DAQ Calibration for Heat Exchanger Calibration of Cold/Hot Flow Rate and Temperature UTC ENCH/ENEV /25/03 Greg Kirton Kevin Zitzow Phuong Mai
Objectives Calibrate Cold Water Flow Rates from DAQ with Measured Flow Rates Calibrate Hot Water Flow Rates from DAQ with Measured Flow Rates Calibrate Temperatures from DAQ with Measured Temperatures
Heat Exchanger in UTC Lab
FT=Flow Transmitter S=Solenoid TT= Temp Transmitter CW=Cold Water W/H=Water Heater CWS=Cold Water Supply CWR=Cold Water Return Schematic of Heat Exchanger
Procedure for Measurements A stopwatch was used to keep time A 1000 ml graduated cylinder was used to measure volume Measured volume of water obtained in 10 seconds. Varied % Opening of Cooling Water Valve % Hot Water Pump Speed 4 measurements were made for each setting
Data Analysis Measurements were averaged and error was calculated using student’s T equation. Computer DAQ was averaged and standard deviation was calculated in Excel DAQ error was reported as 2xSTDEV
Cold Water Flow Calibration
Cold Water Flow Data
Hot Water Flow Calibration
Hot Water Flow Data
Temperature Calibration
Insulation
Tube Side Port B Tube Side Port A Shell Side Port B Shell Side Port A
Temperature Data
Overall Heat Transfer Coefficient of Heat Exchanger
Objectives Compare total heat transfer rates of the hot and cold streams. Determine the overall heat transfer coefficient.
Pictures of the Heat Exchanger Hot water in Cold water in Tube bundle
Heat Transfer Properties 55 tubes Tube Volume = 143 cc Tube Length = 506 mm Total heat transfer area = 0.27 m 2
Heat Transfer Diagram T hot,in T hot,out T cold,in T cold,out q
Log Mean Temperature
Heat Transfer Rate Equations
1 st Run Input = 75% Hot water mass flow rate (HWS) of kg/s CW valve open = 60 % Cold Water mass flow rate (CWS) of 0.080kg/s
q and U Results of 1 st Run q c =5.76 kW q h = 3.37 kW U c = 1352 W/m 2 K U h = 792 W/m 2 K
2 nd Run Input = 40% Hot water mass flow rate (HWS) of kg/s CW valve open = 40 % Cold water mass flow rate (HWS) of kg/s
q and U Results of 2 nd Run q c =2.33 kW q h = 2.25 kW U c = 532 W/m 2 K U h = 514 W/m 2 K
1). HWS = kg/s and CWS = kg/s 2). HWS = kg/s and CWS = kg/s 1st 2nd 1st 2nd Hot Flow Cold Flow
Hot Flow Cold Flow 1st 2nd 1st 1). HWS = kg/s and CWS = kg/s 2). HWS = kg/s and CWS = kg/s
Conclusions 1 st run: q c and q h are not closed. 2 nd run: q c and q h are closed. 1 st run: U c and U h are not closed. 1 st run: U c and U h are closed. U increases as HWS and CWS increase. 1). HWS = kg/s and CWS = kg/s 2). HWS = kg/s and CWS = kg/s