If the lab temperature increases, then … Controller senses temperature increase Controller closes reheat valve If, after 3 minutes, the lab is still too warm … Controller gradually increases supply Controller gradually increases general exhaust to offset Controller adjusts offset to meet ΔP set point Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Temperature Control To meet comfort demands in a lab environment, integral temperature control is a standard feature on Models 8636, 8681 and 8682 controllers which feature adjustable: Temperature dead band range Temperature set point throttling range Temperature set point integral value Reheat valve control direction See App Note LC-129 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Temperature Control Temperature Dead Band (TEMP DB, ±0.1° - 1.0°F) Defines how sensitive controller needs to be regarding space temperature above and below temp set point If the TEMP DB is set to its maximum value (±1.0°F), the controller will not react to changes unless the space temperature rises above or below the set point by 1.0°F. If the TEMP DB is set to its minimum value (±0.1°F), the controller will react to space temperature changes 0.1°F above or below set point. See App Note LC-129 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Temperature Control If TEMP DB is set to 1.0°F, and the TEMP SETP is set to 70.0°F, the controller will not take corrective action unless the space temperature is below 69.0°F or above 71.0°F. See App Note LC-129 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Temperature Control Temperature Throttling Range (TEMP TR, ±2.0°-20.0°F) The temperature range in which the controller fully opens or closes the reheat valve Defines reheat valve movement Smaller TEMP TR range provides more precise control Larger TEMP TR range provides more stable control See App Note LC-129 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Temperature Control If TEMP TR is set to ±3.0°F, and the TEMP SETP is set to 70.0°F, the reheat valve will be fully open when the space temperature is 67°F. Similarly, the reheat valve will be fully closed when the space temperature is 73.0°F. See App Note LC-129 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Temperature Control Temperature Set Point Integral Value (TEMP Ti VAL) Manually changes the temperature control PI integral control loop variable Increasing TEMP Ti VAL will slow the control system which will increase stability Decreasing TEMP Ti VAL will speed up the control system which may cause system instability See App Note LC-129 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Temperature Control Reheat Control Direction (REHEAT DIR) Determines the temperature control signal’s output direction can be set to DIRECT or REVERSE if the control system closes the reheat valve instead of opening the valve, this option will reverse the control signal to now open the valve. See App Note LC-129 for More Information! Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Control How Does This All Work? A Model 8636, Model 8681 or Model 8682 controller receives a temperature input from a temperature sensor (1000 Ω Platinum RTD). The controller maintains temperature control by: Controlling supply and general exhaust for ventilation and cooling Controlling the reheat coil for heating Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Control The controllers have three configurable supply flow minimum set points. The ventilation set point (VENT MIN SET) is the minimum flow volume required to meet ventilation needs of the laboratory (ACPH). The temperature supply set point (COOLING FLOW) is the theoretical minimum flow required to meet cooling flow needs of the laboratory. The unoccupied set point (UNOCC SETP) is the minimum flow required when the lab is not occupied. the supply flow will not be modulated for space cooling when in UNOCC SETP mode; space temperature control will be maintained by modulating the reheat coil. Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Control The controller continuously compares the temperature set point to the actual space temperature. If set point is being maintained, no changes are made. If the space temperature is rising above set point: The controller will first modulate the reheat valve closed. Once the reheat valve has been fully closed for three minutes, the controller will then gradually begin increasing the supply volume by 1 CFM/second up to the COOLING FLOW set point. Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Laboratory Control If the space temperature decreases below the set point: The controller will first reduce the supply volume. Once the supply volume reaches its minimum (VENT MIN SET), the controller will then start a 3 minute time period. If, after 3 minutes the supply flow is still at the VENT MIN SET flow rate, the controller will begin modulating the reheat coil open to meet the heating demand. Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Capabilities Model 8635-M 8635-C 8636 8680 8681 8682 Room pressure monitor x   Room pressure controller Flow tracking controller Flow tracking controller with room pressure feedback Low alarm relay High alarm relay Alarm relay Switch input (occupied/unoccupied) Analog output (pressure) Supply flow input 1 2 4 Supply control Exhaust flow input Exhaust control Temperature input (0 - 10V) Temperature input (RTD) Temperature control Hood flow input 7 Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated TSI’s Position Full-featured controls Local support Choice of laboratory control method Fully digital controls – easy to configure & calibrate Software specials Tailor made to meet specific requirements Integration into BAS via: LON BacNet (currently via gateway) Modbus N2 Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Questions? Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Break Return by 2:45 to Continue Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Demo Lab Copyright© 2006 TSI Incorporated

Copyright© 2006 TSI Incorporated Wrap Up Copyright© 2006 TSI Incorporated