WATER FOR FIRE PROTECTION (Chapter 26) Basic factors of fire – Rapid oxidation of combustible materials – A combination of oxygen, fuel, and heat is required.

Slides:



Advertisements
Similar presentations
Sprinkler Systems and Standpipe Operations
Advertisements

Determining the Occupant Load
Fire Protection Systems
Basics of Fire Sprinkler Design
Carbon Dioxide Systems 1.Carbon dioxide properties 2.Storage 3.Uses 4.Limitations 5.Types of systems 6.Local Application 7.Total Flood.
KURSUS PENGENALAN KEPADA PERKHIDMATAN MEKANIKAL DALAM BANGUNAN
Fire Protection OSHA Part 1910 Subpart L.
Unit 3 Fire Suppression Section 1 Detection and Alarm Systems.
FIREFIGHTING NOZZLES and FIRE HYDRAULICS
Fire Streams Geronimo Vol. Fire Dept.. Extinguishing Properties of Water G Water extinguishes fires by G Cooling G Remove heat from the fire G Smothering.
Hydraulic Calculations
Augmenting Fire Standpipe Systems
Fire Detection and Suppression Chapter 7 Special Extinguishing Systems.
Chapter 12 Systems and Equipment for Fire Protection.
N.F.P.A. 13R Justin Bohlmann FIR-204.
Fire Streams SFFMA Training Objectives: –
AUTOMATIC SPRINKLERS.
Fire Safety II INSY 3020/7970/7976/ENH 670 Occupational Safety & Ergonomics.
FIRE SAFETY & SUPPRESSION C ERT Unit 2. Fires at USC  Several major fires at Fraternities, some with injuries  Occasional fires in laboratories  Birnkrant.
Means of Egress and Fire Protection. 2 Objectives Understand Alarms and Warning Devices Know the location of Exits and Exit Routes Understand the RACE.
FIREFIGHTER I LESSON 15. SPRINKLER SYSTEM DESIGN AND OPERATION Series of sprinklers arranged to automatically distribute enough water to extinguish or.
3-1 NFIRS 3 Structure Fire Module. 3-2 ObjectivesObjectives The participants will be able to: –describe when the Structure Fire Module is to be used.
Smoke Control Fire-Rated Stairwells Fireproofing of Structural Components Egress Lighting Fire-Resistive Construction Elements Fire and Smoke Dampers Emergency.
Characteristics of Water
Purpose of Standpipe and Hose Systems
Chapter 9. Please read chapter 9.  Please review, know and understand the terms related to fire protection page 284.  Know the Classifications of.
Fire Protection John Giefer. Statistics In the Drilling Industry In the Drilling Industry 25% of all inspections found violations of (21 inspections.
Portable Fire Extinguishers Selection and Placement University Safety Council April 19, 2006 Steven G. Triebold Fire Prevention and Protection Program.
Automatic Sprinkler Systems
Updates to NFPA 13 What’s New in the 2013 Edition Kenneth E. Isman, P.E., F.S.F.P.E. For the European Fire Sprinkler Network’s Fire Sprinkler International.
NFPA 13: Installation of Sprinkler Systems
Module C Sprinkler systems (4-20)
Selection and Distribution of Fire Extinguishers.
 OSHA - (Occupational Safety & Health Administration) This is a governmental regulatory body to ensure safe working and learning environments for Americans.
Unit 8: Portable Fire Extinguishers & Smoke Control Management Systems
Technical Review Needed Fire Flow Analysis Developer Services Summit November 16, 2010 Engineering - Asset Planning Joe Dugandzic, PE.
Technology in Architecture Lecture 12 Electrical Equipment Electrical Power Management Fire Protection Systems Lecture 12 Electrical Equipment Electrical.
EGRESS AND FIRE PROTECTION
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Select and deploy the appropriate hose lines to accomplish fire confinement and extinguishment.
CXS490 Carbon Dioxide Systems
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Overview Select and deploy the appropriate hose lines to accomplish fire confinement.
HE UTTAR PRADESH FIRE PREVENTION AND FIRE SAFETY RULES 2005
1 CXS490 - Characteristic of Fire. 2 Other Resources NFPA Standards (available through Seneca Libraries Link NFPA Handbook Manufacturer’s Technical Information.
Mahoney, Hannig, Fire Department Hydraulics, 2nd Ed. ©2009 by Pearson Education, Inc., Upper Saddle River, NJ Fire Department Hydraulics Chapter 8 Required.
CHAPTER 12 Copyright © 2007 Thomson Delmar Learning 12.1 Protective Systems.
Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Fire Protection Systems Chapter 6. Fire Protection Systems Most of the time you will work with an electrical engineer or fire-protection designer to coordinate.
Fire Safety in the Theater By: Haley Patton Patti Ott Beaney Corral
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
Available Water Flow Meter Size Typical flow depending on size
Fire Safety Laura Escalante Miriam Barquera Ivan Morales Chad Jones.
Part C: Class D Fires and Tactical Considerations.
Chapter 6 ID 234 Building Codes Fire Suppression.
The Theory and Practice of Variable Orifice in Automatic Sprinklers VOS Fire Protection Engineering Ltd Ralph R Mehr D.Sc. PE.
ME444 ENGINEERING PIPING SYSTEM DESIGN
Fire Protection OSHA Part 1910 Subpart L By: Joshua Spurlin.
Fire Extinguishers Industrial / Home. Objectives Identify the classification of types of fire as they relate to the use of portable extinguishers Identify.
FIRE SAFETY & SUPPRESSION C ERT Unit 2. The Red Cross responded to 74,000 disasters last year and 93% were fires.
Technology in Architecture Lecture 18 Fire & Life Safety Fire Protection Systems Lecture 18 Fire & Life Safety Fire Protection Systems.
Chapter 6 ID 234 Building Codes Fire Suppression.
Sprinkler Design FSE 221 – Fire Protection Systems
Carbon Dioxide System Design
Technology in Architecture
ID 234 Building Codes Fall 2008 Fire Suppression Chapter 5.
Direction water flow Notes: Occupancy type is PUBLIC The WCs (toilets) are public flush valve.
AUTOMATIC SPRINKLERS.
NFPA13-Fire Sprinkler System
29 CFR NFPA Life Safety Code
NFIRS 3 Structure Fire Module
Bella Vista Fire Department Procedures on Sprinkled Buildings
Presentation transcript:

WATER FOR FIRE PROTECTION (Chapter 26) Basic factors of fire – Rapid oxidation of combustible materials – A combination of oxygen, fuel, and heat is required to start a fire. Classification of fire hazards Classification of occupancy hazards

WATER FOR FIRE PROTECTION (Additional information) Objectives in fire safety – Protection of life Evacuation of people the time interval between detection of fire and arrival of fire fighters. Providing adequate number of fire exits and clearly defined access (i.e. corridors, hallways, etc.) to exits. –Absolute minimum width of an exit access is 28". –In order to accommodate adults using various walking aids, corridors should be at least 36" wide. The standard unit of exit width computation is 22" (i.e. 22" = 1 exit unit). –Exit Width Units = Floor area of the building in sq. ft./(occupant density in sq. ft./person)* (Capacity per unit of exit width)

WATER FOR FIRE PROTECTION (Additional information) Minimum exit requirements: –Basement: 2 –Every building floor: 2 –Building with 50 occupants or more: 2 –Building with 500 occupants or more: 3 –Building with 1,000 occupants or more: 4 Maximum distance of a fire exit from any part of the building –100 to 200 ft. for unspriklered spaces –150 to 300 ft. for sprinklered spaces. – Protection of property – Continuity of operation

WATER FOR FIRE PROTECTION Methods for fire detection Methods of fire control – Standpipe systems – Automatic sprinkler systems Piping design – Hydraulic method: Hazen-Williamson formula – Use of piping schedule – Flow rate of sprinklers Sprinklers on a branch line Protection area per sprinkler Maximum spacing between sprinklers

DESIGN OF SPRINKLER SYSTEMS (Additional information) Residual pressure of the sprinkler system – pressure remaining in a system while water is being discharged from the outlets – sprinkler systems are usually designed for a maximum working pressure of 175 psi. Density of Water Flow (D) – required water flow from a sprinkler in gallons per square foot of area of operation Light hazard: 0.07 to 0.1 gpm/sq.ft. Ordinary hazard: 0.1 to 0.2 gpm/sq.ft. Extra hazard: 0.2 to 0.4 gpm/sq.ft. Size of sprinklers – Find required flow rate (in gpm) of a sprinkler (Density of water flow * Maximum coverage) – Find out k-factor to determine the size of the sprinklers Q = K*  p, where Q = flow rate in GPM, K = flow constant of sprinklers, p = residual pressure in psi Determine the size of the piping system – Use the method for sizing water supply pipes (either pipe sizing formula or piping schedule)

Sprinkler head sizes (Additional information) K-factorNominal orifice size in inch ¼ / / / ½ / / ¾

WATER FOR FIRE PROTECTION (Additional information) Water demand for fire suppression – Area of Sprinkler Operation (ASOP) Only a small part of the sprinkler systems need to be operated during the early stage of fire. Codes, therefore, require only a small area of the building to be calculated for simultaneous flow demand. This area, called the area of sprinkler operation (ASOP), for different hazard classifications is as follows: –Light: sq. ft. –Ordinary: sq. ft. –Extra: sq. ft.

WATER FOR FIRE PROTECTION (Additional information) – Density of Water Flow (D) required water flow from a sprinkler in gallons per square foot of area of operation –Light hazard: 0.07 to 0.1 gpm/sq.ft. –Ordinary hazard: 0.1 to 0.2 gpm/sq.ft. –Extra hazard: 0.2 to 0.4 gpm/sq.ft. – Hose Stream Demand (HSD) water demand of hoses, both inside and outside –Light hazard: 100 gpm –Ordinary hazard: 250 gpm –Extra hazard: 500 gpm – Overage Factor (OVF) Usually 1.1 – Total Water Demand in gpm = ASOP * D * OVF + HSD

Other methods of fire suppression Carbon dioxide Dry chemicals Foam systems Halogenated agents