Synchronous Machines.

Slides:



Advertisements
Similar presentations
ENERGY CONVERSION ONE (Course 25741)
Advertisements

Synchronous Machines (AC Generators)
Synchronous Machines (AC Generators)
Power System Fundamentals
Chapter 4 Synchronous Generators
SYNCHRONOUS MACHINES SUBMITTED BY: Ms. APOORVA KANTHWAL
SYNCHRONOUS GENERATORS
Synchronous Machine The stator is similar in construction that of a induction motor The rotor can be Salient or Non-Salient (cylindrical rotor) Field excitation.
AC Machine.
Synchronous Motors and Generators
Synchronous Motors Constant-speed machine Propulsion for SS “Queen Elizabeth II” –44 MW –10 kV –60 Hz –50 pole –144 r/min.
Lesson 37 AC Generators II
Lesson 33 AC Generators.
Transformers.
Synchronous Generator
SYNCHRONOUS MACHINES SUBMITTED BY: Ms. JASPREET KAUR
Synchronous Motors When a synchronous machine is used as a motor, it is not self-starting. If the rotor field poles are excited by the field current and.
Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.
Department of Electrical and Computer Engineering
Induction Motors.
Module G1 Electric Power Generation and Machine Controls
ENERGY CONVERSION ONE (Course 25741) CHAPTER SIX (& S.G. parallel op. with Pow. Sys. of chapter 5) SYNCHRONOUS MOTORS.
ELECTRICAL ENGINEERING TECHNOLOGY EMT 113/4
Synchronous Induction
5.1 INTRODUCTION TO POLYPHASE SYNCHRONOUS MACHINES
Lecture 32Electro Mechanical System1 Synchronous Reactance  The value of X S can be determined by measurements of the open-circuit and short-circuit tests.
EMT 113/4 ELECTRICAL ENGINEERING TECHNOLOGY
AC Machine CHAPTER 4 EKT 103. AC Machine  Alternating current (ac) is the primary source of electrical energy.  It is less expensive to produce and.
Induction Machine The machines are called induction machines because of the rotor voltage which produces the rotor current and the rotor magnetic field.
Chapter 5. Synchronous Machines.
EET 221 Synchronous Machines Rafiqi.
By: Dr Rosemizi Abd Rahim
By: Dr Rosemizi Abd Rahim
Chapter 6 Synchronous Motors
AC Machine CHAPTER 3 EKT 415. AC Machine  Alternating current (ac) is the primary source of electrical energy.  It is less expensive to produce and.
Lecture 7: Synchronous machines
Magnetic field due to an electric current
Induction Motors. Introduction  Three-phase induction motors are the most common and frequently encountered machines in industry -simple design, rugged,
DC Machines.
BASIC ELECTRICAL TECHNOLOGY DET 211/3
SMJE 2103 Induction Motor.
SMJE 2103 Synchronous Generator. Scope of discussion 1)Construction 2)Rotation speed 3)Generated voltage 4)Equivalent circuit 5)Power and Torque 6)Testing.
EEE223 Energy Conversion II Md. Asif Uddin Khan Lecturer, EEE BRAC University 1.
Chapter 4 : AC Machine Lecturer : Puan Nordiana Binti Mohamad Saaid
SMJE 2103 Induction Motor.
Synchronous Machines.
Synchronous Generator
Lecture 31Electro Mechanical System1 Field Excitation The dc field excitation of a large synchronous generator is an important part of its overall design.
EEE223 Energy Conversion II Md. Asif Uddin Khan Lecturer, EEE BRAC University.
Lesson 12a: Three Phase Induction Motors
Hafizism february 2007 EMT462 Electrical System Technology LECTURE V mohd hafiz ismail level II jejawi.
SYNCHRONOUS GENERATOR
Lesson 34: AC Generators II
Principle of Operation
AC MACHINE Hasnizah Aris.
Lecture 7: Synchronous machines
Synchronous Motor Principle and basics.
Lecture 7: Synchronous machines
Synchronous Motors and Generators
Transformers. Transformer An A.C. device used to change high voltage low current A.C. into low voltage high current A.C. and vice-versa without changing.
Advanced Power Systems
Electrical Machines-II
Synchronous Machines.
EE216 Electrical Engineering
Principle of Operation
Think beyond.
EET 306 Synchronous Machines
Electrical Machines (EELE 3351)
Presentation transcript:

Synchronous Machines

Synchronous Machines Synchronous generators or alternators are used to convert mechanical power derived from steam, gas, or hydraulic-turbine to ac electric power Synchronous generators are the primary source of electrical energy we consume today Large ac power networks rely almost exclusively on synchronous generators

Synchronous Machines In a synchronous generator, a DC current is applied to the rotor winding producing a rotor magnetic field. The rotor is then turned by external means producing a rotating magnetic field, which induces a 3-phase voltage within the stator winding. Field windings are the windings producing the main magnetic field (rotor windings for synchronous machines); armature windings are the windings where the main voltage is induced (stator windings for synchronous machines

Construction Basic parts of a synchronous generator: Rotor - dc excited winding Stator - 3-phase winding in which the ac emf is generated The manner in which the active parts of a synchronous machine are cooled determines its overall physical size and structure

Various Types Salient-pole synchronous machine Cylindrical or round-rotor synchronous machine

5.1 INTRODUCTION TO POLYPHASE SYNCHRONOUS MACHINES Two types: 1-Cylindirical rotor: High speed, fuel or gas fired power plants To produce 50 Hz electricity p=2, n=3000 rpm p=4, n=1500 rpm 2-Salient-pole rotor: Low speed, hydroelectric power plants To produce 50 Hz electricity p=12, n=500 rpm p=24, n=250 rpm

Salient-Pole Synchronous Generator Most hydraulic turbines have to turn at low speeds (between 50 and 300 r/min) A large number of poles are required on the rotor Turbine Hydro (water) D » 10 m Non-uniform air-gap N S d-axis q-axis Hydrogenerator

Salient-Pole Synchronous Generator Stator Salient-pole rotor

Cylindrical-Rotor Synchronous Generator Turbine D » 1 m L » 10 m Steam d-axis q-axis Stator winding     High speed 3600 r/min Þ 2-pole 1800 r/min Þ 4-pole î    Direct-conductor cooling (using hydrogen or water as coolant) î   Rating up to 2000 MVA N Uniform air-gap Stator Rotor winding Rotor S Turbogenerator

Cylindrical-Rotor Synchronous Generator Stator Cylindrical rotor

Construction of synchronous machines Slip rings Brush

Operation Principle The rotor of the generator is driven by a prime-mover A dc current is flowing in the rotor winding which produces a rotating magnetic field within the machine The rotating magnetic field induces a three-phase voltage in the stator winding of the generator

Electrical Frequency Electrical frequency produced is locked or synchronized to the mechanical speed of rotation of a synchronous generator:   where fe = electrical frequency in Hz P = number of poles nm= mechanical speed of the rotor, in r/min

Rotation speed of synchronous generator By the definition, synchronous generators produce electricity whose frequency is synchronized with the mechanical rotational speed. (7.11.1) Steam turbines are most efficient when rotating at high speed; therefore, to generate 60 Hz, they are usually rotating at 3600 rpm and turn 2-pole generators. Water turbines are most efficient when rotating at low speeds (200-300 rpm); therefore, they usually turn generators with many poles.

Internal generated voltage of a synchronous generator The magnitude of internal generated voltage induced in a given stator is where K is a constant representing the construction of the machine,  is flux in it and  is its rotation speed. Since flux in the machine depends on the field current through it, the internal generated voltage is a function of the rotor field current. Magnetization curve (open-circuit characteristic) of a synchronous machine

Equivalent Circuit_1 The internal voltage Ef produced in a machine is not usually the voltage that appears at the terminals of the generator. The only time Ef is same as the output voltage of a phase is when there is no armature current flowing in the machine. There are a number of factors that cause the difference between Ef and Vt: The distortion of the air-gap magnetic field by the current flowing in the stator, called the armature reaction The self-inductance of the armature coils. The resistance of the armature coils. The effect of salient-pole rotor shapes.

Equivalent Circuit_2 generator motor Ia Ef Eres Vt jX jXl Ra + Equivalent circuit of a cylindrical-rotor synchronous machine

5.2.4 EQUIVALENT CIRCUTS Motor: Generator: Synchronous Reactance

Equivalent circuit of a synchronous generator Often, armature reactance and self-inductance are combined into the synchronous reactance of the machine: (7.18.1) Therefore, the phase voltage is (7.18.2) The equivalent circuit of a 3-phase synchronous generator is shown. The adjustable resistor Radj controls the field current and, therefore, the rotor magnetic field.

Three-phase equivalent circuit of a cylindrical-rotor synchronous machine The voltages and currents of the three phases are 120o apart in angle, but otherwise the three phases are identical. + Ia1 Ef1 jXs Ra Ia2 Ef2 Ia3 Ef3 VL-L VL-L =3Vt Vt

Phasor diagram of a synchronous generator Since the voltages in a synchronous generator are AC voltages, they are usually expressed as phasors. A vector plot of voltages and currents within one phase is called a phasor diagram. A phasor diagram of a synchronous generator with a unity power factor (resistive load) Lagging power factor (inductive load): a larger than for leading PF internal generated voltage EA is needed to form the same phase voltage. Leading power factor (capacitive load). For a given field current and magnitude of load current, the terminal voltage is lower for lagging loads and higher for leading loads.

Power and torque in synchronous generators A synchronous generator needs to be connected to a prime mover whose speed is reasonably constant (to ensure constant frequency of the generated voltage) for various loads. The applied mechanical power (7.22.1) is partially converted to electricity (7.22.2) Where  is the angle between EA and IA. The power-flow diagram of a synchronous generator.

Power and torque in synchronous generators The real output power of the synchronous generator is (7.23.1) The reactive output power of the synchronous generator is (7.23.2) Recall that the power factor angle  is the angle between V and IA and not the angle between VT and IL. In real synchronous machines of any size, the armature resistance RA << XS and, therefore, the armature resistance can be ignored. Thus, a simplified phasor diagram indicates that (7.23.3)

Power and torque in synchronous generators Then the real output power of the synchronous generator can be approximated as (7.24.1) We observe that electrical losses are assumed to be zero since the resistance is neglected. Therefore: (7.24.2) Here  is the torque angle of the machine – the angle between V and EA. The maximum power can be supplied by the generator when  = 900: (7.24.3)

Power and torque in synchronous generators The maximum power specified by (7.24.3) is called the static stability limit of the generator. Normally, real generators do not approach this limit: full-load torque angles are usually between 150 and 200. The induced torque is (7.25.1) Notice that the torque angle  is also the angle between the rotor magnetic field BR and the net magnetic field Bnet. Alternatively, the induced torque is (7.25.2)

Measuring parameters of synchronous generator model The three quantities must be determined in order to describe the generator model: The relationship between field current and flux (and therefore between the field current IF and the internal generated voltage EA); The synchronous reactance; The armature resistance. We conduct first the open-circuit test on the synchronous generator: the generator is rotated at the rated speed, all the terminals are disconnected from loads, the field current is set to zero first. Next, the field current is increased in steps and the phase voltage (whish is equal to the internal generated voltage EA since the armature current is zero) is measured. Therefore, it is possible to plot the dependence of the internal generated voltage on the field current – the open-circuit characteristic (OCC) of the generator.

Measuring parameters of synchronous generator model Since the unsaturated core of the machine has a reluctance thousands times lower than the reluctance of the air-gap, the resulting flux increases linearly first. When the saturation is reached, the core reluctance greatly increases causing the flux to increase much slower with the increase of the mmf. We conduct next the short-circuit test on the synchronous generator: the generator is rotated at the rated speed, all the terminals are short-circuited through ammeters, the field current is set to zero first. Next, the field current is increased in steps and the armature current IA is measured as the field current is increased. The plot of armature current (or line current) vs. the field current is the short-circuit characteristic (SCC) of the generator.

Measuring parameters of synchronous generator model The SCC is a straight line since, for the short-circuited terminals, the magnitude of the armature current is (7.28.1) The equivalent generator’s circuit during SC The resulting phasor diagram The magnetic fields during short-circuit test Since BS almost cancels BR, the net field Bnet is very small.

Measuring parameters of synchronous generator model An approximate method to determine the synchronous reactance XS at a given field current: Get the internal generated voltage EA from the OCC at that field current. Get the short-circuit current IA,SC at that field current from the SCC. Find XS from (7.29.1) Since the internal machine impedance is (7.29.2)

Example 1 A 200 kVA, 480-V, 60-Hz, 4-pole, Y-Connected synchronous generator with a rated field current of 5 A was tested and the following data was taken. from OC test – terminal voltage = 540 V at rated field current from SC test – line current = 300A at rated field current from Dc test – DC voltage of 10 V applied to two terminals, a current of 25 A was measured. 1. Calculate the speed of rotation in r/min 2. Calculate the generated emf and saturated equivalent circuit parameters (armature resistance and synchronous reactance)

Solution to Example 1 1. fe = electrical frequency = Pnm/120 fe = 60Hz Ia Ef Vt j1.02 0.2 + 1. fe = electrical frequency = Pnm/120 fe = 60Hz P = number of poles = 4 nm = mechanical speed of rotation in r/min. So, speed of rotation nm = 120 fe / P = (120 x 60)/4 = 1800 r/min 2. In open-circuit test, Ia = 0 and Ef =Vt Ef = 540/1.732 = 311.8 V (as the machine is Y-connected) In short-circuit test, terminals are shorted, Vt = 0 Ef = IaZs or Zs = Ef /Ia =311.8/300=1.04 ohm From the DC test, Ra=VDC/(2IDC) = 10/(2X25) = 0.2 ohm Synchronous reactance

The Synchronous generator operating alone: Example Example 7.2: A 480 V, 60 Hz, Y-connected six-pole synchronous generator has a per-phase synchronous reactance of 1.0 . Its full-load armature current is 60 A at 0.8 PF lagging. Its friction and windage losses are 1.5 kW and core losses are 1.0 kW at 60 Hz at full load. Assume that the armature resistance (and, therefore, the I2R losses) can be ignored. The field current has been adjusted such that the no-load terminal voltage is 480 V. What is the speed of rotation of this generator? What is the terminal voltage of the generator if It is loaded with the rated current at 0.8 PF lagging; It is loaded with the rated current at 1.0 PF; It is loaded with the rated current at 0.8 PF leading. c. What is the efficiency of this generator (ignoring the unknown electrical losses) when it is operating at the rated current and 0.8 PF lagging? d. How much shaft torque must be applied by the prime mover at the full load? how large is the induced countertorque? e. What is the voltage regulation of this generator at 0.8 PF lagging? at 1.0 PF? at 0.8 PF leading?

The Synchronous generator operating alone: Example Since the generator is Y-connected, its phase voltage is At no load, the armature current IA = 0 and the internal generated voltage is EA = 277 V and it is constant since the field current was initially adjusted that way. a. The speed of rotation of a synchronous generator is which is b.1. For the generator at the rated current and the 0.8 PF lagging, the phasor diagram is shown. The phase voltage is at 00, the magnitude of EA is 277 V,

The Synchronous generator operating alone: Example and that Two unknown quantities are the magnitude of V and the angle  of EA. From the phasor diagram: Then: Since the generator is Y-connected,

The Synchronous generator operating alone: Example b.2. For the generator at the rated current and the 1.0 PF, the phasor diagram is shown. Then: and b.3. For the generator at the rated current and the 0.8 PF leading, the phasor diagram is shown. Then: and

The Synchronous generator operating alone: Example c. The output power of the generator at 60 A and 0.8 PF lagging is The mechanical input power is given by The efficiency is d. The input torque of the generator is

The Synchronous generator operating alone: Example The induced countertorque of the generator is e. The voltage regulation of the generator is Lagging PF: Unity PF: Lagging PF: