Structural.

Slides:



Advertisements
Similar presentations
Common Components of a Traditional Wood Framed Building
Advertisements

Unit 45 Metal Framing Industry and Code Regulations • Light-gauge Steel Framing Members • Fasteners • Framing Tools • Metal Framing Safety • Light-gauge.
Finishes many options Walls wood shakes, shingles, board & batten (vertical), plank lap (horizontal), T1-11 ply, vinyl, fiber cement, aluminum, stucco.&
Continuous Insulation for Code- Compliant, High-Performance Walls pima.org.
Building Enclosure Moisture Management Institute (BEMMI)
5. HEAVY TIMBER FRAME CONSTRUCTION
Wall Form Design Example (Continued)
Fire Requirements For Foam Plastic Insulation and WRBs in Exterior Walls Presented to By Jesse J. Beitel July 31, 2012.
Chapter 20 Cladding with Masonry & Concrete
Emerging Standards and their effect on Exterior Continuous Insulation in Commercial Wall Construction.
Fiberock Aqua Tough Exterior Sheathing.
Wood Frame Construction Common Components of a Traditional Wood Framed Building Gateway – Unit 7 – Green Architecture © 2012 Project Lead The Way, Inc.Green.
Competency: Draw wall sections and details. Objective: Apply concepts of wood sill and floor construction.
Fire.
Building science.
Flash and FOIL® Frame Wall Insulation. Module 1 Masonry Wall Insulation Hybrid Spray Foam and Reflective Insulation System – Fi-Foil® Company Introduces…
CONTINUOUS INSULATION PRIMER. PART 1 – Continuous Insulation Definition (ASHRAE 90.1)ASHRAE 90.1 Applications: Roof, Wall, and Foundations.
Continuous Insulation for Code-Compliant & High Performance Walls.
Balloon Frame North-American invention, 1833
Energy Performance and Moisture Control of Ceilings and Roofs 1.
Shear Walls Section 3.
Common Components of a Traditional Wood Framed Building
Attending the ICC Conference in Detroit this September or know someone who is?
BUILDING THE FRAME Walls are constructed in sections, lying down on the floor platform and then tilted up into position. Fundamentals of Building Construction,
Cladding attachment.
Engineering Analysis of NFPA 285 Tested Assemblies
Chapter 32 Drawing Framing Plans.
1 CHAPTER 7 IRC WALL COVERING. 2  701 GENERAL  702 INTERIOR COVERING  703 EXTERIOR COVERING.
INSTALLATION DETAILS. Installation Details for Code Compliance Must be installed per manufacturer’s instructions Architects can provide construction details.
AIR BARRIER REQUIREMENTS. Energy Code - Air Barrier Requirements Material air permeability ≤ cfm/ft 2 per ASTM E2178 (IECC 2012 C )IECC.
Fire Resistance Rated Truss Assemblies Educational Overview.
EXPLANATION OF FOOTNOTE H. R2ci ≠ R5ci – “Footnote h” The application of an earlier version of a footnote to the R- value table was stretched beyond its.
Atlas Polyiso Insulation Insulating Your World. Who Is Atlas? Founded in 1982 Headquarters - Atlanta, GA Producers of Quality Residential & Commercial.
PRESENTED BY: Al Cobb, Founder, Sips School CHAPTER 9 OF 10 Finish Material and Detailing SPONSORED BY:
Overdriven Nails in Structural Sheathings Overview.
APPLICATIONS OF TECHNOLOGY
Advantages of Quality Vinyl Siding. Which Siding is the right Siding? Cedar? New Age Hard Board? Fiber Cement? Metal? Cheap Vinyl?
Competency: Draw wall sections and details
Window Installation: Pan Flashing and Air-Sealing to Prevent Water Intrusion Educational Overview Change title and presenter info to suit purpose. Revised.
Common Components of a Traditional Wood Framed Building
Warm-up 9/20/16 What is the underlayment called below the shingles?
Common Components of a Traditional Wood Framed Building
OBJ: SWBAT create a CAD Rendering of a Utility shed.
APPLICATIONS OF TECHNOLOGY
Use of Resilient Channel or Hat Channel to Meet the Lateral Restraint/Bracing Requirements of the Bottom Chords of MPCWT Floor Systems Overview Revised.
Do Now #7 What are the dimensions of the footing?
Wood Frame Systems Civil Engineering and Architecture®
Long Span Truss Installation
Impact of C&C loads due to ASCE/SEI 7-16
Prepared by John R. Henry, P.E. Senior Staff Engineer
Continuous insulation primer
Warm-up 9/19/16 What template are we using?
CHAPTER 5 IRC 2009 FLOORS.
Competency: Draw wall sections and details.
Educational Overview Revised 6/13/2017
Wood Structures Topic 8 Quality Workmanship
High Performance Walls for Energy Efficiency & Disaster Resilience
Common Components of a Traditional Wood Framed Building
Overdriven Nails in Structural Sheathings
Water-Resistive Barriers: Assuring Consistent Assembly Water Penetration Resistance Educational Overview Revised August 31, 2018.
Summary and conclusion
Common Components of a Traditional Wood Framed Building
Floor Truss Ribbon Board Load Path
Utility Shed Construction
Common Components of a Traditional Wood Framed Building
5. HEAVY TIMBER FRAME CONSTRUCTION
Utility Shed Construction
Common Components of a Traditional Wood Framed Building
Above Grade ICF Walls Interim Summary - Details & Water Management Strategies Building Green With Concrete October 22, 2015 Presented by Brian Hubbs, P.
Presentation transcript:

Structural

PART 3: Building Code Compliance Structural Sheathing /Wind Pressure Cladding Attachment Window Attachment Vinyl Siding over Foam / Wind Pressure Foam sheathing with PC Stucco Foam sheathing with Wood Shakes/Shingles Wall Bracing

Structural Code Requirements are No Different for Walls with CI Integration with Wall Bracing (IRC R602.10) Must have bracing with or without CI (no difference) Integration with framing requirements -- stud sizing, connections, wind uplift load path, etc. Must meet all framing requirements with or without CI (no difference) Wind pressure resistance of exterior wall covering assemblies (IRC R703.1.2) All must provide wind pressure resistance 3

Wind Pressure Resistance (Link to code) NOTE: This 2009/2012 IRC code provision was proposed by ACC-FSC to ensure all sheathing materials and claddings used as wall coverings meet code 4

All Wall Coverings or Sheathings are Subject to Wind Damage Wood structural panels Fiber board Foam sheathing 5

Foam Sheathing Wind Pressure Requirements New in IBC & IRC 2015

Foam Sheathing Wind Pressure Requirements Foam sheathing must resist wind pressure as part of a wall covering assembly: Cladding/furring secures foam to resist negative design wind pressure Typical fasteners intended for temporary wind conditions Foam sheathing material must: Span between studs Have adequate bending strength Foam sheathing attachments can be designed for permanent wind load resistance Per IRC Section R703.1.2, foam sheathing must resist wind pressure as part of a wall covering assembly. Cladding or furring strips secure foam to resist negative. or suction, design wind pressure. Typical foam sheathing fasteners used during installation are intended for temporary wind conditions only, unless otherwise designed to resist full wind load. Foam sheathing material must Span between studs, when not used as “over-sheathing”. It also must have adequate bending strength to resist positive and negative design wind pressure. The IBC is not as specific, but does require exterior walls to be designed to resist the required loads, including wind loads. 7

Code Compliance Resources (wind pressure) ANSI/SBCA/FS 100–2012 Provides path for code compliance and building official approval Referenced in 2015 IBC and IRC Exception: Foam sheathing does not need to comply if used as oversheathing over structural sheathing For more information on wind pressure code compliance, See ANSI/SBCA/FS 100–2012, “Standard Requirements for Wind Pressure Resistance of Foam Plastic Insulating Sheathing Used in Exterior Wall Covering Assemblies,” which is available at sbcindustry.com/fs100.php and has been adopted into the 2015 IBC. 8

Vinyl Siding Over Foam Sheathing (wind pressure) IRC 2009/2012/2015: Except under low wind load conditions or the oversheathing exception above, vinyl siding wind pressure ratings are required to be adjusted when applied over foam sheathing. This may limit product choices in higher wind zones and/or require use of premium vinyl siding products, but the performance will be superior to that of typical vinyl siding installations over other sheathing types. Link to code 9

DOE/IBHS/ACC-FSC/NAHB-RC /VSI Whole Building Wind Tunnel Test 10

Results – OSB/wrap/vinyl Typical building wraps are not a very wind resistant WRB choice. Building protection can be compromised during construction or as a result of siding damage during severe wind events. 11

Results – CI/vinyl (vinyl removed) Foam sheathing and taped WRB joints survived exposure to hurricane force winds with no damage even with siding removed 12

Cladding Attachment ACC-FSC, NYSERDA, DOE and SFA funded research Adopted in NY energy code (effective Dec 2010) Referenced in IBC Section 2603.11 (masonry/concrete) and 2603.12 (steel framing) Referenced in IRC Section 703.15 (wood framing); R703.16 (steel framing); R703.17 (concrete/masonry) TER No. 1006-01 Code compliant guidance for generic applications Must be minimum 15 psi compressive strength FPIS per ASTM standards for XPS, EPS, or Polyiso Proprietary fasteners or connectors and cladding/CI systems also available Siding fastener embedment must be maintained with all thicknesses of foam Also refer to siding manufacturer’s installation requirements (a) (e) (b) (c) (d) (a) (e) (c) (d) cladding (b) furring or WSP (optional) (c) FPIS (d) wall framing (e) fastener 13

Flanged Window Attachment TER No. 1304-01 Attachments for typical window flanges placed over FPIS up to 2” thick Must be minimum 15psi compressive strength foam (XPS, EPS, or Polyiso meeting ASTM standards). See TER No. 1205-05 for details with window bucks to allow unlimited foam thickness.

Foam Sheathing and PC Stucco IBC 2510.6 & IRC R703.6.3 Exception Statement from IRC Exception: Where the water-resistive barrier that is applied over wood-based sheathing has a water resistance equal to or greater than that of 60-minute Grade D paper and is separated from the stucco by an intervening, substantially nonwater-absorbing layer or designed drainage space.

Foam Sheathing and Wood Shakes/Shingles IRC R703.5 Requires double layer lattice of furring Not based on evidence or science BC Cedar Shake & Shingle Guide Show FSC Case Study Report

Wall Bracing Many building design factors impact wall bracing decisions which impact sheathing/insulation decisions. Refer to ACC-FSC Wall Bracing Guide (http://fsc.americanchemistry.com) Code-compliant bracing methods include: Use of foam over continuous sheathing (e.g., OSB, structural fiberboard, etc.) Use of foam between and/or over intermittent braced wall panels (e.g. OSB, let-in, structural fiberboard, hardboard, etc.) All bracing methods have limitations, advantages, and disadvantages (not unique to CI applications) 17

Wall bracing – integration with FPIS Foam sheathing only with let-in bracing Foam sheathing over corner panels and thicker foam sheathing in between for uniform wall thickness (“footnote h” wall) Oversheathing = continuous insulation over continuous wood structural panel sheathing (or proprietary structural insulated panel)