Magnetic Design Considerations Transformers –Used to step-up or step-down voltages Inductors –Storage during energy transfer –Carries a DC current while supplying current –Need to avoid saturation of the core
Transformer Primary Voltage in Terms of Flux
Transformer Powers and Efficiency P t = apparent transformer power P i = transformer input power P o = transformer output power η = transformer efficiency
Bridge Rectifier Example
Analysis Primary voltage V 1 –V 1 = K t fN 1 Φ m (K t = 4.44 for sinusoids) Apparent Power of the transformer –P t = V 1 I 1 + V 2 I 2 For N 1 = N 2 = N and I 1 = I 2 = I –P t = VI = K t fNΦ m I –P t = K t fB m A c NI B m = peak flux density A c = cross-sectional area of the flux path
Analysis (continued) Number of Ampere-Turns –NI = K u W a J K u = fill factor (between 4 and 6) W a = window area Area Product –A p = W a A c = P t /(K t fB c K u J) Current Density –J = K j A p x
Core Configuration Constants
Area Product A p
Core Area for Various Core Types WaWa
Design of a Transformer Example 14.6 f = 60HzV 1 = 120V 60-Hz square-waveV o = 40V, I o = 6.5A Assume η = 95% and window factor K u = 0.4 Use E-core
Solution K t = 4 for a square wave Output Power –P o = V o I o = (40V)(6.5A) = 260 W Total Power –P t = P o (1/η + 1) = 260(1/ ) = W Check Table 14.1 for E-core –K j = 366x = Choose B m = 1.4
Choosing the E-core Choose a type core2-138EI –A p = cm 4 –core weight, W t = kg –core area, A c = 24.4 cm 2 –mean length of a turn, l mt = 27.7 cm
Calculate the number of primary turns
Calculate the number of secondary turns
Calculate the primary current
Calculate the primary wire size Check wire-size Table B.2 in Appendix B AWG #16 has cross-sectional area of 13.07x10 -3 cm 2
Calculate the primary copper loss
Calculate the secondary wire size Check wire-size Table B.2 in Appendix B AWG #11 has cross-sectional area of 41.68x10 -3 cm 2
Calculate the secondary copper loss
Push-Pull
Half Bridge with Center-Tap Transformer
Cores With 2 Permeability Regions