Active Power and Frequency Control

Slides:



Advertisements
Similar presentations
Spinning Reserve from Load Consideration of a Trial at Xcel Energys Cabin Creek Station Presentation to CMOPS January 7, 2005 John Kueck ORNL Brendan Kirby.
Advertisements

Electrical Engineering Department
CONTROLS OF SUPER CRITICAL BOILERS
ENERGY CONVERSION ONE (Course 25741)
1 FREQUENCY CONTROL -- Bhanu Bhushan -- (April, 2011)
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
TUTORIAL 3 Q1 Draw and label a block diagram the elements of a DC power supply which receives an input from the 240 V; 50 Hz mains and produces an output.
DOD Microgrids The Missing Link: Microgrid Applications Michael Dempsey P.E. Burns & McDonnell June 12, 2013 © 2013 Burns & McDonnell. All Rights Reserved.
GENERATOR PROTECTION.
Bob Green Garland Power and Light
Power System Fundamentals
Design of LFC using Optimal Control Theory The optimal controller is designed to minimize the quadratic performance index of the following form For linear.
FREQUENCY CONTROL DURING BLACK START OPERATIONS
1 DISTRIBUTION SERVICE PROVIDER BLACK START TRAINING 2015.
Electric Drives FEEDBACK LINEARIZED CONTROL Vector control was invented to produce separate flux and torque control as it is implicitely possible.
POWER GRID CORPORATION OF INDIA LIMITED Presentation on ‘FREE GOVERNOR OPERATION” By D.K.Guru & S.P.Barnwal.
CHE 185 – PROCESS CONTROL AND DYNAMICS
FUNCTIONS OF THE GOVERNING SYSTEM
System Operator Conference NERC Standards Review for: Simulator Drill Orientation 2014 System Operator Conferences Charlotte NC & Franklin TN SERC/SOS.
SYNCHRONOUS GENERATORS
PRESENTATION FREQUENCY CONTROL
Course: EE447: Computer Applications in Power Systems
Chapter Summer 2. Comparator 3. Block Blocks in Series
Dynamic Behavior and Stability of Closed-Loop Control Systems
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Introduction to Process Control
Governor Response Sequence Bob Green Garland Power and Light ERCOT Future AS Workshop January 20, 2014.
Synchronous Generator
Frequency Control Turbine Governor Droop NERC Requirement
Chapter 6 Voltage Regulators - Part 1- VOLTAGE REGULATION Two basic categories of voltage regulation are:  line regulation;  load regulation. line.
Chapter 7 SYSTEM PROTECTION
1 © Alexis Kwasinski, 2012 Introduction Field Excitation Q Synchronous generators Input: Mechanical power applied to the rotor shaft Field excitation to.
Introduction to Industrial Control Systems
1 Cheng-Ting Hsu Chao-Shun Chen Islanding Operations for the Distribution Systems with Dispersed Generation Systems Department of Electrical Engineering.
Sixth Northwest Conservation & Electric Power Plan Adding Incremental Flexibility to the Pacific Northwest Power System? Maury Galbraith Northwest Power.
PDCWG Report to ROS August 12, 2010 Sydney Niemeyer.
Conclusions Innovative application of induction and synchronous generators in autonomous small hydropower plant Prof. M.T.E. Kahn NeuroMorphoGenics/NMG.
Cascade and Ratio Control
BAL-001-TRE-1 Primary Frequency Response in the ERCOT Region
ECE 576 – Power System Dynamics and Stability
Effect of generation loss and Frequency Response Characteristics (FRC) on tie-line flow to Southern Region under various scenarios and Target setting for.
DYNAMIC BEHAVIOR AND STABILITY OF CLOSED-LOOP CONTROL SYSTEMS
FREQUENCY CONTROL AND AUTOMATIC GENERATION CONTROL
Model Reference Adaptive Control (MRAC). MRAS The Model-Reference Adaptive system (MRAS) was originally proposed to solve a problem in which the performance.
PROCESS CONTROL SYSTEM (KNC3213) FEEDFORWARD AND RATIO CONTROL MOHAMED AFIZAL BIN MOHAMED AMIN FACULTY OF ENGINEERING, UNIMAS MOHAMED AFIZAL BIN MOHAMED.
EXCITATION SYSTEMS Copyright © P. Kundur This material should not be used without the author's consent.
Introduction to Power Supplies
Magnetic field due to an electric current
FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
-- Bhanu Bhushan -- < > (August, 2011)
Announcements Read Chapters 11 and 12 (sections 12.1 to 12.3)
GENERAL BACKGROUND AND SPEED GOVERNORS
Chapter 4 A First Analysis of Feedback Feedback Control A Feedback Control seeks to bring the measured quantity to its desired value or set-point (also.
Power Plant Construction and QA/QC Section 5.3 – Turbine and Engine Governors Engineering Technology Division.
Responsive Reserve Service Deliverability Review September 15,
Generation: Control & Economic Dispatch 2016 System Operator Seminar.
Restoration Concepts PEAK RC Training Classification: Confidential Version No.: 1.5 Date of Document: Document Owner/Author: B Pederson Classification:
Advanced control strategies. CONTROL SYSTEMS The process parameters which are measured using probes described in the previous sections may be controlled.
Control Engineering. Introduction What we will discuss in this introduction: – What is control engineering? – What are the main types of control systems?
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
SMJE 2103 Synchronous Generator. Scope of discussion 1)Construction 2)Rotation speed 3)Generated voltage 4)Equivalent circuit 5)Power and Torque 6)Testing.
MISS. RAHIMAH BINTI OTHMAN
7. FREQUENCY CONTROL AND REGULATING RESERVES
Parallel Operation of Synchronous Generators Based on Sections 5.9 of the Textbook.
Lesson 22: Active Power Division Between Alternators
Lesson 21: Alternator Capabilities and Mechanical Power Control
Introduction To Reactive Power
Sarath Chandrasiri / EPD / MEW DYNAMIC RESPONSE OF GAS TURBINES PRESENTED BY: THE DIRECTORATE OF ELECTRICITY PRODUCTION  K. A. CHANDRASIRI.
Automatic Generation Control (AGC)
ECE 476 POWER SYSTEM ANALYSIS
Presentation transcript:

CONTROL OF ACTIVE POWER AND FREQUENCY Copyright © P. Kundur This material should not be used without the author's consent

Active Power and Frequency Control The frequency of a system is dependent on active power balance As frequency is a common factor throughout the system, a change in active power demand at one point is reflected throughout the system Because there are many generators supplying power into the system, some means must be provided to allocate change in demand to the generators speed governor on each generating unit provides primary speed control function supplementary control originating at a central control center allocates generation In an interconnected system, with two or more independently controlled areas, the generation within each area has to be controlled so as to maintain scheduled power interchange The control of generation and frequency is commonly known as load frequency control (LFC) or automatic generation control (AGC)

Primary Speed Controls Isochronous speed governor an integral controller resulting in constant speed not suitable for multimachine systems; slight differences in speed settings would cause them to fight against each other can be used only when a generator is supplying an isolated load or when only one generator in a system is required to respond to load changes Governor with Speed Droop speed regulation or droop is provided to assure proper load sharing a proportional controller with a gain of 1/R If precent regulation of the units are nearly equal, change in output of each unit will be nearly proportional to its rating the speed-load characteristic can be adjusted by changing governor settings; this is achieved in practice by operating speed-changer motor

ωr = rotor speed Y = valve/gate position Pm = mechanical power Figure 11.6 Schematic of an isochronous governor Figure 11.7 Response of generating unit with isochronous governor

Figure 11.8 Governor with steady-state feedback (a) Block diagram with steady-state feedback (b) Reduced block diagram Figure 11.9 Block diagram of a speed governor with droop

Percent Speed Regulation or Droop where ωNL = steady-state speed at no load ωFL = steady-state speed at full load ω0 = nominal or rated speed For example, a 5% droop or regulation means that a 5% frequency deviation causes 100% change in valve position or power output. Figure 11.10 Ideal steady-state characteristics of a governor with speed droop

Load Sharing by Parallel Units Figure 11.11 Load sharing by parallel units with drooping governor characteristics Figure 11.12 Response of a generating unit with a governor having speed-droop characteristics

Control of Generating Unit Power Output Relationship between speed and load can be adjusted by changing "load reference set point" accomplished by operating speed-changer motor Effect of load reference control is depicted in Figure 11.14 three characteristics representing three load reference settings shown, each with 5% droop at 60 Hz, characteristic A results in zero output; characteristic B results in 50% output; characteristic C results in 100% output Power output at a given speed can be adjusted to any desired value by controlling load reference When two or more units are operating in parallel: adjustment of droop establishes proportion of load picked up when system has sudden changes adjustment of load reference determines unit output at a given frequency

(a) Schematic diagram of governor and turbine (b) Reduced block diagram of governor Figure 11.13 Governor with load reference control Figure 11.14 Effect of speed-changer setting on governor characteristic

Composite System Regulating Characteristics System load changes with freq. With a load damping constant of D, frequency sensitive load change:  PD = D.  f When load is increased, the frequency drops due to governor droop; Due to frequency sensitive load, the net reduction in frequency is not as high. As illustrated in Figure 11.17, the composite regulating characteristic includes prime mover characteristics and load damping. An increase of system load by PL (at nominal frequency) results in a generation increase of PG due to governor action, and a load reduction of PD due to load characteristic

where The composite frequency response characteristic β is normally expressed in MW/Hz. It is also sometimes referred to as the stiffness of the system. The composite regulating characteristic of the system is equal to 1/β Figure 11.17 Composite governor and load characteristic

Supplementary Control of Isolated Systems With primary speed control, the only way a change in generation can occur is for a frequency deviation to exist. Restoration of frequency to rated value requires manipulation of the speed/load reference (speed changer motor). This is achieved through supplementary control as shown in Figure 11.22 the integral action of the control ensures zero frequency deviation and thus matches generation and load the speed/load references can be selected so that generation distribution among units minimizes operating costs Supplementary control acts more slowly than primary control. This time-scale separation important for satisfactory performance.

Figure 11.22 Addition of integral control on generating units selected for AGC

Supplementary Control of Interconnected Systems The objectives of automatic generation control are to maintain: system frequency within desired limits area interchange power at scheduled levels correct time (integrated frequency) This is accomplished by using a control signal for each area referred to as area control error (ACE), made up of: tie line flow deviation, plus frequency deviation weighted by a bias factor Figure 11.27 illustrated calculation of ACE Bias factor, B, set nearly equal to regulation characteristic (I/R + D) of the area; gives good dynamic performance A secondary function of AGC is to allocate generation economically

Figure 11.27 AGC control logic for each area

Figure 11.28 Functional diagram of a typical AGC system

Underfrequency Load Shedding Severe system disturbances can result in cascading outages and isolation of areas, causing formation of islands If an islanded area is undergenerated, it will experience a frequency decline unless sufficient spinning generation reserve is available, the frequency decline will be determined by load characteristics (Fig. 11.30) Frequency decline could lead to tripping of steam turbine generating units by protective relays this will aggravate the situation further There are two main problems associated with underfrequency operation related to thermal units: vibratory stress on long low-pressure turbine blades; operation below 58.5 Hz severely restricted (Fig. 9.40) performance of plant auxiliaries driven by induction motors; below 57 Hz plant capability may be severely reduced or units may be tripped off

Fig. 11.30 Frequency decay due to generation deficiency (L) Fig. 9.40 Steam turbine partial or full-load operating limitations during abnormal frequency, representing composite worst-case limitations of five manufacturers ©ANSI/IEEE-1987

Underfrequency Load Shedding (cont'd) To prevent extended operation of separated areas at low frequency, load shedding schemes are employed. A typical scheme: 10% load shed when frequency drops to 59.2 Hz 15% additional load shed when frequency drops to 58.8 Hz 20% additional load shed when frequency reaches 58.0 Hz A scheme based on frequency alone is generally acceptable for generation deficiency up to 25% For greater generation deficiencies, a scheme taking into account both frequency drop and rate-of-change of frequency provides increased selectivity Ontario Hydro uses such a frequency trend relay Fig. 11.31 Tripping logic for frequency trend relay