SmartLine Startup
Initial wirings SmartLine Initial Wirings
Balance Zones with a 3.9kΩ resistance Initial wirings SmartLine Balance Zones with a 3.9kΩ resistance
If Zones aren’t balanced panel displays “Zone open” Initial wirings SmartLine Fault 01/04 Zone Open Zone 01 <Zone 01> If Zones aren’t balanced panel displays “Zone open”
Balance Dialler with a 10 kΩ resistance (between terminals 19 and 23 ) Initial wirings SmartLine Balance Dialler with a 10 kΩ resistance (between terminals 19 and 23 )
If Dialler isn’t balanced panel displays “Fault Dialler” Initial wirings SmartLine Fault 01/01 FaultDialler If Dialler isn’t balanced panel displays “Fault Dialler”
Initial wirings SmartLine Balance NAC with a 47kΩ resistance
panel displays “Open I/O Panel NAC” Initial wirings SmartLine Fault 01/01 Open I/O Panel NAC If NAC isn’t balanced panel displays “Open I/O Panel NAC”
SmartLine Detectors Wiring Balance other zones with a 3.9 kΩ resistance 3.9 kΩ End of Line resistance on the last detector
SmartLine Callpoints Wiring Balance other zones with a 3.9 kΩ resistance 3.9 kΩ End of Line resistance on the last callpoint
NAC output activates on Alarm: it can activate alarm devices SmartLine NAC Wiring NAC output activates on Alarm: it can activate alarm devices 47 kΩ End of Line resistance on the last device
NAC SmartLine Fault 01/01 Short I/O Panel NAC If panel displays “Short I/O Panel NAC” it will need connect a diode in series (if devices haven’t it) 47 kΩ End of Line resistance on the last device
SmartLine Other wirings 17-18 FAULT Terminals activated on Fault. Fault output can activate some devices
SmartLine 19-20 DIALER Terminals activated on Alarm. DIALER Output can activate an external dialler.
SmartLine 25-26 AUX R Terminals turn off 24V on Reset They can reset latching linear beam smoke detector
SmartLine 27-28-29 RELAY Terminals activated on Alarm (at default) They can activate some devices
Generic Contact Wiring SmartLine Generic Contact Wiring Alarm contact only 680Ω resistance NO Alarm Contact 3.9kΩ resistance
Alarm Contact and Fault Contact Generic contact SmartLine Alarm Contact and Fault Contact 680Ω resistance NO Alarm Contact NC Fault Contact 3.9kΩ resistance
Detection-Line Zone Wiring Gas Detector Wiring SmartLine Gas Detector Wiring Detection-Line Zone Wiring It have to program the Zone as “Gas (Relay Output) INE55/ING55 Detector 3.9kΩ resistance
SmartLine I/O 4-20mA Input Wiring Gas Detector Wiring SmartLine I/O 4-20mA Input Wiring It have to program I/O Line as “Gas 4-20mA Input” INA55-101 board 150Ω resistance INE55/ING55 Detector 3.9kΩ zone balancing resistance
Generic 4-20mA Gas Detector Wiring SmartLine Generic 4-20mA Gas Detector Wiring It have to program I/O Line as “Gas 4-20mA Input” Generic 4-20mA gas detector 4-20mA output 150Ω resistance 3.9kΩ zone balancing resistance Detector have to supply current
Expansion Boards Wiring SmartLine Expansion Boards Wiring To next expansion board
SmartLine Expansion Zones are similar to panel ones Expansion boards SmartLine Expansion Zones are similar to panel ones Balance Zones with a 3.9kΩ resistance
Espansions board SmartLine Expansion NAC output is programmable (at default output is activated on Alarm) Balance NAC with a 47kΩ resistance
SmartLine It have to configure expansion boards Control Panel IN PROGRAMMiING Ver: 2.03 01/01/12 17:45 Enable panel programming phase
SmartLine Expansion boards Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer Acquire int.bus Acquire ext.bus Current Devices Extin.module O Expansion O Ok to execute Current Devices Extin.module O Expansion 1 Ok to execute
SmartLine RS485 Bus Wiring Up to 4 Repeater 2 Power Station RS485 Bus SmartLevel Power Station SmartLetUSee/LCD-Lite Repeater
SmartLine It have to address RS485 Bus devices RS485 Bus Address DIP Switch Position SmartLevel Power Station SmartLetUSee/LCD-Lite Repeater
SmartLine It have to address RS485 Bus devices RS485 Bus Enable SmartLevel programming phase Prog View log LED Test Reset Maintenance LED test Reset Maintenance Programming Booster Options Address RS485 Default Data SmartLevel Power Station Address: 01 SmartLetUSee/LCD-Lite Repeater Address: 02
SmartLine Set End of Line jumper in EOL position on the last device RS485 Bus SmartLine Set End of Line jumper in EOL position on the last device SmartLevel Repeater SmartLevel Power Station Ripetitore SmartLetUSee/LCD-Lite
SmartLine It have to address RS485 Bus devices Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Enable panel programming phase SmartLevel Power Station SmartLetUSee/LCD-Lite Repeater
SmartLine RS485 Bus SmartLevel Power Station Centrale IN PROGRAMMAZ.!! Ver: 2.03 01/01/12 17:45 Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer Acquire int.bus Acquire ext.bus SmartLevel Power Station Current Devices Repeater O Power Station O Ok to execute SmartLetUSee/LCD-Lite Repeater Current Devices Repeater 2 Power Station 1 Ok to execute