Power System Protection

Slides:



Advertisements
Similar presentations
New Energy Horizons Opportunities and Challenges Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25,
Advertisements

Co-ordination of LV Protection Devices
Fuses vs Circuit Breakers for Low Voltage Applications
Distributed Intelligence Provides Self-Healing for the Grid
MOLDED CASE CIRCUIT BREAKER BASICS
© ABB Ltd - ATLV /26/2015 Insert image here Fuses vs Fuseless Technology.
During fault behavior of circuit breaker
CIGRE 7-10 September 2009, Moscow
Electrical Power & Machines “Electrical Engineering Dept” Prepared By: Dr. Sahar Abd El Moneim Moussa 1.
Today’s Topics 1- The per unit system 2-Transformer Voltage Regulation
Overcurrent Protection: Fuses and Circuit Breakers
EE 369 POWER SYSTEM ANALYSIS
Breaker Basics Welcome to this general overview of ABB.
Specification of CTs: CTs are defined in terms of rated burden, accuracy class and accuracy limit. Saturated values of rated burden are: 2.5, 5, 7.5, 10,
EE4503 Electrical Systems Design
SECTION 4 ELECTRIC MOTORS UNIT 19 MOTOR CONTROLS.
Chapter 7 SYSTEM PROTECTION
Section 4: Electric Motors
Discrimination of protection devices on installations
Motor Start Theory ME00107A.
Standards LOW VOLTAGE Below or Equal to 1000V for AC & 1200V for DC
APPA Engineering and Operations Technical Conference Atlanta, Georgia April 13-18, 2007 “Nailing the Basics” Earns Princeton, IL RP3 Diamond Award.
Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up.
Sistemas Eléctricos Industriales
Electrical Installation 2
POWER SYSTEM PROTECTION. Power system Generators Transformers Transmission lines »Underground cables »Overhead lines Distribution systems.
Selective Coordination of Overcurrent Protective Devices
Electrical Distribution Training
TESTING AND COMMISIONING
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Lecture 18 Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
Protection & Switchgear
Announcements Read Chapters 10 and 11
A common 400 Hz AC Power Supply Distribution System for CMS FEE. Authors C. Rivetta– Fermilab. F. Arteche, F. Szoncso, - CERN.
ECE 498HZ: Power Distribution System Analysis
SARDAR VALLABHBHAI PATEL INSTITUTE OF TECHNOLOGY PREPARED BY: 1)BALDIWALA ALIABBAS ( ) 2)PARTH GUPTA ( ) 3)ANIL KHATIK ( )
Protection of Power Systems
  The traditional molded-case circuit breaker uses electromechanical (thermal magnetic) trip units that may be fixed or interchangeable.  An MCCB provides.
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Protection of Power Systems
Protection and Relay Schemes
Protection of Power Systems
HOW TO SIZE ELECTRICAL CIRCUITS
E4 Electrical Installation
Management Of Tulkarm Electrical Network
Protection of Power Systems
E4 Electrical Installation
Smitty’s Two Minute Drill Overcurrent Protection
Selective Coordination
Chapter 7 System Protection
Electrical Installation Practice 2
UNIT II APPARATUS PROTECTION.
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Power Plants By: Stephanie Mercer.
ELECTRICAL POWER-II Electrical engineering sixth semester
Calculations: Transformers and Service Conductor Calculations
Agenda Introduction of Protective Relays
EET 323 – Electrical System Design Lecture 9: Grounding
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
Substation Equipment's
Calculations Review Drill
Fuses vs Circuit Breakers for Low Voltage Applications
Presentation transcript:

Power System Protection Dr. Ibrahim El-Amin

Protective Device Coordination

Definition Overcurrent Coordination A systematic study of current responsive devices in an electrical power system.

Objective To determine the ratings and settings of fuses, breakers, relay, etc. To isolate the fault or overloads.

Criteria Economics Available Measures of Fault Operating Practices Previous Experience

Design Open only PD upstream of the fault or overload Provide satisfactory protection for overloads Interrupt SC as rapidly (instantaneously) as possible Comply with all applicable standards and codes Plot the Time Current Characteristics of different PDs

Analysis When: New electrical systems Plant electrical system expansion/retrofits Coordination failure in an existing plant

Protection vs. Coordination Coordination is not an exact science Compromise between protection and coordination Reliability Speed Performance Economics Simplicity

Protection Prevent injury to personnel Minimize damage to components Quickly isolate the affected portion of the system Minimize the magnitude of available short-circuit

Spectrum Of Currents Load Current Overcurrent Fault Current Up to 100% of full-load 115-125% (mild overload) Overcurrent Abnormal loading condition (Locked-Rotor) Fault Current Fault condition Ten times the full-load current and higher

Coordination Limit the extend and duration of service interruption Selective fault isolation Provide alternate circuits

Coordination C D B A t I A C B

Equipment Motor Transformer Generator Cable Busway

Capability / Damage Curves Gen I2t Motor Xfmr Cable

Transformer Category ANSI/IEEE C-57.109

Transformer t (sec) I (pu) Thermal Mechanical 200 2.5 I2t = 1250 2 Isc Inrush FLA 200 Thermal 2.5 t (sec) I2t = 1250 (D-D LL) 0.87 Mechanical Infrequent Fault (D-R LG) 0.58 Frequent Fault 2 Isc 25 K=(1/Z)2t I (pu)

Transformer Protection

Protective Devices Fuse Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, …) Thermal Magnetic Low Voltage Solid State Trip Electro-Mechanical MCP Overload Heater

Fuse Non Adjustable Device Continuous and Interrupting Rating Voltage Levels Characteristic Curves Min. Melting Total Clearing Application

Total Clearing Time Curve Minimum Melting Time Curve

Current Limiting Fuse (CLF) Limits the peak current of short-circuit Reduces magnetic stresses (mechanical damage) Reduces thermal energy

Let-Through Chart Peak Let-Through Amperes Symmetrical RMS Amperes 15% PF (X/R = 6.6) 230,000 100,000 300 A 100 A 12,500 Peak Let-Through Amperes 60 A 5,200 Symmetrical RMS Amperes

Fuse Generally: CLF is a better short-circuit protection Non-CLF (expulsion fuse) is a better Overload protection

Selectivity Criteria Typically: Non-CLF: 140% of full load

Molder Case CB Types Thermal-Magnetic Frame Size Magnetic Only Trip Rating Interrupting Capability Voltage Thermal-Magnetic Magnetic Only Integrally Fused Current Limiting High Interrupting Capacity

Thermal Maximum Thermal Minimum Magnetic (instantaneous)

LVPCB Voltage and Frequency Ratings Continuous Current / Frame Size Override (12 times cont. current) Interrupting Rating Short-Time Rating (30 cycle) Fairly Simple to Coordinate

480 kV CB 2 CB 1 LT PU CB 2 CB 1 LT Band If =30 kA ST PU IT ST Band

Motor Protection Motor Starting Curve Thermal Protection Locked Rotor Protection Fault Protection

Motor Overload Protection (NEC Art 430-32) Thermal O/L (Device 49) Motors with SF not less than 1.15 125% of FLA Motors with temp. rise not over 40 125% of FLA All other motors 115% of FLA

Locked Rotor Protection Thermal Locked Rotor (Device 51) Starting Time (TS < TLR) LRA LRA sym LRA asym (1.5-1.6 x LRA sym) + 10% margin

Fault Protection (NEC Art 430-52) Non-Time Delay Fuses 300% of FLA Dual Element (Time-Delay Fuses) 175% of FLA Instantaneous Trip Breaker 800% of FLA* Inverse Time Breakers 250% of FLA *MCPs can be set higher

MCP (50) (49) I2T tLR (51) ts Starting Curve LRAs LRAasym MCP 200 HP O/L (49) MCP (50) I2T (51) tLR Starting Curve ts LRAs LRAasym

Overcurrent Relay Time-Delay (51 – I>) Short-Time Instantaneous ( I>>) Instantaneous (50 – I>>>) Electromagnetic (induction Disc) Solid State (Multi Function / Multi Level) Application

Time-Overcurrent Unit Ampere Tap Calculation Ampere Pickup (P.U.) = CT Ratio x A.T. Setting Relay Current (IR) = Actual Line Current (IL) / CT Ratio Multiples of A.T. = IR/A.T. Setting = IL/(CT Ratio x A.T. Setting) IL IR CT 51

Instantaneous Unit Instantaneous Calculation Ampere Pickup (P.U.) = CT Ratio x IT Setting Relay Current (IR) = Actual Line Current (IL) / CT Ratio Multiples of IT = IR/IT Setting = IL/(CT Ratio x IT Setting) IL IR CT 50

Relay Coordination Time margins should be maintained between T/C curves Adjustment should be made for CB opening time Shorter time intervals may be used for solid state relays Upstream relay should have the same inverse T/C characteristic as the downstream relay (CO-8 to CO-8) or be less inverse (CO-8 upstream to CO-6 downstream) Extremely inverse relays coordinates very well with CLFs

Fixed Points Points or curves which do not change regardless of protective device settings: Motor starting curves Transformer damage curves & inrush points Cable damage curves SC maximum fault points Cable ampacities

Calculate Relay Setting (Tap, Inst. Tap & Time Dial) Situation 4.16 kV DS 5 MVA Cable 1-3/C 500 kcmil CU - EPR CB Isc = 30,000 A 6 % 50/51 Relay: IFC 53 CT 800:5 Calculate Relay Setting (Tap, Inst. Tap & Time Dial) For This System

Solution Transformer: IL CT R IR Set Relay:

What is ANSI Shift Curve? Question What is ANSI Shift Curve?

Answer For delta-delta connected transformers, with line-to-line faults on the secondary side, the curve must be reduced to 87% (shift to the left by a factor of 0.87) For delta-wye connection, with single line-to- ground faults on the secondary side, the curve values must be reduced to 58% (shift to the left by a factor of 0.58)

What is meant by Frequent and Infrequent for transformers? Question What is meant by Frequent and Infrequent for transformers?

Answer

What T/C Coordination interval should be maintained between relays? Question What T/C Coordination interval should be maintained between relays?

Answer B A t I CB Opening Time + Induction Disc Overtravel (0.1 sec) Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)

What is Class 10 and Class 20 Thermal OLR curves? Question What is Class 10 and Class 20 Thermal OLR curves?

Answer Class 10 for fast trip, 10 seconds or less Class 20 for, 20 seconds or less There is also a Class 30 for long trip time

Answer