2012 DOE/Contractor Fire Safety Workshop 11 Fire Suppression Technology for Safety Class Applications Presenter:David L. Oar, PE, FSFPE URS Energy & Construction.

Slides:



Advertisements
Similar presentations
PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-
Advertisements

Initiating Devices Manual Fire Alarm Boxes Ionization Smoke Detectors
Philip Anderson National Sales Manager System Sensor Canada.
Fired And Unfired Pressure Vessels
Open-Path Gas Detection - Philosophy of Use or The Story of Clouds.
Aspirated Smoke Detection
Airflow and BSC Biosafety and Biosecurity Awareness Training
KURSUS PENGENALAN KEPADA PERKHIDMATAN MEKANIKAL DALAM BANGUNAN
Utility Management Providence Health System - Oregon Environment of Care.
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
UL/FM Fire Pump Systems Lunch & Learn 04/18/05
737 PNEUMATICS MENU PRINCIPAL.
© Siemens Industry, Inc Confidential / Drive Your Business Forward Ignite the Power of New Products and Partnerships Siemens Fire Partner Summit.
Basic Fire Alarm Systems Overview
Medical Gas Alarm Panels
GST FIRE ALARM SYSTEM INTERNATIONAL BUSINESS DEPARTMENT , GST BEIJING
1 ASPIRATING SYSTEMS TRAINING e-series. 2 Overview e-series model range ASD Software  NetTracer  Detector Monitor  PipeTracer.
Unit 6.2. Mechanical and mixed mode ventilation TB Infection Control Training for Managers at National and Subnational Level.
U N C L A S S I F I E D Operated by the Los Alamos National Security, LLC for the DOE/NNSA Alternative approach to fire suppression – Class A, B, & C fires.
3-1 NFIRS 3 Structure Fire Module. 3-2 ObjectivesObjectives The participants will be able to: –describe when the Structure Fire Module is to be used.
AN INTRODUCTION TO THE CIRRUS PRO RANGE OF FIRE DETECTION DETECTORS
Enclosure Fire Dynamics
FIRE PROTECTION FUNDAMENTALS Chapter 7: WATER-BASED FIRE PROTECTION SYSTEMS & EQUIPMENT INTRO SLIDE.
12 th U.S./North American Mine Ventilation Symposium John Ascuaga’s Nugget Casino Resort Reno, NV, USA June 11, 2008.
Control Rooms  Serve as operations centers for the control and monitoring of a service or process  Flight control rooms  Power generation control rooms.
Gas Furnace Planned Maintenance
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
NFPA-12 Edition 2005 What “IMPACT” will the changes to NFPA-12 have on the design and installation of a CO 2 system?
Kidde Engineered Fire Suppression System 25 bar Equipment Hardware Engineered for use with 3M™ Novec™ 1230 Fire Protection Fluid.
Technology in Architecture Lecture 12 Electrical Equipment Electrical Power Management Fire Protection Systems Lecture 12 Electrical Equipment Electrical.
Patrick Thornton, SNS/FPE June 9, 2008
Fire Alarm System Initiating Devices
© 2012 Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code and the.
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
HVACR311 – Electrical for Refrigeration International Mechanical Code Relating to Refrigeration.
Syrereducerande anlägg – Vad är det ? Erik Secher Kidde Sweden AB.
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Select and deploy the appropriate hose lines to accomplish fire confinement and extinguishment.
High Sensitivity Smoke Detection
Atrium Fire Protection
CXS490 Carbon Dioxide Systems
World Health Organization
ACADs (08-006) Covered Keywords Containment Isolation, actuation logic, Description Supporting Material
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Overview Select and deploy the appropriate hose lines to accomplish fire confinement.
Laser- based smoke detectors
Introduction to the ASD Suppression Actuation Threshold (ASAT) Calculator July _03_ASAT Calculator Sales and Marketing Introduction Presentation.
1 HVACR318 – Refrigeration II International Mechanical Code Relating to Refrigeration.
FIRE SERVICES AT DATA CENTRE
Application – Identifying, Listing Equipment, and Documentation
2 IMPACT - THE FIRE PERMIT = Hot Work Permit 3 Welcome ! This course is linked to the use of IMPACT, so it is assumed that: You know how to use IMPACT.
Control Theory Control System Objectives  Establish a final condition  Provide safe operation  Eliminate the human element  Assure economical operation.
Roof Top Unit Overview (MAGNUM) Visit us at Revision- 12/17/2015.
HEATING AND COOLING SYSTEMS
Small Telco Facility Protection Small, business-critical spaces where business interruption cannot be tolerated.
Teknologi Pusat Data 12 Data Center Site Infrastructure Tier Standard: Topology Ida Nurhaida, ST., MT. FASILKOM Teknik Informatika.
Hot /Cold Aisle Containment  Traditional Data Center/Telco designs are changing significantly!
Presented by John Lewandowski and Mike Larabel Inspection, Testing, and Maintenance of Kitchen Hood Systems Michigan Fire Inspectors Society Winter Educational.
50% LBNE Concept Design WCD Infrastructure. Mechanical.
Class A, B, and now N NFPA 72, 2016 Edition Dan Horon President
MENU PRINCIPAL. THIS PRESENTATION INCLUDES THE SOURCES OF AIR, THE MAJOR SYSTEM COMPONENTS AND THE WAY THE CONTROLS AND INDICATORS ARE USED TO OPERATE.
Industrial Resources, Inc.
FIRE PROTECTION & SECURITY in ELI Beamlines
Section 6: Air-Conditioning (Heating And Humidification)
“ Highlighting the risks and challenges presented by modern data-center cooling systems in fire detection and suppression applications. “ Dave Boyack Sales.
Roof Top Unit Overview (MAGNUM)
NFIRS 3 Structure Fire Module
FBE03: Building Construction & Science
Parker domnick hunter. Safety of Electrical and
Presentation transcript:

2012 DOE/Contractor Fire Safety Workshop 11 Fire Suppression Technology for Safety Class Applications Presenter:David L. Oar, PE, FSFPE URS Energy & Construction Denver, CO Date: May 16, 2012

2012 DOE/Contractor Fire Safety Workshop 2 When do we need Safety Class Fire Suppression? Determined by Safety Analysis Purpose of Safety Class Fire Suppression Safety defines Safety Class functions –Must operate during seismic event –Operates automatically (when personnel are not present) –Survivability of equipment during an emergency

2012 DOE/Contractor Fire Safety Workshop 3 Fire Suppression System Safety Class Functions Extinguish postulated fires— Before fire is allowed to spread to other combustibles Before HEPA filters are compromised from excessive soot or temperature Prevent re-ignition— Determine length of time to insure re-ignition does not occur System must operate after design basis accident Identify design basis accidents

2012 DOE/Contractor Fire Safety Workshop 4 Safety Class Fire Suppression System Requirements To extinguish fires and maintain agent concentration, a system must— Detect fire at an early stage Reduce Airflow –Close supply air dampers –Shutdown supply air fans Discharge suppression agent

2012 DOE/Contractor Fire Safety Workshop 5 Safety Class Fire Extinguishment System Assumptions Assumptions : a.Postulated fires include waste drums, cable trays, and equipment fires b.Soot generation is reduced if postulated fires are extinguished at an early stage before much smoke is generated. c.Agent discharge is required for an extended period of time (e.g. minimum of 30 minutes) d.Planned performance requirements specify the system be able to actuate a second time for a design basis accident (e.g. to protect against re-flash or second fire before recharging suppression agent)

2012 DOE/Contractor Fire Safety Workshop 6 Fire Tetrahedron

2012 DOE/Contractor Fire Safety Workshop 7 Fire Growth Curve

2012 DOE/Contractor Fire Safety Workshop 8 The Four Stages of Fire Growth

2012 DOE/Contractor Fire Safety Workshop 9 Detectors and the Four Stages of Fire

2012 DOE/Contractor Fire Safety Workshop 10 Early Warning Detection Automatic fire detection systems play an essential role in the overall fire protection strategy: –First line of defense against fire (thermal) / smoke (non-thermal) threats –Early intervention by Operators to mitigate potential incidents –Provides early fire department response –Initiates activation of fire suppression system

2012 DOE/Contractor Fire Safety Workshop 11 Photoelectric/Ionization Detectors  Detectors are located on the ceiling.  Smoke must enter the detection chamber.  In photoelectric detectors, a light source detects visible smoke.  In ionization detectors, the presence of invisible particles of combustion is detected.  Alarm is sent to the Alarm Control Panel.

2012 DOE/Contractor Fire Safety Workshop 12 Beam Type Smoke Detectors  Smoke is detected when the light beam is obscured.  Can detect smoke over large open areas.  Subject to vibration and building movement.  Alignment is difficult.  Alarm is sent to the Alarm Control Panel.

2012 DOE/Contractor Fire Safety Workshop 13 Optical Flame (UV/IR) Detectors  Flames are detected inside the cone of vision.  UV can detect more quickly than IR.  Must bracket its vision to prevent extraneous alarms.  Alarm is sent to the Alarm Control Panel.

2012 DOE/Contractor Fire Safety Workshop 14 Air Sampling Detectors  Air is continuously drawn in piping network via a high-efficiency aspirator.  Air sample is filtered before entering the detection chamber.  Laser light source detects presence of particles of combustion.  Information is sent to Releasing Control Panel.

2012 DOE/Contractor Fire Safety Workshop 15 Video Imaging Detectors (VID)  Detects flames and smoke inside field of view.  Can detect reflected light from obscured flame.  Detects pluming smoke clouds.  Alarm is sent to the Alarm Control Panel.

2012 DOE/Contractor Fire Safety Workshop 16 Fire Detection Demonstration Video VESDA Warehouse Fire Tests

2012 DOE/Contractor Fire Safety Workshop 17 Detection Challenges Challenges for reliable fire detection: Smoke dilution HVAC interference –Airflow interferes with normal dispersion of smoke –Unpredictable air flow patterns –The cooling affects of HVAC systems will decrease the temperature of the smoke plume –Limitations on placement due to: Obstructions Velocity Temperature Accessibility for inspection, testing and maintenance once installed can be difficult and risks impacting operations Low Air Velocity Smoke Distribution High Air Velocity Smoke Distribution Unpredictable airflow patterns Air velocity affect on dispersion of smoke

2012 DOE/Contractor Fire Safety Workshop 18 Air Sampling Detectors can be installed on the ceiling, under the floor, and at the return air register.

2012 DOE/Contractor Fire Safety Workshop 19 Fire Suppression System Components  Early Warning Detectors –Detect fires during the incipient stage.  Releasing Panel –Process alarms & activate extinguishment system  Fire Suppression System –Discharges agent through piping system

2012 DOE/Contractor Fire Safety Workshop 20 Fire Suppression System Components

2012 DOE/Contractor Fire Safety Workshop 21 Seismic Design Category Reference Map

2012 DOE/Contractor Fire Safety Workshop 22 Redundant Air Sampling Detectors VESDA Supply Air Room Exhaust Protected Room

2012 DOE/Contractor Fire Safety Workshop 23 Air Sampling Detectors are Proven Worldwide Air sampling detectors can detect fires during the incipient stage, before visible smoke is present. –Reliability is 3.5 times per UL 268 This provides additional time to respond—(Pre- Discharge).

2012 DOE/Contractor Fire Safety Workshop 24 The VESDA VLC Detector  UL Listed for Area and In- Duct Applications.  IBC Certified for operation following seismic event.  Supervised alarm and trouble outputs.  Programmable from % obs / ft to 6.0% obs / ft.  Battery backup from Releasing Panel.

2012 DOE/Contractor Fire Safety Workshop 25 UL 268 Detector Reliability Prediction 4.1The maximum failure rate for a detector unit shall be 4.0 failures per million hours as calculated by a full part stress analysis prediction as described in MIL-HDBK 217 or 3.5 failures per million hours as calculated by a simplified parts count reliability prediction as described in MIL-HDBK 217, or equivalent, see Annex D. A “Ground Fixed” (GF) environment is to be used for all calculations. When actual equivalent data is available from the manufacturer, it is permissible that it be used in lieu of the projected data for the purpose of determining reliability.

2012 DOE/Contractor Fire Safety Workshop 26 Releasing Control Panel  Receives Pre-Discharge signal from detector.  Activates Pre-Discharge Alarm signal.  Closes isolation damper in supply air.  Sends signal to FACP and to Control Room  Receives Discharge signal from detector.  Activates Discharge Alarm signal.  Sends signal to activate Vortex® fire suppression system

2012 DOE/Contractor Fire Safety Workshop 27 RP-2002 Releasing Control Panel  UL Listed for releasing service.  IBC Certified for operation following seismic event.  Supervised initiating and alarm circuits.  Supervised releasing circuit.  Self contained battery backup.  80-character LCD Display.  History log with 256 entries.

2012 DOE/Contractor Fire Safety Workshop 28 Releasing Panels are IBC Seismic Qualified

2012 DOE/Contractor Fire Safety Workshop 29 Confinement Ventilation Control Supply Air Dampers Close Failsafe on Pre-Discharge Alarm Rel Pnl Supply Air Room Exhaust DP CTLR Protected Room In-Leakage Room Exhaust Dampers Controlled by Differential Controller

2012 DOE/Contractor Fire Safety Workshop 30 Confinement Ventilation Control Supply Air Dampers Close Failsafe on Pre-Discharge Alarm Room Exhaust Damper Closes to a Preset Percentage Airflow on Pre-Discharge Rel Pnl Supply Air Room Exhaust Protected Room In-Leakage

2012 DOE/Contractor Fire Safety Workshop 31

2012 DOE/Contractor Fire Safety Workshop 32

2012 DOE/Contractor Fire Safety Workshop 33

2012 DOE/Contractor Fire Safety Workshop 34

2012 DOE/Contractor Fire Safety Workshop

2012 DOE/Contractor Fire Safety Workshop 36 Victaulic Vortex™ Safety Class Nitrogen Supply –Multi-Zone System: Nitrogen sized for initial discharge plus 30 minutes extended discharge Largest Fire Area requires approximately 18% of the nitrogen supply Multiple zones become very cost efficient –Purposed configuration: Nitrogen utilized to reduce the oxygen level Regulated to a 25 PSI output at the emitter Two sets of four (4) tanks—Each with total of 140,000 scf on N 2

2012 DOE/Contractor Fire Safety Workshop 37 Nitrogen Storage / Process Rooms Nitrogen Supply –Multi-Zone

2012 DOE/Contractor Fire Safety Workshop 38 Typical Multi-Zone System High Pressure Valve Supervisory Switch Nitrogen Gas Supply* Water Supply Releasing Panel Fluid Control Module Zone Control Modules *High Pressure Cylinder (2500psi) Emitter: Series 953 Transducer feedback loop Emitter: Series 953

2012 DOE/Contractor Fire Safety Workshop 39 Conclusion  Safety Class requirements are determined by Safety Organization  System must be designed to meet requirements  Reliability must be assured  Provide detectors and suppression agent appropriate for the hazard being protected  Insure system availability with redundancy and supervision  Verify systems are designed and installed properly  Insure system components are tested and maintained properly