Lecture 3 Control valves
Elements of the final control Automatic Valve actuator I/P transducer Valve body
Current Signal 4-20 ma Flapper Nozzle Back pressure Pneumatic Signal 3-15 psi
Diaphragm control valves
Globe valve
Rotary valve
Rotary valve
Globe valve Most common control valve style Can be single- or double- seated
Single-seated valves Usually are employed when Tight shut-off is required, In sizes of 1 inch or smaller where unbalance forces acting on the valve stem is unimportant. Usually have a top guided construction
Double-seated valves Usually is top and bottom guided. Practical leakage approaches 0.5% of the rated CV. Advantage lies in reduction of required actuator forces. Have upper and lower ports of different diameters---allow to withdraw smaller plug through the larger port.
Angle valve Single seated valves with special body configuration to suit specific piping or flow measurements. May be used in case where the piping layout does not allow installing a globe valve.
Three way valves A design extension of a typical double-seated valve. Can be used for diverting service and for mixing service.
Actuators for control valves: Pneumatically operated diaphragm actuators; Piston actuators; Electro-hydraulic actuators; Electro-mechanical actuators; More than 90% in use are pneumatically operated piston or diaphragm type
Safety consideration Air-to-open (AO) Failure close Air-to-close (AC) Failure open
Loss
Defined at maximum Valve opening Related to valve inherent characteristics
Over sized plug to provide Additional Cv Special seat machined Into the body
Equal percentage valves: A (X) = e k(x/xo-1) = a (X-1) Linear valves: A (X) =X= x/xo Equal percentage valves: A (X) = e k(x/xo-1) = a (X-1) Rangeability
Equal Percentage Valve
Equal Percentage Valve
Distortion after installation
Valve hysteresis
Valve positioner
What accomplishment a positioner can have? Provide precise positioning of the valve Provide adequate power on high-pressure applications Increase control valve speed of response Reverse valve action Provide split range operation
Typical positioner performance Pneumatic signal ranges: 3-9, 3-15, 9-15, 3-27, 6-30 psig Air supply pressure: 20 to 100 psig Repeatability: within 0.1% of stroke Hysteresis: within 0.3% of stroke Linearity: 0.5% of stroke
Split range control valves
Control valve sizing Given expected pressure conditions, select throttling control valve to pass the required flow rate. It is a key step In ensuring that the process can be properly Controlled. Basic sizing practices have been standardized Upon (e.g., ISA S75.01) and are implemented as PC-based program by manufactures.
Allocating pressure Drop The value of b is important to the installed valve characteristic curve The pressure drop is an economic loss to the process operation Low pressure drop result in larger valve sizes and in decrease in a range of control Rules of thumb: “20% to 50% of total dynamic pressure drop”, or, “25% or 10 psi”
Determine valve capacity to meet required flow rate--- Computing CV For liquid service:
For gas and vapor: For steam: Cf: critical flow factor Tf: degree of superheat in oF P1:upstream pressure Gf: specific gravity at 14.7psi and 60oF
There are still many other formulas in Provided by control valve manufacturers. The formulas have different forms but give similar results.
To meet working flexibility, CV, DPV and DPt are to satisfy the following:
Given either three of the following five variables ( Q ,qo, CV, DPt , DPV ), the other two can be Computed.
Rangeability of a control valve: After being installed:
There are standard procedures to size a control valves, besides computing CV. In most sizing problem, the size of pipe is Known. It is usually to solve for CV and reducers combined. Thus, a geometric factor, Fp, is required in the flow formula: The details are out of the scope of this lecture.
To select an equal percentage valve: Calculate , the value yields at least 100% of qd with the available pressure drop. Compute q as a function of valve position using the rated Cv and DPv. The valve characteristics should be reasonablly linear in the operation range of interest. If not suitably linear, adjust the rated Cv
At design flow rate, qd :