APPLIED THERMODYNAMICS, PSYCHROMETRY

Slides:



Advertisements
Similar presentations
Water in the Atmosphere
Advertisements

Moisture to water converter. Out Line : Abstract Introduction Heat Pump Heat Pump Components Conclusion.
Chapter 4 Mass and Energy Analysis of Control Volumes (Open Systems)
Heating and Air Conditioning I
Psychrometric Properties of Moist Air
Chapter 5 Atmospheric Moisture. The process whereby molecules break free of liquid water is known as evaporation. The opposite process is condensation,
MOLLIER DIAGRAM.
ChE 473 Process Drying. Dryer Control In order to control any process, we need a good understanding of the process itself What is the drying process?
10/28/97A F Emery1 PSYCHROMETRICS and ELEMENTARY PROCESSES (SI Units) Ashley F. Emery University of Washington.
Examples on using Psychart -- The digital psychrometric software
Psychrometrics.
Gas – Vapor Mixtures & Air – Conditioning
Building Energy Efficiency
PSYCHOMETRICS INTRODUCTION INDEXES PSYCHOMETRIC CHART INTRODUCTION:
Section 04 Thermodynamics Adiabatic Processes Lesson 10/11.
Air conditioning.
Moisture Relationships Troposphere Tropopause barrier!
Pump Affinity Laws. P. 100 of text – section 4: vary only speed of pump P. 100 of text – section 5: vary only diameter P. 106 of text – vary BOTH speed.
Psychrometry HVAC CNST 305 Environmental Systems 1 Dr. Berryman 5cIndoor Air Quality, Psychometrics; Dry and Wet Bulb; Enthalpy; Condensation; Dew Point.
Lecture Saturation The level you’ve reached by week 4 of the semester.
ISAT Module III: Building Energy Efficiency
Atmospheric Moisture: Relative Humidity and Dew Point
Department of Mechanical Engineering ME 322 – Mechanical Engineering Thermodynamics Lecture 35 Analysis of Air Conditioning Processes.
Thermal Analysis and Design of Cooling Towers
1 Dr. C. L. Jones Biosystems and Ag. Engineering Psychrometrics – Lecture 2.
Conditioning of Moist Air
BASIC MECHANICAL ENGINEERING. REFRIGERATION AND AIR CONDITIONING.
10/28/97A F Emery1 PSYCHROMETRICS and ELEMENTARY PROCESSES (English Units) Ashley F. Emery University of Washington.
+ Atmospheric Moisture Chapter 4. + Learning Targets LT #1: I can describe the movement of water through the hydrologic cycle. LT #2: I can summarize.
PSYCHRO11 PSYCHROMETRY CHART 1 & HEAT LOAD RAMLI MOHD. YUSOFF JURUTERA MEKANIKAL CKM, IPJKR MALAYSIA RAMLI MOHD. YUSOFF JURUTERA MEKANIKAL CKM, IPJKR MALAYSIA.
Ideal Gas Mixture and Psychrometric Applications
A C M V PSYCHROMETRY (A Review) Dr. Khairul Habib.
1 Refrigeration Technology wu wei-dong Chapter9. Psychrometry and Air Processes.
EARTH SCIENCE Prentice Hall EARTH SCIENCE Tarbuck Lutgens 
Chapter 14 GAS–VAPOR MIXTURES AND AIR-CONDITIONING
Introduction to Energy Management. Week/Lesson 5 Psychrometrics: The Properties of Air.
Chapter 4. Circulation of Water in the Atmosphere  A general definition of humidity is the amount of water vapor in the air.  Remember, humidity is.
Essential Question: How does WATER in the atmosphere affect weather and climate? What is the most important gas in the atmosphere for weather? What is.
Do Now: Air rises ___________ and ____________ Air rises ___________ and ____________ Air sinks ___________ and ____________ Air sinks ___________ and.
Humidity and Dew Point. Foldable Make a two flap foldable one side Relative Humidity and the other side Dew Point Should Contain What it is How it is.
HUMIDITY AND AIR CONDITIONING
Moisture  There are several methods of expressing the moisture content (water in vapor form) of a volume of air.  Vapor Pressure: The partial pressure.
Humidity Water Vapour in the Air. The more water vapour in the atmosphere A) the air becomes heavier. B) the air becomes lighter. C) the air stays the.
Design & Analysis of Psychrometric Processes Various ways of Generating A Comfort… BY P M V Subbarao Associate Professor Mechanical Engineering Department.
Chapter 13A: PSYCHROMETRIC PROPERTIES
Chapter No-5 STEAM CONDENSERS AND COOLING TOWERS Marks-16
Psychrometric Chart (or Humidity Chart)
SNS COLLEGE OF ENGINEERING Coimbatore-107 Subject: Thermal Engineering
Course Name: Psychrometry Basics Prof. A. D. Kale
Refrigeration and Air conditioning
Chapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint to accompany Thermodynamics: An Engineering Approach, 8th edition.
Introduction to Food Engineering
PSYCHOMETRICS INTRODUCTION INDEXES PSYCHOMETRIC CHART INTRODUCTION:  PSYCHOMETRICS IS THE STUDY OF MOIST AIR.  THE PSYCHOMETRIC CHART IS A GRAPHIC REPRESENTATION.
Psychrometric Processes
Chapter 13A: PSYCHROMETRIC PROPERTIES
Chapter 5 The First Law of Thermodynamics for Opened Systems
Psychrometrics – Lecture 1
Psychrometry & Air-conditioning
Mass and Energy Analysis of Control Volumes (Open Systems)
Psychrometrics – Lecture 1
STEAM CONDENSERS AND COOLING TOWERS Marks-16
Psychrometrics – Lecture 2
Refrigeration & Air-Conditioning
Psychrometric Properties of Moist Air
Psychrometric analysis Revision of principles - Central plant
Topics in Processing Dr. C. L. Jones Biosystems and Ag. Engineering.
BAE4400 Topics in Processing
BAE4400 Topics in Processing
Atmospheric Moisture: Relative Humidity and Dew Point
Psychrometrics – Lecture 1
Presentation transcript:

APPLIED THERMODYNAMICS, PSYCHROMETRY Chapter 7 PSYCHROMETRY N. SATHEESH KUMAR, DEPT OF MECH, MITE MOODABIDRI.

PSYCHROMETRY The study of the properties of air and vapour pertaining to air conditioning problems is called psychrometry. Dry air: it is the mixture of nitrogen, oxygen and small percentage of other gases. Air contains 79% nitrogen, 21% oxygen by volume and has a molecular weight of 29. Moist air: it is the mixture of dry air and water vapour. The amount of water vapour varies according to the temperature of air and reaches saturation at one point. Saturated air mixture: saturated air mixture is a mixture of dry air and water vapour in which the partial pressure of the vapour is equal to the saturation pressure of water at the temperature of the mixture.

Unsaturated air mixture: it is a mixture of dry air and super heated water vapour. The partial pressure of vapour being less than the saturation pressure of water at the temperature of the mixture. Super saturated air mixture: it is a mixture of dry air and water vapour in which the partial pressure of the water vapour is greater than the saturation pressure of water at the temperature of the mixture. Dew point temperature: when the unsaturated air is cooled at constant pressure, the mixture reaches saturation temperature corresponding to the partial pressure of water vapour. This temperature at which condensation of the vapour begins resulting in formation of liquid droplets or dew when the mixture is cooled is called dew point temperature.

Absolute humidity or specific humidity or humidity ratio: The ratio of mass of vapour to the mass of dry air is called absolute humidity. Denoted by ‘ω’.

Dalton’s law of partial pressures: the total pressure of the mixture of gases is the sum of the partial pressures exerted by each gas when it occupies the same volume of the mixture at the same temperature of the mixture. Dry bulb temperature: it is the equilibrium temperature of the mixture indicated by an ordinary thermometer denoted by Tdb. Wet bulb temperature: it is the temperature indicated by a wet bulb thermometer which has its temperature sensitive element (bulb) covered with a wick soaked in water. It is denoted by Twb.

Relative humidity: it is defined as the ratio of partial pressure of water vapour in a mixture to the saturation pressure of water at dry bulb temperature. using perfect gas relation, pv.vv = pg.vg Hence Hence relative humidity is also defined as the ratio of the mass of water vapour in a certain volume of moist air at a given temperature to the mass of water vapour in the same volume of saturated air at the same temperature.

Degree of saturation or saturation ratio: it is defined as the ratio of specific humidity of actual air (ω) to the specific humidity of saturated air (ωg) at the same temperature.

Enthalpy of moist air: Enthalpy of moist air = enthalpy of dry air + enthalpy of water vapour associated. h = hair + ω hvapour = Cp tdb + ω hvapour But, hair = Cpa tdb = 1.005 tdb Where Cpa = is the specific heat of air = 1.005 kJ/kg/K hvapour = hg + Cps (tdb – tdp) = 2500 + 1.88tdb Cps = Specific heat of water vapour = 1.88kJ/kg/K & tdp = 0 Therefore, h = 1.005 tdb + ω(2500 + 1.88tdb) kJ/kg of dry air

Carrier equation: When DBT and WBT are given, for calculating the partial pressure of water vapour in air many equations have been proposed of which Dr. Carriers equation is most widely used. Where, (pg)wb = saturation pressure at wet bulb temperature. pv = partial pressure of water vapour pg = partial pressure of saturated vapour p = total pressure of moist air tdb = dry bulb temperature, 0C twb = wet bulb temperature, 0C

Psychrometric chart: As the calculations of various properties of moist air are tedious and time consuming, all the essential data for complete thermodynamic and psychrometric analysis of air conditioning processes can be summarized and can be presented in the form of a chart. Such a chart which makes it possible to obtain the necessary information readily for engineering calculations related to moist air known as a psychrometric chart. A psychrometric chart is constructed for a given mixture pressure, using dry bulb temperature and the specific humidity as co-ordinates.

At a given mixture pressure, the vapour pressure pv is a function of specific humidity only and hence there is only one value of pv for each value of ω.

Saturation curve: the saturation line represents the states of saturated air at different temperatures. Wet bulb and dew point temperatures fall on this curve. Relative humidity on the curve is 100%. Relative humidity lines: these are the curves with humidity ranging from maximum 100% to minimum 0%. Constant specific volume lines: these are inclined lines and are equally spaced. The WBT lines are much flatter than constant enthalpy lines. DBT lines: these are vertical lines and are equally spaced. DBT increases as we move from left to right. Specific humidity lines: these are horizontal lines and value of ω increases from bottom towards top of chart.

Sensible heating: Heating of air without addition or subtraction of moisture is called sensible heating. This can be achieved by passing the air over a heating coil. The heat added increases the DBT of air. This is useful in winter air conditioning. The heat added is given by, Qs = ma (h2 – h1)

Sensible cooling: Cooling of air without addition or subtraction of moisture is called sensible cooling. This can be achieved by passing the air over a cooling coil. This is useful in summer air conditioning. The heat removed is given by, Qr = ma (h1 – h2)

Cooling and dehumidification: Water vapour may be removed from air by cooling it below its dew point temperature. As a result of the cooling process a portion of the vapour in the air is condensed. Dehumidification will take place along with cooling when the saturation temperature of the cooling coil is below the dew point temperature of the cooling air.

In the above process warm air t1 enters the cooling coil maintained at temperature t2. The surface temperature of the cooling coil t2 is lesser than the dew point temperature of the incoming air, t4. Under ideal conditions air leaves at t2, but due to inefficient cooling it leaves at a higher temperature t3.

The temperature t2 corresponding to point 2 on the saturation curve is known as apparatus dew point, ADP. The ratio of actual heating/cooling to the ideal heating/cooling is known as by-pass factor. In this case it is given by

Adiabatic humidification: if humidification is carried out adiabatically, the energy required for the evaporation of the added moisture must come from the entering air.

As the dry bulb temperature of air decreases during adiabatic humidification process, it is also known as evaporative cooling process or cooling with adiabatic humidification of air. When warm air is passed through a spray chamber, part of water is vaporized and carried away with air. This results in humidification of air.

Mixing process: In this process two or more streams are mixed to produce a stream with desirable state of temperature and relative humidity.

Making moisture balance ma1 ω1 + ma2 ω2 = ma3 ω3 Combining we get, Making energy balance, ma1(ha1 + ω1hv1) + ma2(ha2 + ωhv2) = ma3(ha3 + ω3hv3) Making mass balance ma1 + ma2 = ma3 Making moisture balance ma1 ω1 + ma2 ω2 = ma3 ω3 Combining we get,

Requirement of Comfort air conditioning: The following 5 factors determine the comfort feeling of the people in an air conditioned space. Supply of O2 and removal of CO2. Removal of body moisture dissipated by the occupants. To provide sufficient air movement and air distribution in the occupied space. To maintain the purity of air by removing odour and dust.

Oxygen supply: human body takes in oxygen through the system and gives out CO2. Normally each person requires nearly 0.65m3 of O2 per hour and produces 0.2m3 of CO2. The percentage of CO2 in atmosphere is about 0.6% and it is necessary to maintain this to ensure comfort for easy breathing. Thus the quantity of air supply to an air conditioned space should be regulated properly to see that percentage of CO2 should not be exceeded. 2. Heat removal: it is a well known fact that human beings dissipate good amount of heat to the atmosphere during breathing etc.

The atmosphere should be capable of absorbing the heat dissipated by persons otherwise discomfort exist. Thus sufficient circulation of air should be provided through proper ventilation system to avoid rise in temperature of air in the air conditioned space. Moisture removal: A moisture loss of up to 50% from human body is commonly observed. This should be properly taken into account while designing a air conditioning unit. The ventilation system must be capable of maintaining an RH of below 70%.

4. Air movement: In addition to providing air motion, proper air distribution is very important. Air distribution is defined as a uniform supply of air to an air conditioned system. Air movement without proper air-distribution is permissible for local cooling sensation known as draft. A velocity of about 8m/min associated with temperature differential of 10C do not result in noticeable draft. Velocities greater than this produces uncomfortable drafting conditions.

Purity of air: It is important to maintain quality of air in any air-conditioned space. Odour, dust, toxic gases and bacteria are considered for defining the purity of air. The various factors which makes air impure are: The evaporation on the surface of the body adds odour to the air. The smoke from the surroundings which has a bad effect on nose, eyes and heart. The toxic gases are objectionable as they cause irritation.

Summer air conditioning systems (for Hot and dry outdoor conditions): this system is used when outdoor conditions are hot and dry. That means atmospheric temperature is higher than the comfort temperature with less moisture content (lesser RH).

Atmospheric air at condition ‘1’ (higher DBT and lower RH) enters the air dampers and passes over the cooling coil via an air filter. Temperature of the air is reduced to condition ‘2’ in the cooling coil. Air now enters an adiabatic humidifier and is passed over water eliminators.

Air enters the conditioned space at condition ‘3’ Air enters the conditioned space at condition ‘3’. Point ‘4’ represents the condition of air after passing over the cooling coil if efficiency of the coil were 100%. Condition line 1-2-4 represents the changes in DBT of air when passes over the cooling coil and the condition line 2-3-5 represents the changes in DBT of cooled air in the adiabatic humidifier.

Summer air conditioning systems: Hot and humid outdoor conditions: this system is used when the out door condition is hot and humid, like in coastal areas. That means the atmospheric temperature is higher but at the same time contains large moisture content. This condition eliminates the need for an adiabatic humidifier as shown in fig.

Atmospheric air at condition ‘1’ enter the air filter via air dampers Atmospheric air at condition ‘1’ enter the air filter via air dampers. Filtered air is cooled when it passes over the cooling coil at condition ‘3’. Condition line 1-2-3 represents the changes in DBT of air. While passing over the cooling coil with an efficient coil the air would have been cooled to 2.

As the air temperature is still below the required comfort condition, it is now passed over a heating coil. The air coming out of the coil is at condition ‘5’ which is delivered to the space. Line 3-5-4 represents changes in DBT of air while it passes over the heating coil. Point ‘4’ represents the maximum temperature that could have been attained by using an efficient heating coil.

Winter air conditioning system: APPLIED THERMODYNAMICS, PSYCHROMETRY During winter air in the atmosphere is at lower temperature than the required conditions. Also the relative humidity may be more or lesser than the actual relative humidity required for human comfort. Fig shows an arrangement for such a system where dry conditions prevail in the atmosphere. N. SATHEESH KUMAR, DEPT OF MECH, MITE MOODABIDRI.

APPLIED THERMODYNAMICS, PSYCHROMETRY Cold air from the atmosphere is filtered in an air filter before it passes over the heating coil. Air at condition ‘1’ is heated to ‘3’ in the heating coil. However due to losses, condition of air leaving the heat coil is ‘2’. Condition line 1-2-3 represents the changes in the DBT of air while it passes over the heating coil. Hot air at ‘2’ now enters the humidifier and it is cooled to ‘4’. APPLIED THERMODYNAMICS, PSYCHROMETRY N. SATHEESH KUMAR, DEPT OF MECH, MITE MOODABIDRI.

APPLIED THERMODYNAMICS, PSYCHROMETRY Any water particles suspended in air is removed by the water eliminator. As the humidity and temperature of air have still not reached comfort conditions air is heated again up to point ‘7’ by another heating coil. Due to heat losses the final temperature of air entering the conditioned space is at point ‘6’. APPLIED THERMODYNAMICS, PSYCHROMETRY N. SATHEESH KUMAR, DEPT OF MECH, MITE MOODABIDRI.

Problem 1. Moist air at 30°C,1.01325 bar has a relative humidity of 80%. Determine without using the psychrometry chart Partial pressures of water vapour and air , Specific humidity , Specific Volume and Dew point temperature (V.T.U. July2004)   Corresponding to Pv =3.397 kPa from tables, we get dew point temperature = 28.9°C

Problem 2: Atmospheric air at 101. 325 kPa ha 30°C DBT and 15°C DPT Problem 2: Atmospheric air at 101.325 kPa ha 30°C DBT and 15°C DPT. Without using the psychometric chart, using the property values from the table, Calculate Partial pressure of air and water vapour, Specific humidity , Relative humidity,Vapour density and Enthalpy of moist air  

Problem 3: Air at 30°C DBT and 25°C WBT is heated to 40°C Problem 3: Air at 30°C DBT and 25°C WBT is heated to 40°C. if the air is 300 m3/min, find the amount of heat added/min and RH and WBT of air. Take air pressure to be 1 bar Solution: At 25°C WBT from tables page no 14 Pvs(wbt)=0.03166 bar

4) One stream of air at 5.5m3/min at 15°C and 60% RH flows into another stream of air at 35m3/min at 25°C and 70%RH, calculate for the mixture 1) Dry bulb temperature, 2) Wet bulb temperature 3) Specific Humidity and 4) Enthalpy Solution: For air at 15°C and 60%RH, V=5.5m3/min

Problem 5: An air conditioning system is designed under the following conditions Outdoor conditions: 30°C DBT, 75% RH Required indoor conditions: 22°C DBT,70% RH Amount of Free air circulated 3.33 m3/s Coil dew point temperature DPT=14° The required condition is achieved first by cooling and dehumidification and then by heating. Estimate The capacity of the cooling coil in tons of refrigeration Capacity of the heating coil in kW The amount of water vapour removed in kg/hr

Solution:

Problem 6: A summer air conditioning system for hot and humid weather (DBT=32°Cand 70% RH) Consists in passing the atmosphere air over a cooling coil where the air is cooled and dehumidified. The air leaving the cooling coil is saturated at the coil temperature. It is then sensibly heated to the required comfort condition of 24°C and 50%RH by passing it over an electric heater then delivered to the room. Sketch the flow diagram of the arrangement and represent the process undergone by the air on a skeleton psychometric chart and determine The temperature of the cooling coil The amount of moisture removed per kg of dry air in the cooling coil. The heat removed per kg of dry air in the cooling coil and The heat added per kg of dry air in the heating coil

Problem 7 It is required to design an air conditioning plant for an office room with the following conditions. Outdoor conditions: 14°CDBT, 10°CWBT Required conditions: 20°CDBT,60% RH Amount of air circulated 0.3m3/min/person Starting capacity of the office= 60 The required condition is achieved first by heating and then by adiabatic humidifying. Determine the following. Heating capacity of the coil in kW and the surface temperature required, if the by pass factor of the coil is 0.4 Capacity of the humidifier.

 Problem 8  An air conditioned system is to be designed for a hall of 200 seating capacity when the following conditions are given: Atmospheric condition = 300C DBT and 50% RH Indoor condition = 220C DBT and 60% RH Volume of air required = 0.4m3/min/person The required condition is achieved first by chemical dehumidification and after that by sensible cooling. Find the following . DBT of the air leaving the dehumidifier. The quantity of water vapour removed in the dehumidifier per hour. The capacity of cooling coil in tons of refrigeration. Surface temperature of the coil if the by pass factor of the coil is 0.25.

Solution: Locate point ‘a’, 300C DBT, 50% RH, the atmospheric condition. Locate point ‘c’, 220C DBT, 60% RH, the required indoor condition. “Since chemical dehumidification process follows constant enthalpy line” at a draw a line parallel to constant enthalpy line. At ‘c’ draw a constant  line to cut the previous line at point b. DBT of air leaving the dehumidifier Tb = 40.50C From chart Hb = Ha = 65kJ/kg, a = 0.013 kg/kg of dry air Hc = 45 kJ/kg, b = 0.009 kg/kg of dry air, Vsa = 0.875 m3/min Volume of air = 200 X 0.4 = 80 m3/min Wa = Weight of air = V/Vsa = 80/0.875 = 91.42 kg/min

Quantity of water vapour removed/hour = Wa(a-b)60 = 91. 42(0. 13-0 Quantity of water vapour removed/hour = Wa(a-b)60 = 91.42(0.13-0.009)60 = 21.94 kg/hr Capacity of cooling coil = Wa(Ha-Hb)/ (60 X 3.5) = 91.42(65-45)/(60 X 3.5) = 8.7 tons By pass factor = (Tc-Td)/( Tb-Td) = 0.25 Td = Temperature of cooling coil = 15.830C

Problem 9 An air conditioned system is to be designed for a cinema hall of 1000 seating capacity when the following conditions are given: Outdoor condition = 110C DBT and 70% RH Required indoor condition = 200C DBT and 60% RH Amount of air required = 0.3m3/min/person The required condition is achieved first by heating, then by humidifying and finally by heating. The condition of air coming out of the humidifier is 75% RH. Find the following . Heating capacity of the first heater in kW and condition of the air coming out of the first heater in kW and condition of the air

Locate point ‘a’, 300C DBT, 50% RH, the atmospheric condition Locate point ‘a’, 300C DBT, 50% RH, the atmospheric condition. Locate point ‘c’, 220C DBT, 60% RH, the required indoor condition. “Since chemical dehumidification process follows constant enthalpy line” at a draw a line parallel to constant enthalpy line. At ‘c’ draw a constant  line to cut the previous line at point b. DBT of air leaving the dehumidifier Tb = 40.50C From chart Hb = Ha = 65kJ/kg, a = 0.013 kg/kg of dry air Hc = 45 kJ/kg, b = 0.009 kg/kg of dry air Vsa = 0.875 m3/min Volume of air = 200 X 0.4 = 80 m3/min Wa = Weight of air = V/Vsa = 80/0.875 = 91.42 kg/min

Quantity of water vapour removed/hour = Wa(a-b)60 = 91. 42(0. 13-0 Quantity of water vapour removed/hour = Wa(a-b)60 = 91.42(0.13-0.009)60 = 21.94 kg/hr Capacity of cooling coil = Wa(Ha-Hb)/ (60 X 3.5) = 91.42(65-45)/(60 X 3.5) = 8.7 tons By pass factor = (Tc-Td)/( Tb-Td) = 0.25 Td = Temperature of cooling coil = 15.830C