Power Engineering Society Chicago Chapter Reactive Power: Sources and Solutions 12 February 2003 David E. Mertz, PE Burns & McDonnell Engineers, Inc.

Slides:



Advertisements
Similar presentations
“Power Factor” In Transmission System
Advertisements

POWER FACTOR IN ELECTRICAL ENERGY MANAGEMENT
QUALITY AND TECHNOLOGY
Variable Frequency Drives VFD Basics
Electromagnetic Oscillations and Alternating Current
KW Energy Solutions, LLC Increasing Energy Efficiency Increasing Energy Effectiveness.
Today’s Topics 1- The per unit system 2-Transformer Voltage Regulation
Application of Power Electronics
EXCITATION SYSTEM.
Per Unit Representation Load Flow Analysis Power System Stability Power Factor Improvement Ashfaq Hussain.
Power Factor and Power Factor Correction
Lesson 27 Power Factor Correction
WISA Meeting Help Arrange a Speaker, Write Bio, Introduce
7154/7156 Variable Speed Drives
LOGO LINEAR CIRCUIT ANALYSISSAJID HUSSAIN QAZI MEHRAN U.E.T, KHAIRPUR CAMPUS A.C POWERS AND POWER FACTOR.
Disconnect Switches There are many purposes for disconnect switches in substations and power lines. They are used to isolate or deenergize equipment for.
Unit 29 Three-Phase Transformers. Objectives: Discuss the construction of three-phase transformers. Discuss the formation of a three-phase transformer.
Electricity and Magnetism Carlos Silva October 21 th 2009.
ELECTRICAL ENGINEERING: PRINCIPLES AND APPLICATIONS, Third Edition, by Allan R. Hambley, ©2005 Pearson Education, Inc. Chapter 17 AC Machines.
Voltage Voltage is the potential energy source in an electrical circuit that makes things happen. It is sometimes called Electromotive Force or EMF. Voltage.
Chapter 22 Alternating-Current Circuits and Machines.
F. Ferrandis_SP_ALPHA 2_BLOCK 2_Paper 35_Presentation Barcelona May POWER FACTOR CORRECTION WITHIN INDUSTRIAL SITES EXPERIENCES REGARDING.
Power Distribution Harmonics Case Study of 285-3F Chiller Plant Michael W. Harmon Principle Engineer Savannah River Nuclear Solutions, LLC Savannah River.
Sustainable Energy Systems Engineering Peter Gevorkian Ch 4: Energy Conservation Brevard Community College ETP1401 Bruce Hesher.
POWER FACTOR CORRECTION
Chapter 31 Electromagnetic Oscillations and Alternating Current Key contents LC oscillations, RLC circuits AC circuits (reactance, impedance, the power.
Electromagnetic Oscillations and Alternating Current
Fundamentals of Electric Circuits Chapter 11
Solid State Electricity Metrology
PQSynergy TM 2011 Harmonic Assessment of PEA North1, Chiangmai’s Customers in North Industrial Estate Chotepong Pongsriwat. M.Eng(EE) Chief of Power.
1 Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro Organized by Task Force on Harmonics Modeling & Simulation.
Chapter 7 AC Power Analysis
Power System Fundamentals EE-317 Lecture 3 06 October 2010.
TRANSISTOR TUNED AMPLIFIERS. Inroduction  Sometimes it is desired that an amplifier should amplify either a single frequency or a narrow band of frequencies.
Power System Fundamentals EE 317 Lecture 9 27 October 2010.
IEEE PES General Meeting, Tampa FL June 24-28, Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro.
Management and Organisation of Electricity Use Electrical System Optimisation Belgrade November 2003.
PFC basics EPCOS Power Quality Solutions. PFC basics FK PC PM PFC – Lukas Motta – Jan PFC Basics Ohmic loads Lighting bulbs Iron Resistive heating.
Chapter 17 Power in AC Circuits.
1 11/17/2015 Power Quality Correction. 2 11/17/2015 Power Quality Correction.
1 ECE 3336 Introduction to Circuits & Electronics Set #15 Complex Power Fall 2011, TUE&TH 4-5:30 pm Dr. Wanda Wosik.
Three Phase Motors Maths
General power system. objective Review general energy and power system Application of fundamental knowledge of principal machines, transformer and other.
REACTIVE POWER COMPENSATION
7/08/2002PP.AFD.07 Harmonic Quality1 of 49 Yaskawa Electric America Harmonic Currents, Voltages and Your Building Power System.
Understanding Harmonic Limits per IEEE
Presented by. What is Power Factor? Power Factor is the percentage of current delivered from the utility that is needed to perform the actual work. For.
Halliday/Resnick/Walker Fundamentals of Physics 8th edition
Power Quality By Using FACTS. CONTENTS INTRODUCTION WHAT IS FACTS? FOR WHAT PURPOSE FACTS ARE USED? BASIC TYPES OF FACTS CONTROLLERS BENEFITS OF UTILISING.
KAIST NUCLEAR & QUANTUM NICIEL SEMINAR 1 / 20 A Feasibility Study on Application of Synchronous Condenser for PFC to Domestic Power System of Nuclear Power.
Power Factor Correction
J.PRAKASH.  The term power quality means different things to different people.  Power quality is the interaction of electronic equipment within the.
Power Quality Issues Power Electronics Group.
KAIST NUCLEAR & QAUNTUM NICIEL SEMINAR 1 / 23 Review on Power Factor Young Seung LEE 04/26/2005 SEMINAR.
KAIST NUCLEAR & QAUNTUM NICIEL SEMINAR 1 / 26 Study for Application to Power Factor Correction Young Seung LEE 07/04/2005 SEMINAR.
Lesson 3: Ac Power in Single Phase Circuits
Power Factor Correction The Definitive power solution
Effects of Harmonics on Capacitors Electrical System
Power Capacitors.
FACTS BY SVC, FLEXIBLE AC TRANSMISSION
IG BASED WINDFARMS USING STATCOM
Yaskawa Electric America on Variable Torque Loads
Dr. Zainal salam; Power Electronics and Drives (Version 2),2002, UTMJB
Wind turbine technology
Power System Harmonics
Introduction To Reactive Power
ELECTRICAL ENGINEERING: PRINCIPLES AND APPLICATIONS, Third Edition, by Allan R. Hambley, ©2005 Pearson Education, Inc. Chapter 17 AC Machines.
FACTS BY SVC, FLEXIBLE AC TRANSMISSION
Introduction to Distribution Systems
Lecture 2 Electrical and Electronics Circuits. After you study, and apply ideas in this Lecture, you will: Understand differences among resistance, capacitance,
Presentation transcript:

Power Engineering Society Chicago Chapter Reactive Power: Sources and Solutions 12 February 2003 David E. Mertz, PE Burns & McDonnell Engineers, Inc

Reactive Power What is it? –Current that is 90 degrees out of phase with the voltage in an alternating current system. –Inherent in all alternating current systems –Caused by capacitive (leading) and inductive (lagging) loads. –The complement of “real” power.

Reactive Power Where does it come from? –All conductors are an inductor. –Multiple conductors are inductors with a mutual capacitance.

Reactive Power Where does it come from? –Placing conductors in a magnetic raceway increases their inductance.

Reactive Power Where does it come from? –Magnetic devices are the largest source of lagging (inductive) reactive power –Transformer impedance contributes reactive power, but also limits downstream short-circuit currents.

Reactive Power Where does it come from? –Magnetic devices are the largest source of lagging (inductive) reactive power –Magnetic lamp ballasts also produce lagging reactive power.

Reactive Power Where does it come from? –Magnetic devices are the largest source of lagging (inductive) reactive power –Synchronous electric machines (generators and synchronous motors) can produce either lagging or leading reactive power. –Inductive electric machines (garden-variety motors) produce only lagging reactive power.

Reactive Power What good is it? –In small amounts, it helps transmission line operators control the flow of electric power. –The transmission of high-frequency or step signals in power systems is greatly attenuated by the properties that also give us reactive power. –The same electrical phenomena are used to tune circuits for transmitting and receiving signal broadcast at selected frequencies

Why is it not desirable? –Transmitting reactive together with real power power reduces the conductor ampacity, transformer capacity, and generator capacity available for the real power. –It can lead to the overheating of electrical transmission and distribution equipment. –The same electrical phenomenon attenuates signals on wire-based systems. Reactive Power

How do we control it? –Limit the amount of lagging reactive power required from the electrical power system. –The single largest controllable source of lagging (inductive) reactive power is:

Reactive Power How do we control it? –The single largest controllable source of lagging (inductive) reactive power is: LAZY MECHANICAL ENGINEERS

Reactive Power Reduction by design: –Don’t oversize motors Real Power (Watts) Reactive Power (VAr) Total Power (VA) Large Motor, Large Load

Reactive Power Reduction by design: –Don’t oversize motors Real Power (Watts) Reactive Power (VAr) Total Power (VA) Large Motor, Small Load

Reactive Power Reduction by design: –Don’t oversize motors Real Power (Watts) Reactive Power (VAr) Total Power (VA) Small Motor, Small Load

Reactive Power Reduction by design: –Select high power factor motors These are often high efficiency motors Be aware that high power factor motors often have higher starting current requirements. Ensure that the high efficiency or high power factor motors have the right mechanical characteristics, such as starting torque, for the load.

Reactive Power Reduction by design: –Use variable frequency drives (VFDs) where applicable Power factor on line side of VFD is usually 0.95 or greater. Reactive power reduction alone won’t justify cost of the drive, but can be part of the total return on investment. VFDs have rectifier front ends, which will add harmonic currents to the system.

Reactive Power Reduction by design: –Use synchronous motors for large, constant speed and load applications Synchronous motors can be run as a source of leading as well as lagging power factor A large, constant load is necessary to be able to recover the added cost of the synchronous motor and its field controller. Typically applied at higher voltages (4160, ).

Reactive Power Reduction by design: –Carefully select lighting ballasts Where possible, use electronic ballasts Otherwise, select high power factor ballasts. When using electronic ballasts, be aware of third harmonic consideration.

Reactive Power Lagging power factor countermeasures: –Reduce the demand for reactive power through the measures previously mentioned. Reducing the amount of lagging reactive power on a system has less potential for creating undesirable conditions than trying to correct it through adding sources of leading reactive power. Reducing reactive power demand will almost always reduce the real power demand also.

Reactive Power Lagging power factor countermeasures: –Add sources of leading reactive power once opportunities to reduce lagging power demand have been addressed. Once leading reactive sources have been added to a power system, tuned “LC” circuits have been created. Potentially severe and difficult-to- diagnose harmonic current flows can result if the resonant frequency or frequencies coincide with the fundament or system frequency or its harmonics.

Reactive Power Lagging power factor countermeasures: –Distribution-level Fixed Capacitors: Most economical on a dollars-per-farad basis. No control system required Least flexible in response to changing system conditions. –Load-level Fixed Capacitors Very economical, easy to install, no control system, switches automatically with the load.

Reactive Power Lagging power factor countermeasures: –Distribution-level Switched Capacitors: More expensive than fixed banks, but responds to changes in reactive power demand. Control system required, with added cost, configuration, and maintenance required. Electromechanical type is less expensive than semiconductor switched banks, but it responds more slowly to load changes, which may be a concern if avoiding utility penalties is a concern.

Reactive Power Lagging power factor countermeasures: –Active Harmonic Compensation Systems: Most expensive on a dollars-per-farad basis. Works by “injecting” compensating current into the power system. Highly responsive control system compensates on a sub-cycle basis for both harmonic and reactive power demands. Under normal configuration, reactive power takes a back seat to harmonic cancellation.

Reactive Power Benefits of reactive power control: –Better voltage stability –More efficient use of existing power system. May be able to add load without increasing system ampacities. –Less heating of electrical equipment Extends useful life of equipment. Less real power needed to generate that heat. –Potential reduction in utility charges.

Reactive Power Summary: –Reactive power is inherent in AC systems and serves some useful purposes. –Reduce demand for reactive power before adding capacitors to compensate. –Select leading reactive power sources by balancing cost with need for flexibility and responsiveness.

Reactive Power For further reading: –IEEE Std , Electric Power Distribution for Industrial Plants, Chapter 8. This is a good resource for sizing power factor correction capacitors. Questions and discussion

Reactive Power For further reading: IEEE Std , Electric Power Distribution for Industrial Plants, Chapter 8. This is a good resource for sizing power factor correction capacitors. Questions and discussion.