Material used:  Tin  Lead  Zinc  Silver  Antimony  Copper  Aluminum.

Slides:



Advertisements
Similar presentations
Introduction to Switchgear
Advertisements

Electrical Installation
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
Contactors & Relays.
MOLDED CASE CIRCUIT BREAKER BASICS
Lesson 38 Shipboard Power
© ABB Ltd - ATLV /26/2015 Insert image here Fuses vs Fuseless Technology.
GENERATOR PROTECTION.
CASE STUDIES - PROTECTION OF POWER DISTRIBUTION SYSTEM - I by R. N. Kumar GM, NDPL.
Static Relays Static relays are those in which the designed response is developed by electronic or magnetic means without mechanical motion. The designation.
Power System Analysis/ Power System 1 EEE 4113/ EEE 3131
EVENT LOGGER Contd..  Process of Data Down Load  Data Down Load to Station Monitoring System.
Specification of CTs: CTs are defined in terms of rated burden, accuracy class and accuracy limit. Saturated values of rated burden are: 2.5, 5, 7.5, 10,
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Unit Transformer Unit transformer are step up transformer which is connected to generating house & step up voltage from 15kV voltage to 132 voltage level.
Differential protection : (protective relaying by Blackburn)
Chapter 1 Quick review over Electronics and Electric Components Prepared By : Elec Solv.
Chapter 7 SYSTEM PROTECTION
Interconnect Protection of Dispersed Generators
THE ELECTRIC SUB STATION
Electrical Installation 2
OVER CURRENT RELAY The relay has two settings. These are the time setting and the plug setting. The time setting decides the operating time of the relay.
Grounding, bonding, and ground fault currents
Electrical Distribution Training
Section 3 Basic Electricity and Magnetism
TESTING AND COMMISIONING
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
Protection & Switchgear
Will This Work?. Electric circuit Your challenge: Given a lightbulb holder, a battery holder, a lightbulb, a switch, and connecting wires, make the.
Protection and switchgear
Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001.
November 4, 2013 Topic: Electric Circuit Objectives:
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Introduction To Protective Relays
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Announcements Read Chapters 10 and 11
ISA CIRCUIT BREAKERS TEST SETS
O. MÄKINEN FI Session 3 Block 3 Barcelona May What is an intermittent earth fault (IE/F)? Insulation Conductor Screen Insulation break-down.
Introduction to switchgears
A Training Presentation On 132 KV GSS JAIPUR Submitted in partial fulfillment For the award of the degree of BACHELOR OF TECHNOLOGY Submitted To:- Submitted.
Power Systems Lecture from ch-20
1 Industrial Systems BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection.
Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001.
Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001.
Protection of Power Systems
Protection of Power Systems
Series Circuit What is a Series Circuit? Series Circuit Series Circuit – all parts are connected in a single loop (only one path).
Equipment 1.Circuit Breaker. 3.Fuses. 4.Protecti- ve relay.2.Bus bar. TYPES OF SWITCH GEAR EQUIPMENT:-
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Power System Protective Relaying-Part Two
 Energised by two quantities(voltage and current)  Φ1 and Φ2 set by voltage and current  Eddy currents induced in the disc due to two fluxes  Interaction.
Motor Protection Dr. Hendro Rijanto.
Protection of Power Systems
AC and DC motors.
GROUND-FAULT GROUND-CHECK MONITOR
Chapter 7 System Protection
FAULT ANALYSIS - BALANCED FAULT
Protection Philosophy
ELECTRICAL POWER-II Electrical engineering sixth semester
Calculations: Transformers and Service Conductor Calculations
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
Exercise Session 11 Power systems.
Substation Equipment's
Presentation transcript:

Material used:  Tin  Lead  Zinc  Silver  Antimony  Copper  Aluminum

Where, I = current through the fuse wire ℓ= resistivity of the fuse material d = diameter of the fuse wire L = length of the fuse wire K 1 = parameter constant

CB short circuit current carrying capacity >Operating current of fuse >Max over-load current Time in sec Current in Amp

Current Time I chopping T 1 = Melting Time T 2 = Arcing Time T = Total operating time Hence, T = T 1 + T 2 T1T1 T2T2 T = T 1 + T 2 Fault current without fuse

LoadLoad Fuse Source Series trip When, Over-load current or fault current > Fuse rating Fuse will be burnt and load will be OFF

LoadLoad Fuse Shunt trip When, CT secondary current> Fuse rating Fuse will be burnt and CT secondary current will flow through trip coil and CB will trip. TC

Fuses are classified on the basis of  Continuous current carrying capacity  Overload capacity  Response characteristics  Voltage rating

Use of fuses  Motor  Air-conditioner  Laptop  Cell-phone  Printers

LoadLoad TC Relay Battery CB  CT Secondary current exceeds relay setting current  Relay NO contact will make according to relay characteristics.  Trip coil will get energized  Circuit breaker will trip.

 O/C relay is more accurate and versatile than Fuse protection  O/C relay is more costly and more complicated than fuse.  Time gradation is difficult in case of fuse protection  Once fuse melts protection cannot be re-commissioned until it is replaced.  Unlike relay, fuse characteristics is temperature dependent.

B R N 1. Two-overcurrent & one earth fault relay

2. Three-overcurrent & one-earth fault relay B Y R N

 Overcurrent relay current setting = 125% of nominal load current  Under 3-ph balanced load condition, Earth Fault relay will sense zero current. Thus this relay has to be very sensitive. Earth fault current setting = 20% of rated current

B R N 1. Two-overcurrent & one earth fault relay 2. Three-overcurrent & one-earth fault relay B Y R N E/F relay will operate in both the cases

B Y R N 1. Two-overcurrent & one earth fault relay 2. Three-overcurrent & one-earth fault relay B R N Only R-ph O/C relay will operate Both R & Y-ph O/C relay will operate

Relay only operates when PSM > 1 Let t = operating time from relay characteristics Hence, Relay operating time = t x TMS Where TMS = time multiplier setting

Now-a-days numerical relay has inbuilt three overcurrent and one earth fault element. B Y R N Numerical relay

Protection healthy I input Calculate I rms Compute PSM =I input / I rms If PSM>1 Start timer T 1 If Type = DT DT delay t op If Type = SI Compute t op If Type = VI Compute t op If Type = EI Compute t op If T op >T 1 Alarm Trip yes no

 Less wear and tear  Self supervision facility is available  Setting range is comparatively wide  Choice of operating characteristics is possible  Relay resetting time is adjustable

 Waveform record and post-fault analysis  Remote communication and time synchronization  Over-voltage and under-voltage protection  Over-frequency and under-frequency protection  Trip circuit supervision  CT supervision  VT supervision

Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 Assume out-going feeders are radial. For electromechanical relay let T1 = Operating time of the incomer relay T2 = Resetting time of the incomer relay t1 = Operating time of the feeder relay t2 = Resetting time of the feeder relay And T1 > t1 For numerical relay T2, t2 = 0 51

Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = 0 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 At t = t1 For Electro-mechanical relay

Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = t1 + Δt 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 If T1 < (2.t1-Δt) For Electro-mechanical relay

Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = 0 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 At t = t1 For Numerical relay

Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = t1 + Δt 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 At t = 2.t1 + Δt For Numerical relay

For Electro-mechanical relay time Angular displacement of disc T1 T2 t1 t2 Incomer Feeder-1 Feeder-2 ΔtΔt (T1+ 2Δt) (2t1+ Δt) time Angular displacement of disc T1 t1 ΔtΔt T1

132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 Z p.u. =0.2 75MVA Tr.-1 Z p.u. =0.2 20MVA Tr.-1 Z p.u. =0.6 Out-going feeder B/S I 11,T 11 I 12,T 12 I 13,T 13 I 21,T 21 I 22,T 22 I 23,T 23 I 21,T 21 I 23,T 23 I 31,T 31 I 32,T 32 I 33,T 33 Current setting= I **, TMS=T ** Let base MVA=100

Considering CB short circuit current rating, T 11 > T 12 > T 13 T 21 > T 22 > T 23 T 31 > T 32 > T 33

132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-1: Fault at 132kV bushing of 75MVA Tr. (T-op) 132kv incomer > (T-op) 132kV B/S > (T-op) 132 kV of 75MVA Tr,

132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-2: Fault at 33kV Bus bar (T-op) 132kv incomer > (T-op) 132kV B/S > (T-op) 132 kV of 75MVA Tr, And (T-op) 33kv of 75MVA Tr. > (T-op) 33kV B/S

132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-3: Fault at 33kV bushing of 20MVA Tr. (T-op) 33kV of 75MVA Tr. > (T-op) 33kV B/S > (T-op) 33kV of 20MVA Tr.

132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-4: Fault at 6kV Bus bar (T-op) 33kV of 75MVA Tr. > (T-op) 33kV B/S > (T-op) 33kV of 20MVA Tr And (T-op) 6kv of 20MVA Tr. > (T-op) 6kV B/S

132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-5: Fault at 6kV outgoing feeder (T-op) 6kV of 20MVA Tr. > (T-op) 6kV B/S > (T-op) 6kV outgoing feeder

Normal direction(forward) of power flow = Non-directional O/C Relay 67= Directional O/C Relay Trip This relay operates only when fault occurs in a particular direction. For example, 1. Parallel interconnector: Sink end CB of the faulty interconnector will trip through Directional relay operation since it is sensing reverse current.

Normal direction(forward) of power flow = Non-directional O/C Relay 67= Directional O/C Relay Trip 2. Parallel Transformer feeder : LV side CB of the faulty transformer feeder will trip through directional overcurrent relay operation.

Normal direction(forward) of 30MW power flow Lock-out relay 3. Islanding scheme: By the directional relay operation  synchronization get lost  Lock-out relay operates  Two systems get isolated with part of the load is shed. Load 100MW 30MW 50MW 80MW 51 Trip 67 Trip System-1 System-2

It requires both voltage and current inputs. Under normal operating condition residual voltage and current will be zero. V a + V b + V c = 0 I a + I b + I c = 0 B Y R N Directional O/C & E/F Relay

During any fault a voltage phasor is taken as reference. The position of the fault current phasor w.r.t. the voltage phasor determines the direction of fault – Forward or reverse. V ref α Max. ‘+’ torque line Max. ‘-’ torque line Forward zone Reverse zone IfIf α = Max. Torque angle along which relay is max. sensitive

In general V ref is cross polarized. For example, Type of faultVoltage reference Neutral currentV0V0 R-Phase faultV YB Y-Phase to B-Phase faultV RN 3-Phase short circuit faultMemorized voltage (Numerical relay) Switch ON to 3-Phase Short circuit faultNon-directional behavior

Quadrature Connection: In case of numerical relay V ref is rotated through an angle (δ) w.r.t. which ±90 ⁰ is the forward direction. Type of faultsValue of the angle δ Phase – Phase fault -90 ⁰ Phase – Earth fault +90 ⁰

Phase-Phase fault: Let phase ‘Y’ gets shorted with phase ‘B’. Then phase reference will be V RN. For line side CT neutral (say) forward direction of operation is shown. Directional O/C & E/F Relay V RN δ = -90 ⁰ Forward zone I f =I Y = -I B IfIf V YN V BN -V BN V YB V Ref Reverse zone

Phase-Earth fault: Let phase ‘R’ gets shorted with earth. Then phase reference will be V YB. For bus side CT neutral forward direction of operation is shown. Directional O/C & E/F Relay V RN δ = +90 ⁰ Forward zone I f =I R IfIf V YN V BN -V BN V YB V Ref Reverse zone