IEEE 519-2014 Mark Halpin November 2014.

Slides:



Advertisements
Similar presentations
Interharmonics IEEE T&D Show New Orleans Panel Session PN13 Non-periodic Currents: Causes,
Advertisements

Chapter 6 – Parallel Circuits
QUALITY AND TECHNOLOGY quality of the. When used in electrical installations where harmonics are present, the application of a conventional capacitor.
Introductory Circuit Analysis Robert L. Boylestad
Copyright© Voltimum Experts – not to be reproduced without prior consent of Voltimum UK Voltimum Expert Topic – Power Harmonics.
QUALITY & TECHNOLOGY HARMONIC PROBLEMS IN CAPACITOR BANKS.
Sistan & Balouchestan Electric Power Distribution Company
Chapter 4 DC to AC Conversion (INVERTER)
ENERGY CONVERSION ONE (Course 25741)
Chapter 12 RL Circuits.
Physics 2112 Unit 21  Resonance  Power/Power Factor  Q factor  What is means  A useful approximation  Transformers Outline:
ISSBN, Electronic faculty of Niš, November Use of distortion power for side identification of the harmonic polution Dejan Stevanović, Electronic.
Applying Harmonic Solutions to Commercial and Industrial Power Systems
Dry type transformers Zaragoza Traction application
Fundamentals of Power Electronics 1 Chapter 19: Resonant Conversion Chapter 19 Resonant Conversion Introduction 19.1Sinusoidal analysis of resonant converters.
Fundamentals of Power Electronics 1 Chapter 19: Resonant Conversion Upcoming Assignments Preparation for Lecture 2: Read Section 19.1, Sinusoidal analysis.
Power Engineering Society Chicago Chapter Reactive Power: Sources and Solutions 12 February 2003 David E. Mertz, PE Burns & McDonnell Engineers, Inc.
Announcements Be reading Chapter 3
Chapter 16 CMOS Amplifiers
Power Factor and Power Factor Correction
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
SHUNT CAPACITOR FUNDAMENTALS AND PROTECTION
Problem Solving Part 2 Resonance.
LOGO LINEAR CIRCUIT ANALYSISSAJID HUSSAIN QAZI MEHRAN U.E.T, KHAIRPUR CAMPUS A.C POWERS AND POWER FACTOR.
1 Locating Harmonic Sources System Impedance Impacts of Harmonics K-factor Interharmonics.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Fundamentals of Electric Circuits Chapter 11
F. Ferrandis_SP_ALPHA 2_BLOCK 2_Paper 35_Presentation Barcelona May POWER FACTOR CORRECTION WITHIN INDUSTRIAL SITES EXPERIENCES REGARDING.
Alternating Current Circuits
Oscillators with LC Feedback Circuits. LC Feedback elements are used for the generation of higher frequencies of oscillation. Because of lower unity gain.
1 Chelmsford Amateur Radio Society Advanced Licence Course Carl Thomson G3PEM Slide Set 4: v1.2, 20-Aug-2006 (3) Technical Aspects - AC Circuits Chelmsford.
Power in AC Circuits ELEC 308 Elements of Electrical Engineering
PQSynergy TM 2011 Harmonic Assessment of PEA North1, Chiangmai’s Customers in North Industrial Estate Chotepong Pongsriwat. M.Eng(EE) Chief of Power.
2. Terms and definitions1 # Terms and Definitions # Voltage Sags and Interruptions.
Applied Harmonics Control of Harmonics
Chapter 3 Power System Harmonic Mitigation. INTRODUCTION Power system harmonic issues have existed since the early 1900 ’ s. The earliest discovered issues.
Chapter 7 AC Power Analysis
Lyndonville Electric Department Feasibility Analysis Review December 2,
Capacitor Training Duck River Electric Membership Corp. Doug Simpson.
Voltimum Expert Topic – Power Harmonics. What are Harmonics? They are waveforms with frequencies that are multiples of the fundamental frequency (Typically.
Harmonics and PFC The love story By Pol Nisenblat.
Announcements Please read Chapter 3; start on Chapter 6
IEEE PES General Meeting, Tampa FL June 24-28, Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro.
Announcements For lectures 9 and 10 please be reading Chapter 3
© 2003 Eaton Corporation. All rights reserved. Understanding Harmonics Richard Molloy Technology Sales Manager, Power Quality.
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
Chapter 2 Harmonics and Interharmonics Theory
Analysis of Traction System Time-Varying Signals using ESPRIT Subspace Spectrum Estimation Method Z. Leonowicz, T. Lobos
7/08/2002PP.AFD.07 Harmonic Quality1 of 49 Yaskawa Electric America Harmonic Currents, Voltages and Your Building Power System.
Understanding Harmonic Limits per IEEE
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
Asea Brown Boveri Jumet S.A. FD 1/30 ASEA BROWN BOVERI Harmonic Problem ? Are Tuned Filters THE Solution ?
SARDAR VALLABHBHAI PATEL INSTITUTE OF TECHNOLOGY PREPARED BY: 1)BALDIWALA ALIABBAS ( ) 2)PARTH GUPTA ( ) 3)ANIL KHATIK ( )
Chapter 10 RC Circuits.
Protection of Power Systems
J.PRAKASH.  The term power quality means different things to different people.  Power quality is the interaction of electronic equipment within the.
Power Quality Issues Power Electronics Group.
Chapter 14 Series and Parallel AC Circuits. Objectives Become familiar with the characteristics of a series and parallel ac circuit Find the total impedance.
Parul Institute Of Technology Name Of Subject:-Electrical Machines Name Of Faculty:-(1) Suresh Sahoo (2) Yogendra Tiwari E&C 3 rd Sem. Prepaid By :- Sr.No.NameEnrolment.
RC Circuits (sine wave)
Part Three – Relay Input Sources
Power Factor Correction The Definitive power solution
Effects of Harmonics on Capacitors Electrical System
APFC-03 Reactive Power Compensation Method & Settings
Lesson 22: AC Power Factor and Power Factor Correction
HARMONIC MITIGATION USING PASSIVE FILTERS
Analysis of the Amplitude and Frequencies of the Voltage Magnification Transients in Distribution Networks due to Capacitor Switching Mohamed Saied Electrical.
Power System Harmonics
Protective Relaying Conference
Alternating Current Circuits
Presentation transcript:

IEEE 519-2014 Mark Halpin November 2014

What Has Stayed the Same? Most importantly, the overall philosophy Users are responsible for limiting harmonic currents System owner/operator are responsible for managing voltage quality All recommended limits apply only at the PCC Existing recommended limits are retained Some new ones added

What Has Been Changed? Philosophy of changes  Driven by 20 years of experience with 519-1992 and increased cooperation with IEC Multiple changes related to Measurement techniques Time varying harmonic limits Low voltage (<1 kV) harmonic limits Interharmonic limits Notching and TIF/IT limits Also “editorial” changes to Reduce document size Minimize miss-use of PCC-based limits Better harmonize with other standards projects

Measurements Recommended to use IEC 61000-4-7 specifications 200 ms (12 cycle @ 60 Hz) window gives 5 Hz resolution

Indices From IEC 61000-4-30 3 s “very short” value 10 min “short” value

Assessment of Limit Compliance What value should be compared against the limit?

Weekly Statistical Indices 95th or 99th percentile Value to be compared against limit

Changes to the Limits New voltage limit provision for low voltage (<1 kV) 5% individual harmonic, 8% total harmonic distortion Revised current limits for general transmission systems (> 161 kV) Maximum Harmonic Current Distortion in Percent of IL Individual Harmonic Order (Odd Harmonics) Isc/IL <11 11≤h< 17 17≤h< 23 23≤h< 35 35≤h TDD <25* 1.0 0.5 0.38 0.15 0.1 1.5 25<50 2.0 0.75 0.3 2.5 ≥50 3.0 1.15 0.45 0.22 3.75

Percentile-Based Voltage Limits Daily 99th percentile very short time (3 s) values should be less than 1.5 times the values given in Table … Weekly 95th percentile short time (10 min) values should be less than the values given in Table …

Percentile-Based Current Limits Daily 99th percentile very short time (3 s) harmonic currents should be less than 2.0 times the values given in Table … Weekly 99th percentile short time (10 min) harmonic currents should be less than 1.5 times the values given in Table … Weekly 95th percentile short time (10 min) harmonic currents should be less than the values given in Table …

Interharmonic Limits (“Recommendations”) Voltage-only 0-120 Hz limits based on flicker

Editorial Changes Improve definitions of all relevant terms to account for greater understanding and improved instrumentation Removal of “flicker curve” Removal of “tutorial” material (shorten document) Strengthen introductory material dealing with PCC-only applicability of recommended limits

Experience So Far Granted, this is limited mostly to “experiments” over the last 6-12 months Users with relatively stable harmonic emissions are essentially unaffected Users with rapidly-changing harmonic emissions may show reduced levels in measurements The 200 ms window acts as a smoothing filter Percentiles and multipliers appear to be relatively consistent with “short time harmonic” multipliers often used with 519-1992

Passive Mitigation of Power System Harmonics Mark Halpin November 2014

Outline Passive Filters Performance comparisons Conclusions Basic resonance concepts Single-tune filters C-type filters Performance comparisons Sensitivities to network conditions Overall effectiveness Conclusions

Series Resonance Concept capacitive inductive resonant frequency, wr Major concept: The impedance can become a very low value

Series Resonance In Practice Harmonic Voltages harmonic currents Effects include: 1. Heating in transformer 2. Fuse blowing at capacitor bank Typical resonances: --500 kVA, 12.47 kV, 5% --300-1200 kvar capacitor --wr=173-346 Hz (3rd-6th harmonic)

Parallel Resonance inductive capacitive resonant frequency, wr Major concept: The impedance can become a very high value

Parallel Resonance in Practice Harmonic Currents harmonic voltages Effects include: 1. Excessive voltage distortion 2. Capacitor bank fuse blowing Typical resonances --500 kVA, 480 V, 5% --400 kVA load, 80% pf lagging --pf correction to 95% lagging (120 kvar) --wr=547 Hz (9th harmonic)

Resonance Summary Series resonance Parallel resonance Widely exploited in harmonic filters Can lead to (harmonic) overcurrents Parallel resonance Frequently leads to (harmonic) overvoltages Sometimes used in blocking filters

Single-Tuned Filters “Single tune” means a single resonant point Classical Single-Tuned Filter C-type Filter

Applications Classic single-tuned filters C-type filters Common in industrial applications Inside facility At the PCC May use multiple filters, each tuned to a different frequency Traditionally used by utilities (declining) C-type filters Not common in industrial applications Becoming dominant in the utility environment Often used in conjunction with classic single-tuned designs Purpose is always the same—give harmonic currents a low-impedance path “to ground” Results in reduced voltage distortion

Application Considerations Ratings Capacitor RMS voltage Peak voltage RMS current kVA Reactor currents Peak current Losses

Filter Application Procedure Use frequency scan and harmonic study to determine requirements Number of filters (estimate) Tuned frequency for each Ratings (estimate) Start with lowest-frequency filter and work upward (in frequency) Each filter has parameters than can be at least partially optimized Consider credible system changes Assess impacts of filter parameter variations (±10%, maybe more) Evaluate total performance vs. requirements Specify required ratings (tweak design as necessary)

Comments on Frequency Scans These results indicate the potential for a problem They are extremely useful for designing filters Identification of high/low impedance frequencies (resonant conditions) Assessment of filter impacts on frequency response Alteration of undesirable impedance characteristics Demonstration of intentional low impedance path(s) They are subject to the accuracy of the models used Complete assessments require a harmonic study Results subject to model accuracy and assumptions Limit compliance Ratings of components

Demonstration Case Basic harmonic situation and sensitivities Series and parallel resonance conditions Mitigation using filters Single-tuned “industrial” C-type “utility”

Normal Condition Frequency Response—LV Filter Application (Are impedances high or low at known harmonic frequencies?)

Sensitivities—Substation SC Power (equivalent impedance at LV bus) Increasing severity and frequency with fault MVA Increasing severity (lower Z) and increasing frequency with Fault MVA Decreasing severity and Increasing frequency with fault MVA These sensitivities would be considered pretty small and insignificant

Sensitivities—Capacitor Status (equivalent impedance at LV bus) Low(er) frequency resonance not much affected by MV cap High(er) frequency resonance significantly affected by MV cap inductive capacitive Low(er) frequency resonances not much affected by things that impact high(er) frequency response—opposite not true!!

Sensitivities--Conclusions Large changes in system impedances, equivalents, etc., (fault MVA) are usually needed for significant effects Relatively small changes in capacitor bank status (or size) can have major impacts Filters must function under all of the potential scenarios

Design Approach Convert existing 480 V cap bank to filter bank by adding series reactor Capacitor voltage rating often will be exceeded in the end! X/R ratio of reactor can have significant impact Losses Performance Additional resistance can be added in series if needed (losses will increase!) for performance Note: Tuned frequency normally taken ≈5% below target Avoid overload Parameter variation

5th Harmonic Single-Tune Design

Filter Quality (“Q”) Factor The “sharpness” of the frequency response of a filter is often indicated by the filter “Q” The filter Q indicates Damping (less sharp characteristic—more damped) Lower Q, more damping Losses Lower Q, more losses For the previous slide Q=500, 50, 5, 1

A Closer Look at Q All this discussion of Q doesn’t look like a big deal…

Performance Evaluation (480 V Bus Impedance) 5th harmonic currents produce much less 5th voltage after filter Filter Q has an obvious impact on the entire response!

Performance Evaluation (LV Filter Impact on MV System at Cap Bank) 5th harmonic currents produce much less 5th voltage after filter Lower Q: Not as much filtering at 5th harmonic much less amplification at higher frequencies

Filtering on 12 kV Network Discussion so far based on filtering on customer-side (LV) Presumably associated with limit compliance If all network users are in compliance (currents), excessive voltage distortion may still exist Strong resonances can create large (noncompliant)voltage effects from small (within compliance) currents Solution is to filter on MV (utility) side Filter designs must account for LV filter presence (or not)

Same Approach for Filter Design Note: Tuned frequency normally taken ≈5% below target Avoid overload Parameter variation Q=100R=0.5184 W Q=10R=5.1835 W

12 kV Filter Performance Filter eliminates 5th resonance, but creates new ones that could be as bad (or worse). Best solution probably to split 600 kvar into 2x300 kvar and make two filters—5th and 7th

The C-type Filter Tuning (selection of parameters) is more difficult than for single tuned filters Starting from an existing cap bank Ctotal Step 1 Choose L to tune filter frequency as for single-tuned designs (based on Ctotal) Step 2 Divide existing capacitance into two parts C2 chosen so that L and C2 are series resonant (Z=0) at the power frequency C1 determined from “Ctotal-C2” (C in series combines as parallel) Step 3 Pick R to provide desired high(er) frequency damping

C-type Filter Example Will a 12 kV C-type perform better than the conventional single-tuned design? Existing 600 kvar bankCtotal=10.235mF L=10.367 W (27.5 mH) for ftune=300 Hz (from ST design) For 60 Hz “bypass” tuning, C2=255.85 mF C1=10.66 mF Select R for desired damping Note Q defined differently

C-type vs. ST Filter Performance

12 kV Filter Sensitivities (LV Cap/Filter Off-line) The real advantage of the C-type is control of HF response

Comments on Comparisons Both filter types are effective at the tuned frequency C-type has very low power frequency losses Single-tuned filter has resistive losses proportional to cap bank reactive current squared Low Q single tuned designs are helpful to reduce secondary resonances created by filter additions Alternative is to add secondary filters Low Q C-type designs provide good damping of secondary resonances by default Much less likely to encounter “secondary” problems C-type designs make poor utilization of existing cap banks Consider using one bank for var compensation with a separate filter installation

Passive Filter Conclusions Two main types exist—both work Single tuned Main advantages: Simplicity, up-front cost Main disadvantages: losses, can create secondary problems C-type Main advantages: Low losses, HF response Main disadvantage: up-front cost, poor utilization of existing cap banks Frequency scans are a great tool for filter design A harmonic study is required to determine necessary ratings

Backup Slides

Basic Frequency Scan Concepts (from load to 12 kV cap bank--focus on parallel resonance) 1 A @ 6th harmonic produces this voltage 1 A @ 13th harmonic produces this voltage 1 A @ 60 Hz produces this voltage (drop)

Magnification Factors (a normalized frequency scan) 100% current @ 6th harmonic produces 80X voltage!!! 6th harmonic current required to be much smaller to produce 3% 6th harmonic voltage (IEEE 519 limit) Normal (100%) 60 Hz current produces normal voltage drop (maybe 5-10 %)

Applying Scan Results 5th harmonic current might be 20% (1/5) of the fundamental, but the MF=18. 5th harmonic voltage of (5-10%)*18/5=18% or more could be produced  A filter may be needed if the current is this large Normal (100%) 60 Hz current produces normal voltage drop (maybe 5-10 %)