1 Position Paper on IEEE Task Force on Insulator Icing Test Methods Item # 5 Power Supply Requirements By Rudi F. Kremer Vice President.

Slides:



Advertisements
Similar presentations
The stator winding are supplied with balanced three-phase AC voltage, which produce induced voltage in the rotor windings. It is possible to arrange the.
Advertisements

Chapter 12 Transformers. Chapter 12 Transformers.
SELF INDUCTION DURING AC FLOW, MAGNETIC FIELD IS NOT CONSTANT. AN OPPOSING ACTION WITHIN THE COIL IS PRODUCED.
ENERGY CONVERSION ONE (Course 25741)
Chapter 12 Electromagnetic Induction Permission granted to reproduce for educational use only. © Goodheart-Willcox Co., Inc. Objectives  Demonstrate.
Al Penney VO1NO Inductance.
Dry type transformers Zaragoza Traction application
Today’s Topics 1- The per unit system 2-Transformer Voltage Regulation
EE 311: EE Junior Lab Experiment 5 - Single Phase Transformers J. Carroll 9/25/06.
Announcements Be reading Chapter 3
Transformers and Coupled Circuits
electronics fundamentals
Topic 1 : Magnetic Concept and Transformer
Unit Transformer Unit transformer are step up transformer which is connected to generating house & step up voltage from 15kV voltage to 132 voltage level.
NETWORK OPERATING DIVISION Operating Effectiveness Phase Shifters What is a Phase Shifter These transformers create a difference in phase angle between.
Transformers Test Friday 3/30/12. Electromagnetic Induction Induction is the process of producing (inducing) a voltage by passing a wire through a magnetic.
Unit 28 Single-Phase Transformers. Objectives: Discuss the different types of transformers. List transformer symbols and formulas. Discuss polarity markings.
4. Transformers allow generated voltage to be either increased or decreased before it is used.
Chapter 22 Alternating-Current Circuits and Machines.
CHAPTER 6: TRANSFORMER BAKISS HIYANA ABU BAKAR
LECTURE 28 AC Voltage Controllers Dr. Rostamkolai
Chapter 2 Transformers.
Transformers Mechanical and Electrical Systems SKAA 2032
Unit 27 Transformers. Objectives –After completing this chapter, the student should be able to: Describe how a transformer operates. Explain how transformers.
FOWLER CHAPTER 12 LECTURE 12 TRANSFORMERS. TRANSFORMERS CHAPTER 12 TRANSFORMERS ARE MULTIPLE WINDING INDUCTORS. WORK ON THE PRINCIPLE OF MUTUAL INDUCTANCE.
BENE 1113 PRINCIPLES OF ELECTRICAL AND ELECTRONICS
Alternating Current Circuits
Topic 12: Electromagnetic induction 12.2 Alternating current
Alternating Current Circuits
DC/AC Fundamentals: A Systems Approach
Electronics Fundamentals 8 th edition Floyd/Buchla © 2010 Pearson Education, Upper Saddle River, NJ All Rights Reserved. chapter 14 electronics.
Single Phase Transformer
Electromagnetism Topic 12.2 Alternating Current. Rotating Coils Most of our electricity comes from huge generators in power stations. Most of our electricity.
Physics 12 Mr. Jean May 4 th, The plan: Video clip of the day AC/DC power generation.
Announcements For lectures 8 to 10 please be reading Chapter 3
POWER CIRCUIT & ELECTROMAGNETICS
Announcements Please read Chapter 3; start on Chapter 6
EET 103 Transformer Chapter 5 1. A transformer is a device that changes ac electric energy at one voltage level to ac electric energy at another voltage.
Modeling of Power Transformers A Static Device. Transformers The transformer enables us to utilize different voltage levels across the system for the.
Electric Machine Introduction
EET 221 Synchronous Machines Rafiqi.
BASIC ELECTRICAL TECHNOLOGY Chapter 6: Single Phase Transformer
Chapter 2 Transformers Edit by Chi-Shan Yu Electric Machinery.
Chapter 8 Alternating Current Circuits. AC Circuit An AC circuit consists of a combination of circuit elements and an AC generator or source An AC circuit.
Induction Motors Equations, Performance, Electrical Equivalent Circuits.
Electromagnetic Induction. Motion of a magnet in a coil or loop creates (induces) voltage If coil is connected to complete circuit, current flows Relative.
General power system. objective Review general energy and power system Application of fundamental knowledge of principal machines, transformer and other.
FUNDAMENTALS OF ELECTRICAL ENGINEERING [ ENT 163 ] LECTURE #10 ELECTRICAL MACHINES HASIMAH ALI Programme of Mechatronics, School of Mechatronics Engineering,
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
BASIC ELECTRICAL TECHNOLOGY DET 211/3
ELECTRICAL MACHINE DET 204/3 JIMIRAFIZI BIN JAMIL Transformer CHAPTER 1.
POWER CIRCUIT & ELECTROMAGNETICS EET 221 Transformer.
Halliday/Resnick/Walker Fundamentals of Physics 8th edition
AC Current An AC circuit consists of a combination of circuit elements and an AC generator or source The output of an AC generator is sinusoidal and varies.
D.C. Machine & Transformer Topic: Instrument Transformer Electrical:-1 presented by: Jill Chauhan ( ) Chirag Agarawal ( )
Parul Institute Of Technology Name Of Subject:-Electrical Machines Name Of Faculty:-(1) Suresh Sahoo (2) Yogendra Tiwari E&C 3 rd Sem. Prepaid By :- Sr.No.NameEnrolment.
Chapter 13 Ideal Transformers
Chapter 13 Ideal Transformers
TRANSFORMER A transformer is a static device.
TRANSFORMERS.
CHAPTER 4 SINGLE-PHASE TRANSFORMER
Chapter 18 Transformers.
Ideal Transformers Chapter Objectives:
Electric Machine Induction Motor
Electric Machine Introduction
Electromechanical Systems
electronics fundamentals
ECE 333 Green Energy Systems
Chapter 14.
Lecture 2 Electrical and Electronics Circuits. After you study, and apply ideas in this Lecture, you will: Understand differences among resistance, capacitance,
Presentation transcript:

1 Position Paper on IEEE Task Force on Insulator Icing Test Methods Item # 5 Power Supply Requirements By Rudi F. Kremer Vice President

2 1. Abstract

3 AC single phase power supplies utilized for alternating current insulator artificial icing tests shall have a defined impedance and the ability to provide an adjustable output voltage (which may change in the stated impedance range during operation) to an unknown and variable load impedance.

4 AC single phase power supplies may comprise (a) a transformer with an adjustable output voltage (recognized as variable ratio or variable transformer) or (b) may combine a variable ratio transformer and a fixed ratio transformer to step-up the output voltage, or (c) may combine a variable ratio transformer and a cascade-connected transformer arrangement to step up the output voltage to match the test requirements.

5 The variable transformer may be designed as a two winding transformer with one primary winding and one secondary winding or as an auto-transformer with one winding electrically and magnetically coupled. The variable transformer arrangement shall be rated for heavy duty application. The Fixed Ratio Transformer (recognized as step-up transformer) may be designed as (a) a two winding transformer or (b) a group of two or more step-up transformers connected in cascade.

6 The line frequency or the frequency of the test voltage shall be in the range of Hz.

7 2. Scope

8 Exclusively, the properties of Alternating Current Single Phase Power Supplies generating a variable output voltage to a test specimen are described below. NOTE: Moving-Coil Variable Transformers and Generators (Motor Generator Sets) do not fall into this category because of different electrical properties and will not be reviewed

9 3. Objectives

10 To determine and specify the requirements and electrical properties of the power supplies utilized in AC high voltage Insulator Artificial Icing Tests. To develop methods and characteristic data which will permit the specification and verification of performance tests on power supplies employed in AC Insulator Artificial Icing Tests. An AC single phase power supply shall provide reproducible and reliable test data.

11 4. Introduction

12 An AC single phase power supply may be described as an electrical apparatus which provides an output voltage, output apparent power, with an output impedance (within a specified range) at constant frequency, to an unknown and variable load.

13 In the field of high voltage testing, a variable ratio transformer (or cascade transformer group) and a fixed ratio transformer are employed to provide the necessary output voltage to the test object. The resolution of the output parameters (voltage [V], apparent power [VA], and impedance [  ]) may be infinitely variable or quasi-stepless depending on the variable transformer type.

14 5. Electrical Properties of Variable Transformers:

15 Today, toroidal variable transformers, column type variable transformers, and Thoma variable transformers are in practical operation. Toroidal variable transformers use current collector assemblies traveling circumferentially to the winding contrary to a column-type variable transformer having current collector assemblies traveling axially to the winding. Both types have the common feature of a low turn-to-turn voltage. The turn-to-turn voltage of <.7 V is necessary to yield uninterrupted output voltage and to limit losses during current flow.

16 Column-Type Variable TransformerToroidal Variable Transformer

17 The resolution of the output parameters (voltage [V], apparent power [VA]) is quasi-stepless. In general, variable transformers feature a single layer secondary winding on the magnetic core to allow a current collector to travel axially or circumferentially. This distinctive characteristic confines the shape and dimensions of the magnetic core and winding design. However, the magnetic core and winding layout does not permit the use of preventive measures to reduce the stray field caused by the current collector during current flow. Depending on the required output voltage, the current collector has to move on the winding. During current flow a stray field will be generated depending on the position of the current collector. Consequently, the impedance of toroidal and column type variable transformers are not constant. The impedance of toroidal and column type variable transformers depends on the current collector position during current flow.

18 Furthermore, the core shape and winding design of toroidal/column type variable transformers limit the range of the output voltage. The input/output voltage ratio of both types typically does not exceed <1:15. However, to comply with heavy-duty application requirements the input/output voltage ratio of toroidal/column type variable transformers should be 1:1. The Thoma variable transformer is a type of variable transformer in which a single layer of wire is wound onto a rotating cylinder. The current collector assembly moves axially along the secondary winding.

19 Thoma type variable transformers generally are designed as two winding transformers and are oil immersed. The distinctive properties of the Thoma type variable transformers are infinitely variable resolution of the output parameters (voltage [V], apparent power [VA], constant impedance [  ]) in % traveling range of the current collector position, line separation and providing an inductive compensation. The primary winding may be designed to accept an input voltage up to 50 kVAC, 50/60 Hz. The Thoma type variable transformer features a gapped core, which reduces the harmonic content of the output voltage. In addition, the gapped core represents an inductive load which compensates 8-10% of a rated capacitive load. Thoma type variable transformers comply with the heavy duty requirements.

20 6. Electrical Properties of Step-Up Transformers:

21 A step-up transformer shall feature a primary and secondary winding. The low voltage end of the secondary winding shall be grounded. The short circuit impedance or short circuit voltage shall be <6%. To match different load impedances, the secondary winding may be designed with additional taps.

22 7. Variable Transformer and Step-Up Transformer:

23 If an AC single phase power supply comprises a variable transformer and a step-up transformer, the system short circuit impedance or system short circuit voltage shall be 15%-8% in the output voltage range of 65%-100%.

24 8. Duty Cycle and Application An AC single phase power supply shall be designed for heavy duty application. Example of heavy duty operation is: No movement of the current collector system for extended time or frequent ON and OFF under load.

25 9. System Parameters The impedance or short circuit voltage shall be indicated via a graph: Impedance/Short Circuit Voltage as function of the output voltage or traveling range. The waveshape of the output voltage should approximate a sinusoid with both half cycles alike, and it should have a ratio of peak-to- rms values equal to the square root of 2 within +5%.

Excerpt An AC power supply shall provide an output voltage separated from the input line. An AC power supply shall provide an adjustable output voltage in the range from 0-100% to a variable load within a specified range. An AC power supply shall comprise a variable transformer and a step-up transformer (or cascade transformer arrangement) to match the voltage and load impedance of the test object.

27 The step-up transformer may be designed with additional taps. The short circuit impedance or short circuit voltage shall be 15%-8% in the output voltage range of 65%-100%. The short circuit impedance or short circuit voltage shall be indicated via a graph. An AC single phase power supply shall be designed for heavy duty application.

28 Comments Regarding Power Supply Requirements 1.IEC Standard 507, Second Edition , “Artificial pollution tests on high voltage insulators to be used on AC systems” and IEEE Standard , Clause 15.3 does not determine and specify clearly and definitely the electrical properties of power supplies utilized in AC high voltage test apparatus. In addition, both standards do not provide methods and characteristic data for manufacturers and end-users to verify the quality standard of an AC high voltage power supply.

29 2. I would like to suggest for discussion the following amendment and additions to Clause #5 of 3 rd Draft of Position Paper: An AC power supply shall provide an output voltage separated from the input line. An AC power supply shall provide an adjustable output voltage in the range from 0-100% to a variable load within a specified range.

30 An AC power supply shall comprise a variable transformer and a step-up transformer (or cascade transformer arrangement) to match the voltage and load impedance of the test object. The step-up transformer may be designed with additional taps because useful tap operation range %. Utilizing the short circuit voltage and short circuit power factor to determine the electrical properties of an AC power supply. The short circuit impedance or short circuit voltage shall be indicated via a graph (would replace clause #5a).

31 The short circuit impedance or short circuit voltage shall be in a range of 15%-8% of the output voltage range of 65%-100%. Leakage current measurement capacity (would replace clause #5b). An AC single-phase power supply shall be designed for heavy-duty application. Rudi F. Kremer, Vice President