Seismic code and design standard for transmission line and substation in Japan September 3, 2003 Hajime Imura The Kansai Electric Power Co.,Inc.

Slides:



Advertisements
Similar presentations
SHIP LOADS AND STRESSES
Advertisements

Understanding Electrical TransmissionDemonstration A1 A Guide to the National Grid Transmission Model Demonstration A1 How is electricity generated and.
Seismic Code Highlights Determining what level of Seismic Restraints are Required Arkansas Fire Prevention Code 2002 Based on the IBC 2000.
Seismic Considerations & Power Bushings
INTRODUCTION OF ULTRA-HIGH VOLTAGE (UHV) 1000 kV AC TRANSFORMER
EQ1 INTRODUCTION TO EARTHQUAKE ENGINEERING. EQ2 Sequence  Plate movement  Type of faults  Wave motion  Energy release  Urban earthquake risk  Structural.
1 Transmission Fundamentals Chapter 2 (Stallings Book)
Chapter-3-1CS331- Fakhry Khellah Term 081 Chapter 3 Data and Signals.
Physics 1251 The Science and Technology of Musical Sound Unit 1 Session 9 Transients and Resonances Unit 1 Session 9 Transients and Resonances.
Fire Sprinkler Earthquake Protection – Sway Bracing
TRANSMISSION FUNDAMENTALS Review
Chile Observatories Earthquake Readiness Workshop La Serena, Chile December Seismic Retrofit of Existing Observatories Chile Observatories Earthquake.
S TRUCTURAL A NALYSIS OF M ECHANICAL M ODULES F OR M ODULAR D ESIGNED N UCLEAR P LANTS J UNE, 2011 By: Steven K. Sherfey, P.E. Presented By: Ankit (Andy)
Seismic design for the wind turbine tower (WP1.5 background document presentation) Institute of Steel Structures Aristotle Univ. of Thessaloniki.
DECLERCQ Jan BE Alpha 4 – Block 2 Barcelona May TRANSFORMERS FOR WIND TURBINES NEED FOR NEW DESIGNS OR BUSINESS AS USUAL Dr. Jan Declercq.
Assumption University Thailand EE4503 Electrical Systems Design Introduction 1.
Hydraulics.
Lecture 2 January 19, 2006.
IRENG07 1 Seismic Consideration Discussion for The Interaction Region Fred Asiri-SLAC.
SEISMIC ANALYSIS Stability of a slope can be affected by seismicity in two ways: earthquake and blasting. These seismic motions are capable of inducing.
Earthquake Predictibility, Forcasting and Early Warning Bill Menke October 18, 2005.
ULg : Pr. J.L. Lilien WISMIG meeting, Arlington, USA, May 2008 New trends on real time measurement on power lines : application to ampacity, aeolian vibrations.
Alternating Current, Power Distribution, and Voltage Systems
U U 1 Excitation of Structural Resonance Due to a Bearing Failure Robert A. Leishear David B. Stefanko Jerald D. Newton IMECE 2007 ASME, International.
Are High Tension Power Lines Necessary? JALEEL STERLING ASHLEY CARLONI DAVID BERNHART ELIZABETH ANDERSON.
Stu Nishenko, Khalid Mosalam, Shakhzod Takhirov, and Eric Fujisaki SEISMIC PERFORMANCE OF INSULATORS IN ELECTRIC SUBSTATIONS.
SELECTION OF SUPPORTING ARRANGEMENT FOR CRITICAL PIPING By DILEEP PILLAI.
Transmission Lines …….. Conductor Material
Analyses of tunnel stability under dynamic loads Behdeen Oraee; Navid Hosseini; Kazem Oraee 1.
1 A. Lipsky, N. Miteva, E. Lokshin Department of Electrical and Electronic Engineering Ariel University Center of Samaria Israel Electric Power Quality.
1 Introduction to Power Systems Expensive! Influential!Intrusive! Source: Riadh W. Y. Habash, Electromagnetic Fields and Radiation, Marcel Dekker, New.
December 3-4, 2007Earthquake Readiness Workshop Seismic Design Considerations Mike Sheehan.
WHO WANTS TO BE A MILLIONAIRE?
Earthquakes pg 123.   Seismometer- an instrument that measures earthquakes  Earthquake- is a series of low frequency shock waves traveling through.
Yuji Otake, Akito Araya and Kazuo Hidano
Experience you can trust. Hurricane Hardening Commission Staff Workshop on Electric Utility Infrastructure Richard E. Brown, PhD, PE Tallahassee,
APPLIED ELECTRICITY SS3
Lecture 1 – Power Quality INTRODUCTION TO POWER QUALITY Power Quality phenomenon-Terms and definitions-Various Power events in power quality - causes for.
1 TRANSMISSION SYSTEM OVERVIEW NETWORK OPERATING COMMITTEE April 17, 2007 New Mexico Transmission System Overview.
1. 2 CE-312 Engineering Geology and Seismology Instructor: Dr Amjad Naseer Lecture#15 Department of Civil Engineering N-W.F.P University of Engineering.
NATURAL FREQUENCY AND BUILDING RESPONSE structural engineers are keeping us safe.
Lee County Electric Cooperative 2007 Hurricane Preparedness Activities.
Along-wind dynamic response
Lesson 14 Test Method for Product Fragility 第 14 课 产品脆值试验方法.
Choice of Design Conditions 2 December 2015choise of design condition1.
Earthquake Resistant Building designs. Buildings are designed to withstand vertical forces. Buildings are designed to withstand vertical forces. If earthquakes.
Introduction  Utilities transmit electricity over power lines into home as an alternating current (AC) wave.  This is how power travels through wiring.
A Presentation On 132 KV GSS BEHROR
Distribution Systems-General
BASICS OF DYNAMICS AND ASEISMIC DESIGN
1 Transmission of Electrical Energy Electrical energy is carries by conductors such as overhead transmission lines and underground cables. The conductors.
EE 207: Fundamentals of Electrical Power Systems
Fatigue Analysis in ASME B31.3 Piping
Grid maintenance expenses Commerce Commission Workshop 2 March 2010.
Introduction High Voltage!!.
Basics Of Seismic Vibration Control
SUB-STATIONS.
By Dr. Moustafa Zayed Lecture 1
Seismic Waves Large strain energy released during an earthquake
Dead zone analysis of ECAL barrel modules under static and dynamic loads Marc Anduze, Thomas Pierre Emile – LLR CALICE Collaboration Meeting.
Elasticity and Oscillations
How the ground shakes? Dr. Syed Mohamed Ibrahim M.Tech., Ph.D., by
Lecture 2 Types of Loads By Dr. Moustafa Zayed.
Dead zone analysis of ECAL barrel modules under static and dynamic loads for ILD Thomas PIERRE-EMILE, Marc ANDUZE– LLR.
Seismic Moment Dr. Syed Mohamed Ibrahim M.Tech., Ph.D.,
Basics of electrical engineering
Introduction To Reactive Power
SPH3U UNIVERSITY PHYSICS
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
Presentation transcript:

Seismic code and design standard for transmission line and substation in Japan September 3, 2003 Hajime Imura The Kansai Electric Power Co.,Inc.

Contents 1. Basic concepts on seismic design of electric facilities 2. Seismic design of electric facilities - Overhead transmission line - Underground transmission line - Substation 3. Evaluation of the present seismic design 4. Summary

Basic concepts on seismic design of electric facilities Category 1Category 2 Dams LNG tanks Oil tanks Power generation facilities Transmission lines Substations Distribution lines Load dispatching center Telecommunications a) No serious trouble occurs for a Level A earthquake. There are two categories(Category 1 & 2) according to the kinds of facilities. Electric facilities performance that can be expected is decided by intensity of earthquake(Level A & Level B). Level A : An earthquake which occurs once or twice in the lifetime of facilities. Level B : An earthquake with a vertical shock or a trench-type earthquake which seldom occurs (ex. Hanshin-Awaji earthquake). a) No serious trouble occurs for a Level A earthquake. b) No serious damage on human lives occurs for Level B earthquake.

Seismic design of electric facilities 1. Overhead Transmission Line No criteria in the aspect of seismic design 40m/s wind earthquake [Overhead transmission tower is designed so as not to be fallen down by 40m/s-wind (typhoons are assumed). The wind force is severer than earthquake motions.]

Seismic design of electric facilities 2. Underground transmission line No criteria in the aspect of seismic design [Reason] Cables have flexibility and strength against earthquake motions, and it is laid with off-set considering thermal elasticity and good working conditions. (1) Cables It is designed based on seismic design of substation equipment. (2) Cable heads and oil supplying systems(for OF cables) [Reason] Polycon FRP Pipes (PFP) have been usually adopted. They have flexibility on their joints and can withstand earthquake motions. (3) Conduit and human maintenance hole No criteria in the aspect of seismic design

Seismic design of electric facilities 3. Substation (Outdoor) Porcelain type equipment (CB, DS, PCT, Cable head) Transformer BodyBushing Design force (horizontal) 3 m/s 2 5 m/s 2 - The force is assumed to be applied to the lower end of the equipment Design Technique * 1F and underground of indoor substation : Same as outdoor Others :designed one by one considering the motion of the building foundation Position of the force being applied foundation Transformer body Pocket Bushing Dynamic Static Resonant sine wave, 3 cycles -- 5 m/s 2

Evaluation of the present seismic design The present seismic design was established in 1980 based on the experience of “Off-Miyagi earthquake”, which occurred in We reviewed the present design after Hanshin-Awaji earthquake. Hanshin-Awaji earthquake occurred in 1995 [The viewpoints of evaluation] - Theoretical evaluation - Demonstrative evaluation earthquake Seismic Design of Substation ▼Off-Miyagi ▼Hanshin-Awaji ■ 1980 Dynamic Seismic Design □ (1998) review

Theoretical evaluation on Hanshin-Awaji earthquake 1) Frequency Expectation in return period is around 1000 years. Maximum acceleration Response coefficient Response acceleration Dominant frequency Shin-Kobe S/S5.84m/s m/s Hz KEPCO R&D Center 6.48m/s m/s Hz KOBE meteorological observatory Present seismic criteria 8.18m/s m/s Hz 3.0 m/s m/s 2 (1)(2)(1) * (2) Hz 2) Actual earthquake motions and response acceleration

Theoretical evaluation on Hanshin-Awaji earthquake 3) Response acceleration spectrum at Shin-Kobe S/S 4) Seismic strength of substation equipment - Porcelain insulators and bushings have some margin(about 2 times) of its strength considering the strength variation on the process. - Even if considered the variation of it strength, only 1% of the insulator would be damaged. Safety Factor Maximum Acceleration 26m/s 2 at 3.05Hz Acceleration(m/s 2 ) Natural frequency (Hz) (Cont’d) Design:14m/s 2 In specific frequency range( Hz), response acceleration exceeds the present seismic criteria(14m/s 2 ).

Demonstrative evaluation on Hanshin-Awaji earthquake 1) Strong earthquake motions, but little serious damage 2) Damaged equipment was designed based on older design. - Many of damaged equipment were designed based on older seismic design before 1978 and almost all of the equipment designed on the present design do not suffer significant damage. - Strong earthquake a) Shin-Kobe S/S : 5.84 m/s 2 b) KEPCO R&D center : 6.48 m/s 2 c) Kobe meteorological observatory : 8.8 m/s 2 - Some equipment were damaged in Itami & Shin-Kobe S/S, but not so much serious damage which leads to loss of function. 3) Experiences of other big earthquakes - There were strong earthquakes other than the Hanshin-Awaji, but we did not suffer severe damage.

Evaluation of the present seismic design (Cont’d) [Overhead transmission] According to the analysis of seismic response by using the waveform observed at Kobe meteorological observatory (8.1m/s 2 ; maximum acceleration in the Hanshin-Awaji), typical transmission towers of 500, 275, 77 kV have enough strength against maximum possible acceleration. [Underground transmission] Only some of the transmission line based on former design (laid without off-set) suffered damage. The present seismic design has good performances.

Summary (1) The present seismic criteria is: a) Substation Resonant 3 cycles sine wave - Porcelain type equipment : 3m/s 2 (Horizontal acceleration) - Transformer : 5m/s 2 (Horizontal acceleration) b) Overhead transmission line No criteria in the aspect of seismic design (If the structure withstand 40m/s-wind, enough strength for earthquake) c) Underground transmission line No criteria in the aspect of seismic design (The components have various flexibility and have enough strength.) (2) Experiences of strong earthquake such as the Hanshin-Awaji, proved good performance of the present seismic design.

End