What is power factor? Measurement and correction of power factor Dis-advantages of low power factor Advantages of power factor correction Outline:- Lecturer:-

Slides:



Advertisements
Similar presentations
“Power Factor” In Transmission System
Advertisements

EE 212 Passive AC Circuits Lecture Notes 2b EE 212.
Chapter 11 AC Power Analysis
Since Therefore Since.
POWER FACTOR IN ELECTRICAL ENERGY MANAGEMENT
COST EFFECTIVE SOLUTION TO REDUCING YOUR ENERGY BILL’S POWER MASTER Power Master, LLC, 2040 E. Ridge Rd, Rochester, NY, 14622,
Energy Savings Through Power Factor Correction
KW Sentry ® Energy Controller (EC) It is a Desired & a Simple Solution for… RISING ENERGY COSTS It is a Desired & a Simple Solution for… RISING ENERGY.
Per Unit Representation Load Flow Analysis Power System Stability Power Factor Improvement Ashfaq Hussain.
Power Engineering Society Chicago Chapter Reactive Power: Sources and Solutions 12 February 2003 David E. Mertz, PE Burns & McDonnell Engineers, Inc.
Storey: Electrical & Electronic Systems © Pearson Education Limited 2004 OHT 16.1 Power in AC Circuits  Introduction  Power in Resistive Components 
Power Factor and Power Factor Correction
Lesson 27 Power Factor Correction
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Lecture 27Electro Mechanical System1  The fact that power is always positive reveals that it always flows from the generator to the resistor.  This is.
Lesson 26 AC Power and Power Factor
LOGO LINEAR CIRCUIT ANALYSISSAJID HUSSAIN QAZI MEHRAN U.E.T, KHAIRPUR CAMPUS A.C POWERS AND POWER FACTOR.
Chapter 7 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Plant Utility System (TKK-2210)
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Voltage Voltage is the potential energy source in an electrical circuit that makes things happen. It is sometimes called Electromotive Force or EMF. Voltage.
Electrical Principles Chapter 2
Technical Presentation on the new Power Saving Unit (PSU) Introduced By View Power.
Utility Savings Bill McGroarty Suburban Electric Supply Co.
Chapter 11 AC Power Analysis
POWER FACTOR CORRECTION
Lecture 28Electro Mechanical System1  Consider a circuit with a source, a load, & appropriate meters.  P and Q are positive, so the load absorbs both.
Power in AC Circuits ELEC 308 Elements of Electrical Engineering
Solid State Electricity Metrology
Chapter 7 AC Power Analysis
Circuits II EE221 Unit 11 Instructor: Kevin D. Donohue Complex Power, Power Conservation, Power Factor Correction, and Applications.
Circuit Master Circuit Master™ uses three PROVEN technologies* – Capacitor (reduces DEMAND) – Harmonic Filter (harmful frequencies) – Surge Protection.
Power System Fundamentals EE-317 Lecture 3 06 October 2010.
Management and Organisation of Electricity Use Electrical System Optimisation Belgrade November 2003.
PFC basics EPCOS Power Quality Solutions. PFC basics FK PC PM PFC – Lukas Motta – Jan PFC Basics Ohmic loads Lighting bulbs Iron Resistive heating.
Power Factor Improvement Lecture 9. Normally, the power factor of the whole load on a large generating station is in the region of 0·8 to 0·9. However,
Power factor correction √. POWER FACTOR IS THE COSINE OF ANGLE BETWEEN V AND I.
Chapter 17 Power in AC Circuits.
1 11/17/2015 Power Quality Correction. 2 11/17/2015 Power Quality Correction.
1 ELECTRICAL TECHNOLOGY EET 103/4  Define and explain sine wave, frequency, amplitude, phase angle, complex number  Define, analyze and calculate impedance,
Chapter 10 Sinusoidal Steady- State Power Calculations
By. Sajid Hussain Qazi MUET SZA Bhutto Campus, Khairpur.
Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee )
Three Phase Motors Maths
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
General power system. objective Review general energy and power system Application of fundamental knowledge of principal machines, transformer and other.
REACTIVE POWER COMPENSATION
Lecture 32Electro Mechanical System1 Assignment 10 Page 396 Problems 17-9, 17-14, and Due Date: Thursday 28 th April, 2011 Quiz No.5 Next Week Quiz.
Presented by. What is Power Factor? Power Factor is the percentage of current delivered from the utility that is needed to perform the actual work. For.
FUNDAMENTAL OF ELECTRICAL POWER SYSTEMS (EE 270)
Power Factor Correction
KAIST NUCLEAR & QAUNTUM NICIEL SEMINAR 1 / 23 Review on Power Factor Young Seung LEE 04/26/2005 SEMINAR.
1 Chapter 3 AC Power Analysis. 2 AC Power Analysis Chapter 3 3.1Instantaneous and Average Power 3.2Maximum Average Power Transfer 3.3Effective or RMS.
1 March 2001 EPCOS FK PM PFC Basics of Power Factor Correction BASICS OF POWER FACTOR CORRECTION.
Lesson 3: Ac Power in Single Phase Circuits
Power Generation and Distribution
Power Factor Correction The Definitive power solution
Power in AC Circuits Introduction Power in Resistive Components
Power Factor Correction The Definitive power solution
Effects of Harmonics on Capacitors Electrical System
Lesson 22: AC Power Factor and Power Factor Correction
Automated power Factor Correction and Energy Monitoring System
POWER FACTOR CORRECTION
Chapter 11 AC Power Analysis
Introduction To Reactive Power
Power in AC Circuits Introduction Power in Resistive Components
Houston Power Services Company
Sr. Lecturer in Electrical Engg. Govt. Polytechnic,Manesar
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
The instantaneous power
Presentation transcript:

What is power factor? Measurement and correction of power factor Dis-advantages of low power factor Advantages of power factor correction Outline:- Lecturer:- Engr: Sajid Hussain Qazi Made by:- 12k-EL 17,28 Electrical Engineering Department MUCET KHAIRPUR

Basic Formulae CIRCLE

POWER FACTOR Defination:- Power factor (P.F) is the ratio between active power and apparent power Active power/Apparent power or P.F=Kw/Kva Power factor involves the relationship between two types of power: Working Power and Reactive Power Most loads in electrical distribution systems are inductive, which means that they require an electromagnetic field to operate Inductive loads require two kinds of current: Working Power – performs actual work of creating heat, light, motion, etc Reactive Power – sustains the electromagnetic field PF measures how effectively/efficiently electrical power is being used

Examples of Electric Equipment and Their Power Factor Different types of electric equipment have different Power Factors and consequently different efficiencies and current requirements: Name of Equipment Power Factor Percent Lightly loaded induction motor .20 Loaded induction motor .80 Neon-lighting equipment .30 - .70 Incandescent lamps 1 All types of resistance heating devices (e.g. toaster, space heater) 1

a b c Power Triangle Real Power or Working Power (kW) - Measured Reactive Power (kVAR) b c Real Power or Working Power (kW) - Measured Reactive Power (kVAR) - Measured Apparent Power (kVA) - Calculated Apparent Power (kVA) 2 2 2 Pythagorean Theorem: c = a + b 2 2 2 kVA = kW + kVAR

Active and reactive powers are designated by P & Q respectively. The average power in a circuit is called active power and the power that supplies stored energy to reactive elements is called reactive power. P.F For Inductive load:- Inductive loads cause the current to lag behind the voltage.The wave form of voltage and curret then are “out of phase” with each other. The more out phase they become then the lower the power factor will be.Power factor is usually expressed as cos phi(φ). Consider a canal boat is being pushd by a horse. If the horse could walk on water then angle is φ(phi) would be zero and cos(0)=1.Meaning all the horse power is being used to pull the load. However the relative position of the horse influnces the power. As the horse gets closer to barge, angle φ1 increases and power is wasted, but as the horse positioned further away, then angle φ2 gets closer to zero and less power is wasted

ACTIVE POWER (P) Also known as “real power” or simply “power”. Active power is the rate of producing, transfaring, or using elctrical energy. It is measured in watts and often expressed in kilowatts(KW) or Megawatts(MW). The term “active” or “real” power are used in place of the term “power” alone to differentiate it from “reactive power”.

Or other defination of active power can be that Active power the actual power ( Kw ) or Real power Consumed by a load .If we are not maintaining the power factor at the appreciable value that is if cos0 is decreasing then sino is increased that is VI SIN o that is reactive power. cos o = Active power / Apparent Power = Kw / KVA. Reactive power = VI SINo = Kvar. The power which is actually utilised in the circuit is known as active power. REACTIVE POWER (Q) Reactive power is nothing but which is delivered by the inductive load and does not do any usefulwork . It is measured in Kvar or simply Var. Reactive power is that component of power for which we don't pay any money, but we put our own system to a pressure. It is like somebody climbing upstairs and coming down without doing anything

APPARENT POWER (S) The product of the voltage (in volts) and the current (in amperes). It comprises both active and reactive power.. It is measured in “volt-amperes”(va) and often expressed in “kilovolt-amperes”(kva) or “Megavolt-amperes”(Mva). When current and voltage wave forms are in phase as shown below then corresponding power wave form of an electrical network would be:-

When current and voltage wave forms are out of phase as shown below then corresponding power wave form of an electrical network would be:-

Effect Of Low P.F On Inductive Load

Causes Of Low Power Factor A poor power factor can be the result of either a significant phase difference between the voltage and current at the load terminals or it can be due to a high harmonic content or distorted/discontineous current wave form. Poor load current phase angle is generally the result of an inductive load such as an induction motor , power transformere, lightening ballasts, welder or induction furnanc, Induction generators, wind mill generators and high intensity discharge lights. Dis-Advangates Of a Low Power Factor Increases heating losses in transformer and distribution equipments. Reduce plant life. Unstablise voltage levels. Increase power losses. Upgrade needs costly equipments. Decreases energy efficiency. Increases electricity cost by paying power factor surcharges.

Correction Of Power Factor Most loads on an electrical distribution system fall into one of three catogries; resistive, inductive or capactive. World wide the most common is likely to be inductive (almost 85%). Typical examples of this includes transformers, fluorescent lightening and AC induction motors. Most inductive loads use a conductive coil winding to produce an electromagnetic field, allowing the motor to function. All inductive loads require two kind o f power to operate: Active Power:- (KW)- to produce the motive force Reactive Power:- (KVAR)- to energize the magnetic field The operating power from the distribution system is composed of both active (working) and reactive (non-working) elements. The active power does useful work in driving the motor whereas the reactive power only provides the megnetic field

The amount of power capacitor KVAR required to correct a system to a desired power factor level, is the difference between the amount of KVAR in the uncorrected system and the amount of desired KVAR in the corrected system The most efficient location for power factor capacitor is at the load. Capacitors work from the point of installation back to the generating source. Individual motor correction is not always practical, sometimes it is more practical to connect larger capacitors on the distribution bus or install an automatic syatem at the incoming service along with fixed capacitors at the load

After Correction Of Power Factor

After Correction Of Power Factor

Utilization Of Power With & Without Capacitor

KVAR Correction Capactive Powet Factor Correction (PFC) is applied to electric circuits as a means of minimising the inductive componenet of the current and there by reducing the losses in the supply. The introduction of power factor correction capactiors is a widely recognised method of reducing an electrical load, thus minimising wasted energy and hence improving the efficiency of a plant and reducing the electricity bill. It is not usually necessary to reach unity, i.e. Power factor 1, since most supply companies are happy with a PF of 095 to 0.98. By installing suitably sized switched capacitors into the circuit, the the power factor is improved and the value becomes nearer to 1 thus minimising wasted energy and improving the efficiency of a plant. Power factor can be increased by synchronous motor as well.

Refrences:- 1- Internet (www.authorstream.com) Advantages Of Power Factor Correction Eliminate power factor penalities Increase system capacity Reduce line losses in distribution systems Conserve energy Improve voltage stability Increase equipment life Save on utility cost Enhance equipment operation by improving voltage Improve energy efficiency Reduction in size of transformers, cables and switchgear in new installations Delay costly upgrades Less total plant KVA for the same KW working power Improves voltage regulation due to reduced line voltage drop Refrences:- 1- Internet (www.authorstream.com) 2- Book (Electrical & Electronic Principles & Technology By John Bird) Page no: 223, 239, 240, 241