LHC UPS Systems and Configurations: Changes during the LS1 V. Chareyre / EN-EL LHC Beam Operation Committee 11 February 2014 EDMS No /02/2014
Outline UPS systems and replacement project during LS1 New configuration in the alcoves and LHC odd points New configuration in LHC even points New powering interlock rules EMC considerations Conclusion 2EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
UPS Systems for the LHC Critical equipment around the LHC powered by Uninterruptible Power Supply (UPS) systems QPS (Quench Protection System), Beam Dump System, Beam Loss Monitor, etc. Machine Protection Cryogenics and vacuum control systems, power converters auxiliary circuits, etc. Machine Availability UPS principle Continues to provide power to critical loads whenever the input power fails for the time given by the backup battery Nominal conditions: load powered via the double conversion path Input source failure: the load remains supplied by the inverter using the battery stored energy Load automatically transferred to the bypass line in case of: Internal UPS failure End of battery autonomy (requires bypass AC source available) Short-circuit or overload on the downstream distribution (unlikely) Fully automatic, load transfers < 1 ms 3 LHC Beam Operation Committee Changes in UPS Configurations EDMS No /02/2014
LHC UPS Systems Replacement Project Replacement of the existing APC Silcon UPS systems during the LS1(see EDMS ) Project motivations: Improve the reliability Decrease the failure rate Minimize LHC run time losses Change of UPS system topology: come back to the conventional double conversion UPS topology (with output isolation transformer) 4 Delta Conversion Double Conversion EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
Basic Requirement for the QPS Basic requirement for a safe powering: 2 independent power paths and protected by upstream UPS systems So-called F3 and F4 power lines distributed all along the tunnel QPS redundant equipment connected to F4 5EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
UPS Configurations before the LS1: Alcoves (REs) and Odd Points Basic requirement: 2 independent power paths and protected by upstream UPS systems No link between both UPS units 6 Output UPS power protected UPSs interfaced with the Powering Interlock Controller (PIC): Magnet powering stopped when loosing one UPS EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
New UPS Configurations in the Alcoves (REs) and Odd Points 3 rd UPS (UPS backup) powering the bypass of both UPS F3 and UPS F4 = Stand-by redundancy ‘Natural’ redundancy: no communication bus between the 3 UPS units 7 Output UPS power protected Distribution Unchanged EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
Tolerance to the First Failure Example: UPS F3 internal failure UPS F3 transfers to bypass instantaneously UPS backup takes over the F3 load 2 power paths still protected After a failure, we come back to the same situation as today (but with conventional UPS systems!) 8 Output UPS power protected Output UPS power NOT protected Failure of a second UPS in the same zone will stop the magnet powering (PIC triggered) EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
UPS Configurations in LHC Even Points (Before 2009) 9 2 parallel-redundant UPS systems in: UA (IP left side) US UA (IP right side) EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
UPS Configurations in LHC Even Points: before LS1 10 Redundant QPS equipment powered from the UPS system located in the adjacent zone F3 and F4 lines always powered from 2 different redundant UPS configurations (one in US, one in UA) Allowed to preserve parallel-redundant UPS systems in UAs and USs Was already tolerant to the first UPS failure (in each zone) EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
New UPS Configurations in LHC Even Points 11 Distribution remains unchanged Standby redundancy applied in UAs and USs F3 and F4 lines still powered from 2 different redundant UPS configurations (one in US, one in UA) EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
Tolerance to the First Failure (in each Zone) 12 Example: failure of the first UPS in UA Transfers to bypass instantaneously UPS backup takes over full load in UA Redundant power paths still protected Failure of one UPS in the adjacent zone (US in this case) is allowed Failure of 2 UPS units in the same zone will stop the magnet powering (PIC triggered) EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
New Powering Interlock Rules One single UPS failure = 2 power paths still protected = No PIC triggered New rules: Magnet powering can continue upon one single UPS failure Machine can start with 2 UPS systems out of 3 in the alcoves and LHC odd points Machine can start with one UPS system out of 2 in the UA and US zones New UPS configurations allows to wait for the next stop for repairing an UPS failure Gives us more time for preparing and optimizing the intervention UPS redundancy restored (and improved) Increases availability for all users, including EN-EL for fault repairs 13EDMS No /02/2014 LHC Beam Operation Committee Changes in UPS Configurations
New UPS Systems – EMC Considerations APC Silcon UPS systems well-known to produce noise at 8 kHz High frequency noise caused by switching transistors (IGBTs) for creating the sine wave at the output Switching frequencies varies according to the UPS manufacturer and the design New UPS specified according to applicable standards (IEC ) With the objective of attenuating perturbation at around 8 kHz: reduce noise level or shift it to higher frequencies (MHz frequencies are damped by distribution cables) 14 LHC Beam Operation Committee Changes in UPS Configurations EDMS No /02/2014
New UPS Systems – EMC Performance Industrial double conversion BORRI UPS selected from invitation to tender New UPS fully compliant with required standard (IEC : EMI and EMC) CERN internal (re-)qualification of the new UPS with the help of TE-EPC Noise immunity (UPS = victim) Burst immunity (high frequency, low power): within IEC standards Surge immunity (lightning, high power): very good (2 x IEC standard levels) Noise emission (UPS = aggressor) EMC conducted noise on AC input/output lines created by the UPS: within IEC standards UPS output (< 100 kHz): the peak at ~8 kHz (now at ~7 kHz) is reduced by a factor 5 UPS output (> 100 kHz): another peak appears at ~1.3 MHz (but still 4 times lower than the existing at 8 kHz) 15 LHC Beam Operation Committee Changes in UPS Configurations EDMS No /02/2014
EMC Performance Comparison 16 LHC Beam Operation Committee Changes in UPS Configurations EDMS No /02/2014 1MHz 8kHz
EMC Performance – Situation Assessment in the Tunnel 17 LHC Beam Operation Committee Changes in UPS Configurations EDMS No /02/2014 UPS output Downstream distribution switchboard Downstream distribution switchboard with UPS OFF Local distribution in tunnel with UPS OFF 5 m 150 m
Conclusion Change of UPS system topology: Conventional double conversion topology much more reliable New UPS system network configuration Delocalization in points 5, 7 and 8 (R2E project) UPS network majorly improved during LS1: Safe powering for machine protection system with independent and redundant paths Availability increased for all users and thus for LHC operation Tolerance to the first UPS failure in each zone Noise in the 8 kHz range reduced with new UPS systems Noise in the MHz range: ‘false’ problem since noise is attenuated along the distribution cables Up to now: ~80 new UPS BORRI installed and in operation on surface and underground, no problem reported today Filtering solution (MHz) being studied with TE-EPC 18 LHC Beam Operation Committee Changes in UPS Configurations EDMS No /02/2014