2014 TWIN STATE SEMINAR JULY 18, 2014 Impact of CMS’ Adoption of 2012 NFPA 101 & 99 Dave Dagenais, CHFM, CHSP, FASHE.

Slides:



Advertisements
Similar presentations
FHM TRAINING TOOLS This training presentation is part of FHM’s commitment to creating and keeping safe workplaces. Be sure to check out all the training.
Advertisements

NFPA EDITION OVERVIEW AND DISCUSSION Presented by Dave Dagenais, BS, SASHE, CHFM, CHSP Tuesday, October 5, 2010 Not Speaking on Behalf of NFPA.
NFPA-101, LIFE SAFETY CODE, 2003 EDITION Chapter 15 Existing Schools
2009 Edition – NFPA 101 Steve Hornyak, DAHC, CDT, FDAI
Safety in Hospitals A Computer – Based Learning Program for Students.
Facilities Management and Design Chapter 4 Safety and Security systems.
Emergency Preparedness and Response
Electronic Locking and Exemption Request Form Training
General Safety Overview and Information
NFPA 72 and NFPA 101 Supervised Automatic Sprinkler System Overview
East Carolina University Compressed Gas Safety Training Program
Utility Management Providence Health System - Oregon Environment of Care.
CMS Proposed Rule § CMS: 2012 Life Safety Code Adoption Advocacy Liaison Meeting
Notes From ASHE Conference and CMS LSC Waiver Summaries
Barrier Management Symposiums Region 10 Feb 2016 Region 6 Apr 2015 Region 1 7/12/15 Region 5 8/3/14 Region 2 5/12-16/14 Region 3 Fall 2015 Region 4 Mar.
“Categorical CMS Waivers”
 Please mute your line to reduce background noise  Do not put us on hold if you have background music on your hold line.  At the end of the presentation.
Emergency Lighting Code Review Presented by Iota Engineering LLC.
Doug Hohbein Chief Plans Examiner Nebraska Fire Marshal Agency
The Life Safety Surveyor Facility Tour
January 16, 2014 Brad Keyes, CHSP Changes to the 2014 Acute Care & Critical Access Hospital Manuals on Life Safety Compliance.
Zone Valves.
DOH Survey Citation Update; What’s New, What’s Hot, What’s Not!
Texas Department of Insurance State Fire Marshall’s Office Sixth Report on State University Fire Safety January 2002.
Presented by David Dagenais, SASHE, CHFM, CHSP Tuesday September 27 th, 2011.
NSHE Annual Trade Show & Conference Brad Taylor, CHFM ASHE Region 8 Board Representative May 2, 2014.
Indiana Federation of Ambulatory Surgical Centers September 27, 2013 To promote and provide essential public health services.
Fire Electrical Back Security
2012 International Fire Code Adopted as the minimum fire safety standard by the State of Wyoming City of Sheridan must adopt the minimum standard to retain.
CSHE Los Angeles Chapter 2013 Annual Devin J Hugie, SASHE, CHFM, CHSP-FSM, CHEP.
WELCOME DBI & SFFD Meet the Pros October 11, 2007.
January 5, Review of Emergency Operations Plan Tasks and Citations Tips & tools for creating your plan and avoiding deficiencies.
NFPA EDITION OVERVIEW AND DISCUSSION Presented by Dave Dagenais, BS, SASHE, CHFM, CHSP Thursday, February 17, 2011 Not Speaking on Behalf of NFPA.
NFPA Edition Healthcare Facility Management Society Of New Jersey June 18, 2009.
Emergency Action Plans
Presented by Gene Cable, PE, FPE Dave Dagenais, BS, SASHE, CHFM, CHSP Friday, March 19, 2010.
EGRESS AND FIRE PROTECTION
Health Facilities Planning Seminar Plan Review Division Irvin J. Poke, AIA, Chief Todd Y. Cordill, NCARB, Assistant Chief Providing for Michigan’s Safety.
Business Owners and Managers and the Fire Code
The ASHE advocacy highway is a two-way street of communication between ASHE and chapter advocacy liaisons The goal of the advocacy highway is to support.
The Second Survey Point of Vulnerability How Should I Prepare for the Facility Tour? Healthcare Engineering Consultants.

The Physical Environment Tracers How Should I Prepare for the Physical Environment Tracers? Healthcare Engineering Consultants  Will limit.
Fire Safety By Alicia Civile and Alexandra Fernandez.
AIA Guidelines for Design and Construction of Hospital and Healthcare Facilities Presented By: Michael A. Rogers, PE
Exit Routes and Fire Protection
Courtesy: Jeff Anderson, RCDD Associate / Systems Project Manager Communications, Security & Technology Division October 14, 2015 Locking the Means of.
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC.
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
Part 5: Meeting the Challenge of the “EC Tracers” Healthcare Engineering Consultants How Should I Prepare for the “EC Tracer” Part of the Survey?
NFPA 2 Overview Susan Bershad, Staff Liaison, NFPA.
COMMON DOH SURVEY CITATIONS UPDATE RANDY BENSON WHS HEALTHCARE QUALITY SERVICE JANUARY 2016.
Presented by: Danny Webster ASSE 6020 Medical Gas Inspector ASSE Medical Gas Verifier Phone:
Utilities & Engineering Department16 Blossom St., Boston Introduction to the Hospital Emergency Power Supply System (EPSS) Jason D'Antona,
Transfer Station Safety OR WORKER AND PUBLIC RISK.
Flammable Liquids Directorate of Training and Education
And an update of 2012 Life Safety Code and Joint Commission Standards.
NFPA 99 – 2012 Building a better medical gas maintenance program.
Process Safety Management Soft Skills Programme Nexus Alliance Ltd.
CIHQ - All Rights Reserved 2017
ARCHITECTURAL SAFETY FEATURES –Exit Separations –Continuation of Exit Stairs from lower to upper floors –Discharge from Exits FIRE PROTECTION FEATURES.
Fire Door Inspections Qualified Training
East Carolina University Compressed Gas Safety Training Program
Brad Keyes, CHSP HFAP Engineering Advisor Jamie Crouch, BSBM, MHA
Electrical Receptacle Testing
General Requirements of NFPA 101
Ambulatory Health Care vs. Business Occupancy
Locking the Means of Egress in Health Care Facilities
Emergency Preparedness Requirements
National Fire Protection Association Update
Presentation transcript:

2014 TWIN STATE SEMINAR JULY 18, 2014 Impact of CMS’ Adoption of 2012 NFPA 101 & 99 Dave Dagenais, CHFM, CHSP, FASHE

CMS IS PROPOSING TO ADOPT NFPA 101 & NFPA 99 WITH THE FOLLOWING MODIFICATIONS

ADOPTION, CHANGE IN DEFINITION Changes definition of “health care occupancy” from applying to “4 or more patients” to “regardless of the number of patients served” Could apply to hospital outpatient depts.  Based on billing of hospital-based provider services in outpatient buildings

ROLLER LATCHES Does not allow the exception in the LSC that permits use of roller latches CMS standards have permitted use of roller latches for more than 20 years Roller latches have become common in behavioral health

ALCOHOL BASED HAND RUBS 2012 LSC allows ABHRs Accepts 2012 LSC requirements but adds “if installed to prohibit inappropriate access” – Interpretive guidance is needed to determine what this means.

SPRINKLER 4-HOUR RULE NFPA 25 formerly required evacuation or fire watch of facilities if a sprinkler system was out of service for more than 4 hours in a 24-hour period. This has been changed in NFPA 25 to 10 hours to accommodate a “work day.” CMS proposes going back to the 4-hour period.

CMS WILL REQUIRE OR SMOKE VENTS Required when flammable anesthetics were used Removed as operating room ACH increased, sprinkler requirements were added, severity of fire risk and extent decreased

36" SILL HEIGHT Okay for new construction As written will apply to existing construction  How many existing facilities will this affect?  What is the cost to fix this condition? Is it worth it?  Staff should not break out windows during a fire  Patients should not be evacuated through windows

ADOPTION OF NFPA 99, 2012 EDITION Directly adopts NFPA 99: Health Care Facilities Code Except chapters: Chapter 7=IT andNurse Call Chapter 8=Plumbing Chapter 12=Emergency Preparedness Chapter 13=Security

CATEGORICAL WAIVERS

S&C Issued August 30th, 2013 Covers several “categorical waivers”

Allows substitution of a centralized computer system for (one) Category 1 medical gas master alarm. MEDICAL GAS MASTER ALARMS

Permits existing openings in exit enclosures to mechanical equipment spaces if they are protected by fire- rated door assemblies. OPENINGS IN EXIT ENCLOSURES

Reduces the annual diesel-powered generator exercising requirement from two (2) continuous hours to one hour and 30 minutes. EMERGENCY GENERATORS AND STANDBY POWER SYSTEMS

Allows more than one delayed-egress lock in the egress path where the clinical needs require specialized security measures or when a patient requires specialized protective measures for safety. DOORS

Allows: 1.Suite to suite egress 2.Allows one of the two required exits to enter an exit stair 3.Increase the sleeping room suite size up to 10,000 sq. ft. SUITES

Allows: 1.Reduction in the testing frequencies for sprinkler system vane-type and pressure switch type waterflow alarm devices to semiannual, 2.Electric motor-driven pump assemblies to monthly. EXTINGUISHING REQUIREMENTS

Allows the increase in size of containers used solely for recycling clean waste or for patient records awaiting destruction outside of a hazardous storage area to be a maximum of 96- gallons CLEAN WASTE & PATIENT RECORD RECYCLING CONTAINERS

Corridor Width New “Effective” Corridor width  Fixed furniture allowed  Rolling carts, equipment and movement aids allowed S&C Bench c.c. 5’-0” 8’-0”

DECORATIONS Increases the amount of wall space that may be covered by combustible decorations  20% Not Sprinklered  30% Sprinklered  50% Sprinklered in patient room (less than 4)

FIREPLACES Allows the installation of direct vent gas fireplaces in smoke compartments containing patient sleeping rooms and the installation of solid fuel burning fireplaces in areas other than patient sleeping areas

S&C OR Relative Humidity lowering the humidity requirement for operating rooms and other anesthetizing locations from at least 35percent to at least 20 percent.

HOW TO REQUEST A CATEGORICAL WAIVER Document your desire and that you comply with the waiver provisions in your policy and procedures manual. Verbally announce that you are requesting the waivers at each entrance interview of a survey Check with your State Agency and verify the waivers will be accepted for licensing Indicate Life Safety waiver requests in your BBI Indicate Environment of Care waiver requests in your management plan

NFPA EDITION OVERVIEW AND DISCUSSION

ITEMS DELETED-OVERVIEW Laboratory requirements Manufacturers’ requirements on electrical equipment Annexes B, D, & E are deleted. They are technology not used any longer. All of the Occupancy Chapters

NEW ITEMS-OVERVIEW Standard becomes a Code Fundamentals Chapter on Risk Information Technology and Communication Systems Plumbing Heating Emergency Management (new requirements) Security Fire Protection unique to Health Care Facilities

HOW THE CODE WORKS Determine the worst case procedure. Select the Risk Category. Select the systems or procedures in the Code that are prescribed by that level of risk Category

ADMINISTRATION (CHAPTER 1) To provide minimum requirements for the:  Performance  Maintenance, Testing and Inspection  Safe practices based on risk

ADMINISTRATION (CHAPTER 1) Applies to all health care facilities (other than home health) Applies to NEW construction and equipment only  altered or renovated or modernized Some testing and maintenance requirements apply to existing Emergency Management and Security apply to existing

REFERENCED PUBLICATIONS (CHAPTER 2) All Referenced publication material has been updated to most current version

DEFINITIONS (CHAPTER 3) Anesthetizing location – General anesthesia Battery powered lighting units – NFPA General anesthesia and levels of sedation  Deep sedation  General anesthesia  Minimal sedation  Moderate sedation Medical support gas

FUNDAMENTALS (CHAPTER 4) Category 1 - Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers shall be designed to meet system Category 1 requirements as defined in this code.

FUNDAMENTALS (CHAPTER 4) Category 2 - Facility systems in which failure of such equipment is likely to cause minor injury to patients or caregivers shall be designed to meet system Category 2 requirements as defined in this code.

FUNDAMENTALS (CHAPTER 4) Category 3 - Facility systems in which failure of such equipment is not likely to cause injury to the patients or caregivers, but can cause patient discomfort shall be designed to meet system Category 3 requirements as defined in this code.

FUNDAMENTALS (CHAPTER 4) Category 4 -Facility systems in which failure of such equipment would have no impact on patient care shall be designed to meet system Category 4 requirements as defined in this code.

FUNDAMENTALS (CHAPTER 4) 4.2* Risk Assessment. Categories shall be determined by following and documenting a defined risk assessment procedure. A.4.2 Risk assessment should follow procedures such as those outlined in ISO 31010, NFPA 551, SEMI S or other formal process. The results of the assessment procedure should be documented and records retained.

GAS AND VACUUM SYSTEMS (CHAPTER 5) Adding testing and inspection requirements on existing non-stationary medical booms Testing per manufacturers recommendations, every 18 months or based on risk assessment.

GAS AND VACUUM SYSTEMS (CHAPTER 5) Zone Valves. All station outlets/inlets shall be supplied through a zone valve as follows:  The zone valve shall be placed such that a wall intervenes between the valve and outlets/inlets that it controls.

“Wet Location” changes to “Wet Procedure Location” throughout the entire document ELECTRICAL SYSTEMS (CHAPTER 6)

Requires that overcurrent protection devices only be accessible to authorized personnel and not permitted in public access spaces ELECTRICAL SYSTEMS (CHAPTER 6)

Increases minimum number of receptacles  General Care – From 4 to 8  Critical Care – From 6 to 14  Operating Rooms – New requirement of 36

Permits fuel transfer pumps, receptacles, ventilation fans, louvers and cooling systems related to generators to be added to the life safety or critical branch (deleted from equipment branch) ELECTRICAL SYSTEMS (CHAPTER 6)

Monthly Generator Testing - 10 second transfer not required  (Annual Confirmation)

New section which permits switches in lighting circuits connected to Life Safety and critical branch as long as they don’t serve as illumination of egress as required by NFPA 101 ELECTRICAL SYSTEMS (CHAPTER 6)

New section on campus electrical systems being added Attempts to  clear up  conflicts  with NEC

ELECTRICAL SYSTEMS (CHAPTER 6) Requires all operating rooms to be wet procedure locations (unless risk assessment is done)

ELECTRICAL SYSTEMS (CHAPTER 6) Permits isolated power or ground fault protection within operating rooms

ELECTRICAL SYSTEMS (CHAPTER 6) Eliminates emergency system heading and equipment system heading and utilizes branches  Life Safety  Critical  Equipment

ELECTRICAL SYSTEMS (CHAPTER 6) Added text to permit a 0.1 second delay for selective coordination

IT AND COMMUNICATION (CHAPTER 7) New chapter covers  IT rooms  Fire protection  Nurse call  Emergency call  Staff emergency assistance

PLUMBING (CHAPTER 8) TIA will cover plumbing requirements Essentially will refer to other model codes or standards

TIA Nonmedical Compressed Air Potable Water. Potable water systems shall comply with applicable plumbing codes Nonpotable Water. Nonpotable water systems shall comply with applicable plumbing codes Water Heating. Maximum hot water temperatures shall comply with applicable plumbing codes Water Conditioning. Water shall be treated or heated to control pathogens in the water Nonmedical Compressed Air Grease Interceptors Grey Waste Water Clear Waste Water.

HEATING, VENTILATION AND AIR CONDITIONING (CHAPTER 9) New TIA will cover oxygen transfilling room requirements Waste Anesthesia Gas Disposal (WAGD)

TIA Commissioning Medical Gas Storage or Transfilling Natural Ventilation Mechanical Ventilation Waste Gas Medical Plume Evacuation

ELECTRICAL EQUIPMENT (CHAPTER 10) Chapter reorganized Testing requirements have been updated Leakage requirements have been updated

MULTIPLE OUTLET CONNECTIONS (POWER TAPS) Allows power taps that meet the following o Permanently attached o Some of load not over 75% o Cord meets NFPA 70 o Electrical integrity is regularly verified and documented o When new equipment is attached, integrity must be verified again.

GAS EQUIPMENT (CHAPTER 11) Temperature limitations to storage of cylinders must comply with (temperatures not to exceed 54o C or 130o F Specifies the requirements for carts and hand trucks that transport cylinders (must be self supporting and have appropriate chains.)

EMERGENCY MANAGEMENT (CHAPTER 12) Completely rewritten and expanded for 2012  Two categories of risk  In-patient facility is expected to be operable  In-patient and out-patient areas that augment the critical mission but not receive in-patients Requires a Hazard Vulnerability Analysis (HVA)  Natural Hazards  Human-caused Events  Technological Events

EMERGENCY MANAGEMENT (CHAPTER 12) Requires plans to manage resources and assets Requires Exercises Requires Evaluation of Exercises Special Care was taken to avoid conflicts with the Joint Commission and CMS

SECURITY MANAGEMENT (CHAPTER 13) Planning for protection of the Staff and Facility beyond disasters Requires a Security Vulnerability Assessment (SVA) Requires a responsible person Education requirements of security staff  Customer Service  Emergency Procedures  Use of Force  De-escalation  Use of Restraints

SECURITY MANAGEMENT (CHAPTER 13) Requires procedures for  Hostage  Bomb Threat  Workplace Violence  Disorderly Conduct  Restraining Orders

SECURITY MANAGEMENT (CHAPTER 13) Identifies known security sensitive areas  Emergency Departments  Pediatric and Infant Care units  Medication Storage  Clinical Labs  Forensic Patient Treatment Areas  Dementia or Behavior Health Units  Communications, data infrastructure and medical records

SECURITY MANAGEMENT (CHAPTER 13) Other subjects covered  Media control  Crowd control  Security equipment – follow NFPA 731  Employee practices  Security operations

HYPERBARIC FACILITIES (CHAPTER 14) Piping requirements have been updated New requirements for location of shutoff valve Updated requirements for reserve to central supply system New requirements for hyperbaric medical air system

FEATURES OF FIRE PROTECTION (CHAPTER 15) Chapter applies to new and existing Pulls most of text from NFPA 101 Fire alarm and detection Protection of gas cylinder storage HVAC detection requirements Defend in place requirements Closets sprinkler exception (less than 6 sq. ft.) Orientation and training requirements

NFPA EDITION OVERVIEW AND DISCUSSION

Normally occupied building service equipment support area People not present on a regular basis DEFINITIONS (CHAPTER 3)

Door leaves shall open readily from the egress side The requirements of shall not apply when door is exposed to elevator temperature in compliance with listing. MEANS OF EGRESS (CHAPTER 7)

Two release operation is permitted on existing doors when an occupant load does not exceed three providing it does not require simultaneous operation.

EXISTING HEALTHCARE OCCUPANCY (CHAPTER 19) Door locking is permitted for clinical or security needs provided staff can readily unlock doors. o Provisions must exist for rapid removal Remote control locks Keys carried by staff Other reliable means o Only one lock per door o More than one permitted with AHJ

DELAYED EGRESS LOCKS (CHAPTER 19) More than one delayed egress lock is permitted in the egress path

DELAYED EGRESS LOCKS (CHAPTER 19) Permits items in corridor such as wheeled equipment, carts in use, medical emergency equipment, patient lift and transport equipment and fixed furniture as long as it does not reduce the corridor width to less than 5 feet.

SUITES (CHAPTER 19) Permits sleeping suites to be 7500 sq. ft. where protected with sprinklers. Can go to 10,000 sq. ft. o Direct visual supervision o Supervised sprinkler system o Automatic smoke detection

SUITES (CHAPTER 19) Permits suites to egress through adjoining suite and more than one intervening room.

ALCOHOL BASED HAND RUB (CHAPTER 19) Exempts one dispenser per room from the 10- gallon per smoke compartment requirement.

DECORATIONS (CHAPTER 19) Increases the amount of wall space that may be covered by combustible decorations 20% Not Sprinklered 30% Sprinklered 50% Sprinklered in patient room (less than 4)

SPRINKLERS (CHAPTER 19) Sprinklers not required in clothes closets in patient sleeping rooms where the area does not exceed 6 sq. ft.

CONTAINERS FOR RECYCLING, CLEAN WASTE OR PATIENT RECORDS (CHAPTER 19) May be between 32 – 96 gallons if they meet FM standard 6921.

Thank You Questions? Dave Dagenais, CHFM, CHSP, FASHE