FSTS Leak Rate Qualification Procedure J. Botelho Direito EN/CV/PJ 29/11/2012 FSTS - Leak Rate Qualification Procedure
Leak Rate Qualification Process 29/11/2012 FSTS - Leak Rate Qualification Procedure
Maximum Leak Rate for the FSTS He Leak Rate [mbar.l/s] (inlet pressure of 0.1 mbar) Number of connections (or locations to be tested) Maximum leak rate per connection Condenser3.47x x10 -4 Vapour line5.62x x10 -4 Liquid line3.22x x10 -6 Brine Circuit1.53x x /11/2012 FSTS - Leak Rate Qualification Procedure
Validation Pressure Test 29/11/2012 FSTS - Leak Rate Qualification Procedure Thermosyphon Circuit – Return LineThermosyphon Circuit – Condenser
Validation Pressure Test 29/11/2012 FSTS - Leak Rate Qualification Procedure Thermosyphon Circuit – Liquid LineBrine Circuit