Material used: Tin Lead Zinc Silver Antimony Copper Aluminum
Where, I = current through the fuse wire ℓ= resistivity of the fuse material d = diameter of the fuse wire L = length of the fuse wire K 1 = parameter constant
CB short circuit current carrying capacity >Operating current of fuse >Max over-load current Time in sec Current in Amp
Current Time I chopping T 1 = Melting Time T 2 = Arcing Time T = Total operating time Hence, T = T 1 + T 2 T1T1 T2T2 T = T 1 + T 2 Fault current without fuse
LoadLoad Fuse Source Series trip When, Over-load current or fault current > Fuse rating Fuse will be burnt and load will be OFF
LoadLoad Fuse Shunt trip When, CT secondary current> Fuse rating Fuse will be burnt and CT secondary current will flow through trip coil and CB will trip. TC
Fuses are classified on the basis of Continuous current carrying capacity Overload capacity Response characteristics Voltage rating
Use of fuses Motor Air-conditioner Laptop Cell-phone Printers
LoadLoad TC Relay Battery CB CT Secondary current exceeds relay setting current Relay NO contact will make according to relay characteristics. Trip coil will get energized Circuit breaker will trip.
O/C relay is more accurate and versatile than Fuse protection O/C relay is more costly and more complicated than fuse. Time gradation is difficult in case of fuse protection Once fuse melts protection cannot be re-commissioned until it is replaced. Unlike relay, fuse characteristics is temperature dependent.
B R N 1. Two-overcurrent & one earth fault relay
2. Three-overcurrent & one-earth fault relay B Y R N
Overcurrent relay current setting = 125% of nominal load current Under 3-ph balanced load condition, Earth Fault relay will sense zero current. Thus this relay has to be very sensitive. Earth fault current setting = 20% of rated current
B R N 1. Two-overcurrent & one earth fault relay 2. Three-overcurrent & one-earth fault relay B Y R N E/F relay will operate in both the cases
B Y R N 1. Two-overcurrent & one earth fault relay 2. Three-overcurrent & one-earth fault relay B R N Only R-ph O/C relay will operate Both R & Y-ph O/C relay will operate
Relay only operates when PSM > 1 Let t = operating time from relay characteristics Hence, Relay operating time = t x TMS Where TMS = time multiplier setting
Now-a-days numerical relay has inbuilt three overcurrent and one earth fault element. B Y R N Numerical relay
Protection healthy I input Calculate I rms Compute PSM =I input / I rms If PSM>1 Start timer T 1 If Type = DT DT delay t op If Type = SI Compute t op If Type = VI Compute t op If Type = EI Compute t op If T op >T 1 Alarm Trip yes no
Less wear and tear Self supervision facility is available Setting range is comparatively wide Choice of operating characteristics is possible Relay resetting time is adjustable
Waveform record and post-fault analysis Remote communication and time synchronization Over-voltage and under-voltage protection Over-frequency and under-frequency protection Trip circuit supervision CT supervision VT supervision
Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 Assume out-going feeders are radial. For electromechanical relay let T1 = Operating time of the incomer relay T2 = Resetting time of the incomer relay t1 = Operating time of the feeder relay t2 = Resetting time of the feeder relay And T1 > t1 For numerical relay T2, t2 = 0 51
Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = 0 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 At t = t1 For Electro-mechanical relay
Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = t1 + Δt 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 If T1 < (2.t1-Δt) For Electro-mechanical relay
Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = 0 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 At t = t1 For Numerical relay
Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 At t = t1 + Δt 51 Incomer Out-going Feeder-1 Out-going Feeder-2 Out-going Feeder-3 51 At t = 2.t1 + Δt For Numerical relay
For Electro-mechanical relay time Angular displacement of disc T1 T2 t1 t2 Incomer Feeder-1 Feeder-2 ΔtΔt (T1+ 2Δt) (2t1+ Δt) time Angular displacement of disc T1 t1 ΔtΔt T1
132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 Z p.u. =0.2 75MVA Tr.-1 Z p.u. =0.2 20MVA Tr.-1 Z p.u. =0.6 Out-going feeder B/S I 11,T 11 I 12,T 12 I 13,T 13 I 21,T 21 I 22,T 22 I 23,T 23 I 21,T 21 I 23,T 23 I 31,T 31 I 32,T 32 I 33,T 33 Current setting= I **, TMS=T ** Let base MVA=100
Considering CB short circuit current rating, T 11 > T 12 > T 13 T 21 > T 22 > T 23 T 31 > T 32 > T 33
132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-1: Fault at 132kV bushing of 75MVA Tr. (T-op) 132kv incomer > (T-op) 132kV B/S > (T-op) 132 kV of 75MVA Tr,
132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-2: Fault at 33kV Bus bar (T-op) 132kv incomer > (T-op) 132kV B/S > (T-op) 132 kV of 75MVA Tr, And (T-op) 33kv of 75MVA Tr. > (T-op) 33kV B/S
132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-3: Fault at 33kV bushing of 20MVA Tr. (T-op) 33kV of 75MVA Tr. > (T-op) 33kV B/S > (T-op) 33kV of 20MVA Tr.
132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-4: Fault at 6kV Bus bar (T-op) 33kV of 75MVA Tr. > (T-op) 33kV B/S > (T-op) 33kV of 20MVA Tr And (T-op) 6kv of 20MVA Tr. > (T-op) 6kV B/S
132kV Incomer-1 132kV Incomer-2 132kV Bus bar 33kV Bus bar 6kV Bus bar 75MVA Tr.-2 75MVA Tr.-1 20MVA Tr.-1 Out-going feeder B/S Case-5: Fault at 6kV outgoing feeder (T-op) 6kV of 20MVA Tr. > (T-op) 6kV B/S > (T-op) 6kV outgoing feeder
Normal direction(forward) of power flow = Non-directional O/C Relay 67= Directional O/C Relay Trip This relay operates only when fault occurs in a particular direction. For example, 1. Parallel interconnector: Sink end CB of the faulty interconnector will trip through Directional relay operation since it is sensing reverse current.
Normal direction(forward) of power flow = Non-directional O/C Relay 67= Directional O/C Relay Trip 2. Parallel Transformer feeder : LV side CB of the faulty transformer feeder will trip through directional overcurrent relay operation.
Normal direction(forward) of 30MW power flow Lock-out relay 3. Islanding scheme: By the directional relay operation synchronization get lost Lock-out relay operates Two systems get isolated with part of the load is shed. Load 100MW 30MW 50MW 80MW 51 Trip 67 Trip System-1 System-2
It requires both voltage and current inputs. Under normal operating condition residual voltage and current will be zero. V a + V b + V c = 0 I a + I b + I c = 0 B Y R N Directional O/C & E/F Relay
During any fault a voltage phasor is taken as reference. The position of the fault current phasor w.r.t. the voltage phasor determines the direction of fault – Forward or reverse. V ref α Max. ‘+’ torque line Max. ‘-’ torque line Forward zone Reverse zone IfIf α = Max. Torque angle along which relay is max. sensitive
In general V ref is cross polarized. For example, Type of faultVoltage reference Neutral currentV0V0 R-Phase faultV YB Y-Phase to B-Phase faultV RN 3-Phase short circuit faultMemorized voltage (Numerical relay) Switch ON to 3-Phase Short circuit faultNon-directional behavior
Quadrature Connection: In case of numerical relay V ref is rotated through an angle (δ) w.r.t. which ±90 ⁰ is the forward direction. Type of faultsValue of the angle δ Phase – Phase fault -90 ⁰ Phase – Earth fault +90 ⁰
Phase-Phase fault: Let phase ‘Y’ gets shorted with phase ‘B’. Then phase reference will be V RN. For line side CT neutral (say) forward direction of operation is shown. Directional O/C & E/F Relay V RN δ = -90 ⁰ Forward zone I f =I Y = -I B IfIf V YN V BN -V BN V YB V Ref Reverse zone
Phase-Earth fault: Let phase ‘R’ gets shorted with earth. Then phase reference will be V YB. For bus side CT neutral forward direction of operation is shown. Directional O/C & E/F Relay V RN δ = +90 ⁰ Forward zone I f =I R IfIf V YN V BN -V BN V YB V Ref Reverse zone