Residential Variable Capacity Heat Pump Field and Lab Testing: Final Results 20 November 2013 Ecotope 1.

Slides:



Advertisements
Similar presentations
Performance measurement
Advertisements

Key HVAC Design Concepts. Agenda Discuss relevance of thermal enclosure system to HVAC system. Present the three major steps to design an HVAC system.
1 Proposed Revision to Energy Star New Homes Deemed Savings September 19, 2008.
Heat Pump Research Project Sponsored by the Heat Pump Working Group June 7, 2005.
IEA HPP Annex 28 Calculation method Workshop IEA HPP Annex 28 8 th International Heat Pump Conference, Las Vegas, 30 May 2005 Carsten Wemhöner, Operating.
Ductless Heat Pumps in Residential Applications Proposed Research Plan.
Energy Saving DDC Control Strategies
Evaluation of Energy Savings for Strip Curtains Presented To RTF Scott Moore PECI Sr. Engineer June 2, 2009.
Heat Loss & Gain Calculations 1. How Heat Moves in Homes Conduction is the transfer of heat through solid objects, such as the ceilings, walls, and floors.
1 Performance of Heat Pumps in the Pacific Northwest Larry Palmiter Erin Kruse Ecotope, Inc. Presentation for RTF Meeting Portland, OR November 4, 2003.
NEEM Manufactured Homes Field Test Results David Baylon, Ecotope.
Heat Pump Water Heaters Provisional UES Proposal Regional Technical Forum October 4 th, 2011.
Prescriptive Duct Sealing UES Measure Proposal Regional Technical Forum Subcommittee July 8, 2013.
Manufactured Homes Calibration: Existing and New Homes Mohit Singh-Chhabra & Josh Rushton RTF Update May 12, 2015.
BPA Pre-Pilot, Monmouth  14 homes with installed DHP, single zone, single compressor.  11 Monmouth, 2 Moses Lake, 1 Tacoma  Savings.
1 Proposed Changes to the RTF’s Heat Pump Specifications Impact on Estimated Deemed Savings and C&R Discount Program Credits.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
SEEM Tool Overview Regional Technical Forum Member Orientation January 22, 2013.
1 Air Source Heat Pumps Potential Changes in the RTF’s Specifications & Savings Estimates and Their Impact on C&R Discount Program Credits.
Night Covers on Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30,
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee November 16, 2011 Mira Vowles, P.E., CEM.
DUCT EFFICIENCY AND HEAT PUMP PERFORMANCE Paul Francisco David Baylon Ecotope, Inc.
General Troubleshooting Tips.
EvergreenEcon.com Heat Pump Water Heater Model Validation, Market Progress Assessment, and Process Evaluation RTF HPWH Sub-Committee Meeting October 15,
Heat Pump Water Heaters: Tier 2 – Ducted Interior Installations Provisional UES Proposal Regional Technical Forum February 14 th, 2012.
Update on the SEEM Simulation Program Larry Palmiter and Ben Larson August 4, 2008 Ecotope Inc. Presented at Regional Technical Forum Portland, Oregon,
Michael Logsdon, Ben Larson, David Baylon 13 December th Avenue NE, Seattle, WA (206)
Basics Air Flow Basics -Air is invisible -Everyone assumes adequate airflow -Frequently airflow is 30%-50% low -Cooling – 400 CFM per ton -Heating.
DHP for Houses with Electric FAF Research Plan: Revisions Adam Hadley, Ben Hannas, Bob Davis, My Ton R&E Subcommittee February 25, 2015.
Ben Larson 1 November th Avenue NE, Seattle, WA (206)
July 26, 2014 Refrigeration Subcommittee Proposed Revision of Refrigeration Provisional Data Requirements.
Michael Logsdon, Ben Larson, David Baylon 13 December th Avenue NE, Seattle, WA (206)
QC Follow-up for Single Family SEEM Calibration, HVAC UES Measures, and Weatherization Measures Adam Hadley Regional Technical Forum May 12, 2015.
Slide 1 B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Variable Capacity Heat Pump RTF Sub-Committee February 22, 2012 Mira Vowles, P.E., CEM.
Air Source Heat Pump Specifications Proposed Revisions Regional Technical Forum Subcommittee July 2, 2013.
Variable Capacity Heat Pump RTF Sub-Committee
Applying SEEM Updates, Calibration, and Measure Interaction Decisions to: Single Family Weatherization and HVAC UES Measures Follow-up from August RTF.
1 NORTHWEST ENERGY EFFICIENCY ALLIANCE DHP Costs & NEBs Ecotope, Inc. August 20, 2013.
Residential Duct Insulation New Deemed Measure Proposal – A Second Look Regional Technical Forum May 4 th, 2010.
Variable Speed Heat Pumps Provisional UES Proposal Presentation to the Regional Technical Forum September 18, 2012 Presentation by Kacie Bedney, Bonneville.
Residential New SF Energy Star Homes Idaho and Montana UES Measure Updates: Energy Star Homes, DHP TCO Homes, and BOP2 Homes March 18 th, 2014.
PSE Delta Q Project Results Bruce Manclark, Delta T Bob Davis, Ecotope RTF meeting, 5 January 2009.
Multifamily Homes: Calibration Update Regional Technical Forum December 8 th, 2015.
Water is the Natural Choice Water: The Natural Choice For Efficiency – Building System efficiency not just a unit rating – Equipment Ratings EER and COP.
A Reliable but Simplified Method for Measuring the Savings from Advanced RTU Control Retrofits February 13, 2013 Presentation to: RTF Commercial Rooftop.
Heat Pump Specifications Summary of Requirements for RTF and PTCS Installations and Updates November 4, 2003.
Planning UES Measures: SF New Construction Heat Pump Upgrades (9.0 HSPF and VCHP) Heat Pump Commissioning Controls and Sizing Adam Hadley Regional Technical.
Objectives Ventilation analysis with HOP Human exposure/IAQ Ventilation and energy.
Regional Air Source Heat Pump Performance and Savings Research and Evaluation Project Proposed Scope of Work and Estimated Budget February 10, 2004.
All content in this presentation is protected – © 2008 American Power Conversion Corporation Row Cooling.
Day 3 Part 3 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
Heat Pump Program Evaluation Baseline Practice and Conditions.
Heat Pump Water Heaters: Interior, Ducted Installations Presentation to the Regional Technical Forum December 13, 2011 Ben Larson, Ecotope
Research Strategy: Residential Ductless Heat Pumps Research and Evaluation Subcommittee Christian Douglass and Josh Rushton January 8, 2016.
EMERGING TECHNOLOGIES AVAILABLE TO REDUCE COMPRESSED AIR DEMAND Double Acting Air Cylinder Double Acting Air Cylinder Air Operated Diaphragm Pumps Air.
SOLAR POWERED AIR CONDITIONER
Heat transfer Steady state conditions not for dynamic systems in buildings through walls, roofs, floors, windows, doors building structures and U-values.
Maria’s Restaurant Chapter 2 Section 9
Part 16 Technician’s Guide & Workbook for Duct Diagnostics and Repair
Chilled Beam Performance:
Heat recovery feature Competitive approach
Variable Refrigerant Volume
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Zoning Load Calculations
The key to comfort and efficiency for heating and air-conditioning
Manual D Duct Sizes Room Cooling CFM % Total CFM Heating CFM Kitchen GR Dining Bed Bed 3.
Mandatory Design Requirements
Liebert DSE High efficiency thermal management
Maria’s Restaurant Chapter 2 Section 9
Maximizing the Use of Ductless Mini-Splits in Existing Homes
Presentation transcript:

Residential Variable Capacity Heat Pump Field and Lab Testing: Final Results 20 November 2013 Ecotope 1

History Inverter-driven compressor tech making increasing inroads (ductless systems now at 20,000 plus installs in NW); BPA has incented central ducted systems via PTCS on provisional basis Advisory committee formed to guide research plan – Range of experience on committee – Interest in zoned systems, delivery temperatures – Timeline/budget limited research scope Study summary – Heating season only – ‘Detailed’ (full capacity/COP) vs non-detailed sites – Combination of field/lab info (EPRI) – ASHRAE 152 duct model exercised plus SEEM for full season estimates 2

Major Findings – Expectations/Reality VCHP performs 25-30% better than a single speed 7.9 HSPF heat pump on an annual basis (note nominal average HSPF for this product ~12). Duct losses increased ~5% over a single speed heat pump Overall system offers improved performance over single speed base cases Heat pump sizing still matters Auxiliary heat lockout control still matters 3

Field Deployment Planning/refinement occurred through late 2012 Field deployment set for late February, 2013 (six sites); central OR chosen for likelihood of remaining cold weather (about 24 potential sites) Critical points measured – 5 minute metering for electricity usage (including air handler circuit power- CFM mapping) – One-time measurements of house heat loss (including blower door test (system sizing, heating season simulation)), duct area/R-values, duct leakage, system CFM (at least 3 points so CFM could be correlated with power), heat pump control settings 4

Site Pictures 5

Site Summaries SiteidLocationOD unit size (tons) House Type Heated Floor Area (ft 2 ) OccsPTCS HP? PTCS Ducts ? Strip heat lockout temp Powell Butte, OR 3Site26942Yes not set Powell Butte, OR 2Mfd13942No Bend, OR 3Site26632YesNonot set Bend, OR 3Site25152Yes not set Redmond, OR 4Site18602No Redmond, OR 4Site26602No 35 6

Duct Leakage/Air Handler Data Site ID Both sides duct leak to out at 50 Pa* (SCFM) Supply duct leak to out at 50 Pa* (SCFM) Reference ‡ Air Handler Flow (CFM, SCFM)* Reference ‡ supply static pressure (Pa) Reference ‡ return static pressure (Pa) ***151***943, , n/a 889, , , , * Leakage and air handler flow results corrected to standard air (68°F and 1 atmosphere). The elevation of houses in the Bend area (about 3,000 ft above sea level) results in lower air density. More specifically, the density is about 88.9% of the density of standard air. The air handler flow values show both the local CFM and the standard SCFM. ‡ “Reference” airflow corresponds to the supply and return static pressure measurements shown in the table. Typically this airflow represents the highest flow that could be attained using the User Interface (thermostat); this measurement was taken to make sure the air handler was not working against an extreme external static pressure (above 200 Pa) at its highest flow. No adverse static pressure conditions were found. All of these systems were set up by the installer in COMFORT mode (so maximum flows typically average CFM/nominal ton of capacity). ***These measurements taken at 45 Pa 7

Airflow & Fan Power Site

Air Handler Curves - All Sites 9

Balance Points (for 2 sites) 10

Heat Pump Balance Points Site ID Peak total UA † (BTU/hr °F) DHL base ‡ (BTU/hr) DHL w/DE †† (Btu/hr) HP Balance Point (°F) Heat Pump Size (tons) ,63897, ,26026, , ,99669, ,45272, * All Design Heating Load (DHL) calculations based on 4° F design temperature. †Shell plus infiltration heat loss at heating design temperature ‡Design Heating Load without duct losses at the design temperature ††Design Heating Load with duct losses included 11

Detailed Field Results (834 monitored hours) 12

Capacity and COP Calculations Capacity determined by multiplying fitted airflow by coil temperature split True RMS power is measured at the panel for both indoor and outdoor units and converted to Btu/hr COP is ratio of capacity to input power at a given outdoor temperature Following 2 graphics do not include duct losses 13

Performance vs Outdoor Temp (1) (no duct effects included) 14

Performance vs Outdoor Temp (2) (no duct effects included) 15

Measured Field Performance (common five week period) Site ID Average Outdoor Temp. (F) Total Input (kWh) Total Output (kWh) COP (avg) ER heat output fraction Metered Time Span (hrs)

Compressor Response to Changing Heating Load Low compressor speed: input power < 1.25 x observed minimum input Medium compressor speed: anything in between low and high High compressor speed: input power > 0.87 x observed maximum input 17

Air Handler Response to Changing Heating Load Low fan speed: airflow < 1.25 x listed minimum airflow (comfort mode) Medium fan speed: anything in between low and high High fan speed: airflow > 0.87 x listed maximum airflow (comfort mode) 18

Operating Mode Summary Fan and compressor speeds track one another – Given a compressor speed, there is a preferred fan speed – High compressor outputs almost never pair with low and medium fan – Low compressor speeds pair with both low and medium fan Runtime Fractions: Compressor Only Operation Compressor Speed Fan Speed LowMediumHighAll Low Medium High All Compressor and Auxiliary Operation Compressor Speed Fan Speed LowMediumHighAll Low Medium High All

Rolling in the Ducts… 20

Duct System Inputs Duct leakage, normalized to fraction of air handler flow (which changes at different flows) Duct R-value Duct area Buffer space temperature (measured only for supply buffer space) ASHRAE 152 used to calculate distribution efficiency 21

Average Duct Performance and Calculated Duct Distribution Efficiency (DE) (common five week period) Site ID System Airflow (CFM) Avg Supply Buffer Zone Temp (°F)SLFRLFDE n/a

Modeling VHCPs – Annual Performance Annual performance estimated with SEEM Simulation largely unchanged from September 2012 RTF presentation – Performance curve from catalogue data found to work well enough for systems modeled – Field study found that the operating modes pair fan and compressor speed (previous default assumption in simulation – remains unchanged) 23

Modeled VCHP and Duct System Efficiency (using SEEM for entire heating season) 24

Lab (EPRI) vs Field Results Agreement on capacity and COP measurements generally good; more divergence for some cases Lab tests done in EFFICIENCY mode All sites in Oregon set up in COMFORT mode Lab showed higher COPs as expected because of EFFICIENCY vs COMFORT mode Possibility of variability for individual pieces of equipment, as well 25

Lab results Field results Lab vs Field Comparison (2 ton system) 26

Overall Findings 27 VCHP performs 25-30% better than a single speed 7.9 HSPF heat pump on an annual basis Duct losses increased ~5% over a single speed heat pump Overall system offers improved performance over single speed base cases Heat pump sizing still matters Auxiliary heat lockout control still matters

Next Possible Steps Cost analysis. Collect data on installed costs and compare to annual estimates of savings. More complete set of SEEM runs- additional comparisons to base cases (HP and/or EFAF) Possible UES process (depends on cost analysis) Further discussion of how system could be commissioned (PTCS) 28