VENTING AND COMBUSTION AIR

Slides:



Advertisements
Similar presentations
Response to CHIMNEY FIRES
Advertisements

Regulations (Standards - 29 CFR) Flammable and Combustible liquids
Fired And Unfired Pressure Vessels
HVAC523 Heat Sources.
International Mechanical Codes Scald Protection. – Where a combination potable water-heating and space-heating system requires water for space.
Factor of Evaporation: lbs/hr steam produced per BHp.
C HAPTER 4 C OMBUSTION A IR The importance of combustion, dilution, and ventilation air.
Chimney Fundamentals And Operation
Combustion Appliances
California Mechanical Code
Commercial Mechanical Requirements
Heating, Ventilating, and Air-Conditioning (HVAC)
Student Book © 2004 Propane Education & Research CouncilPage Placing Appliances into Initial Operation Knowing the proper techniques and.
ENERGY STAR Qualified Homes
NFPA 96 and Building Code Requirements for Commercial Kitchen Hood Systems Presentation for the Sevier County Fire Code and Building Code Officials Presented.
Service Technician Training
Proper Vent Sizing 4 Natural Draft Furnaces 4 Fan Assisted Furnace 4 Common Vent Systems.
SUPPLY DUCT SYSTEMS (Additional information. Read sections 18.4, 18.5, & 18.6) General –The supply duct system conveys conditioned air from an AHU to the.
Watertube Boiler.
UL/FM Fire Pump Systems Lunch & Learn 04/18/05
Engineered Products Make-Up Air for Heating and Cooling.
The House as a System 1. Air Temperature and Water Vapor.
Engineer Presentation
Backdraft Dampers. Backdraft Damper Training Application Backdraft dampers allow air to flow in one direction only and prevent unwanted (hot/cold outside.
Placing Vapor Distribution Systems and Appliances into Operation MODULE 5 Validating Combustion Air.
HVACR416 - Design Pressure Measurement Part 2. Pressure Measurement Several pressure measurements exist. They all measure the same things, the force of.
Welcome to Field Controls: HRV / ERV Training Duct Systems Part 3
Hydrotherm’s NEW KN Series
Ventilation for Confined Spaces requires ventilation as follows: An employee may not enter the space until the forced air ventilation has eliminated.
Placing Vapor Distribution Systems and Appliances into Operation MODULE 3 Validating Vapor Distribution Systems.
Fuel Oil Systems Fuel Oil Systems consist of: Storage Tanks Pumps
STEAM HEATING.
Mechanical for Oil Heat
Gas Furnace Planned Maintenance
9-1 Copyright  2010 McGraw-Hill Australia Pty Ltd PowerPoint slides to accompany Puffett, Hossack, Stone, Burn & Miles, Gasfitting 2e Chapter 9 FLUING.
8/27/ ENERGY VS EFFICIENCY Bob Witt CPD.
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer.
HVACR311 – Electrical for Refrigeration International Mechanical Code Relating to Refrigeration.
“We Bring Engineering to Life” U.S. Tobacco GAP – Barn Testing Procedure.
NFPA 31 Standard for the installation of Oil- Burning Equipment
Air Conditioning International Mechanical Code
Placing Vapor Distribution Systems and Appliances into Operation MODULE 10 Spillage Test.
HVACR116 – Trade Skills Longest length method.
1 HVACR318 – Refrigeration II International Mechanical Code Relating to Refrigeration.
Placing Vapor Distribution Systems and Appliances into Operation MODULE 4 Identifying Venting Requirements and Characteristics.
Chapter 38 Fireplace Construction and Layout. 2 Links for Chapter 38 Fireplace Terms Energy Efficiency Fireplace Section Related Web Sites Fireplace Elevations.
Chapter 24 Chimneys and Fireplaces Copyright Goodheart-Willcox Co., Inc. May not be posted to a publicly accessible website. Explain how masonry chimneys.
Day 2 Part 1 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
HEAT-GENERATING EQUIPMENT INTRODUCTION SELECTION EFFICIENCY FURNACES BOILERS CENTRAL HVAC SYSTEMS.
3.0 Comprehensive Performance Audit Fossil Fuel Appliances Health & Safety 3.2.
Day 1 Part 4 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
Day 2 Part 2 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
4.0 Equipment Installation Aspects (Section 4.5 On-Rate for Fuel-Fired Equipment)
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – March 2011eere.energy.gov COMBUSTION BASICS HEATING SYSTEMS FOR ENERGY AUDITORS AND INSPECTORS.
Boiler Safety Valve Regulations
The GranView Fireplace
Math Review CAZ Volume and Air Free CO PPM Calculations
RESIDENTIAL CONDENSING GAS FURNACES Vent Design & Installation Training Spring 2014 UTC Building & Industrial Systems Confidential and Proprietary Information.
N F G C r e v I s I o n s.
N F G C r e v I s I o n s.
XP PLUS Intro High Efficiency Circulating Water Heater
Boiler Safety Valve Regulations
Presentation transcript:

VENTING AND COMBUSTION AIR WWW.ROBERTSMECH.COM VENTING AND COMBUSTION AIR Roberts Mechanical Equipment Co.

WWW.ROBERTSMECH.COM ANSI Categories will tell you a great deal about the boiler and the application. III I IV II ANSI CATEGORIES

Understand the Table Left side indicates a negative pressure. II III IV I Left side indicates a negative pressure. Right Side indicates a positive pressure. WWW.ROBERTSMECH.COM Understand the Table

Top indicates non-condensing appliance (85% or less). Bottom indicates condensing appliances (86% or more). II III IV I WWW.ROBERTSMECH.COM Understand the Table

Examples (negative) Atmospheric Some fan assisted III Masonry Chimney B-Vent material WWW.ROBERTSMECH.COM Examples (negative)

Examples (Positive) Forced Draft Side wall vented III In line fan I UL Pressure stack or welded steel WWW.ROBERTSMECH.COM Examples (Positive)

Condensing / Non-Condensing inlet water temperature boiler efficiency, % 180 40 130 80 100 86 94 condensing boiler non-condensing boiler dew point III I WWW.ROBERTSMECH.COM IV II Condensing / Non-Condensing Effect of Inlet Water Temperature to Boiler Efficiency natural gas = 1050 Btu/ft

Lining A Masonry Chimney (Cat. I) Atmospheric – Clay Tile Liner Fan Assisted – Clay Tile Liner (Interior) Metal Liner (Exterior) Exception: Clay tile liner can be used with exterior chimney if an Atmospheric appliance is connected to the same chimney II III IV I WWW.ROBERTSMECH.COM Lining A Masonry Chimney (Cat. I) Reference: ANSI Z223.1-2002 10.4.1 and 13.1.9, NFPA211 4-2.2

Lining A Masonry Chimney (Category III) Forced Draft – Welded Steel, Pressure Stack, or Inner Liner of Pressure Rated Stack II III IV I WWW.ROBERTSMECH.COM Lining A Masonry Chimney (Category III) Reference: ANSI Z223.1-2002 10.4.1 and 13.1.9, NFPA211 4-2.2

Lining A Masonry Chimney (Category II) III IV I WWW.ROBERTSMECH.COM Fan Assisted– (85%+ Combustion Efficiency) AL29-4C Lining A Masonry Chimney (Category II) Reference: ANSI Z223.1-2002 10.4.1 and 13.1.9, NFPA211 4-2.2

Lining A Masonry Chimney (Category IV) II III IV I WWW.ROBERTSMECH.COM Fully Condensing – AL29-4C Lining A Masonry Chimney (Category IV) Reference: ANSI Z223.1-2002 10.4.1 and 13.1.9, NFPA211 4-2.2

Safe Venting by Code National Fuel Gas Code Horizontal distances Large stack area Self venting connector rise Fan Min capacities Different type of appliances Existing masonry chimneys Location of draft inducer WWW.ROBERTSMECH.COM Safe Venting by Code National Fuel Gas Code NFPA54 * IAS (A.G.A.) * ANSI Z 223.1

Common Violations (NFPA 54) Z223.1-2002 (Venting of Equipment) 10.6.1.4 The total horizontal distance of a vent plus the horizontal vent connector serving draft hood-equipped appliances shall not be greater than 75 % of the vertical height of the vent. Table 13.1 and 13.2 The total horizontal length of the vent plus the vent connector for a single Category I appliance is: 100% of the height (vent 6 – 30 ft high); 30 ft (vent 31 – 50 ft high); 50% of the height (vent 51 – 100 ft high) Height of Vent Not Greater than 75% of the Vertical Height WWW.ROBERTSMECH.COM Common Violations (NFPA 54) Z223.1-2002 (Venting of Equipment)

13. 2. 2 The maximum vent connector horizontal length shall be 18 in 13.2.2 The maximum vent connector horizontal length shall be 18 in./in of connector diameter. 13.2.4 The length of the common vent manifold shall not exceed 18 in./in. of common vent diameter. 13.2.5 The horizontal length of the common vent offset shall not exceed 18 in./in. of common vent diameter. Diameter 18 inches per inch WWW.ROBERTSMECH.COM Common Violations (NFPA 54) Z223.1-2002 13.2 (Sizing of Venting Systems)

Common Violations (NFPA 54) Z223 Sizing Tables WWW.ROBERTSMECH.COM 1’ Min. (3”-10” diameter) 2’ Min. (12”- 18” diameter) 4’ Min. (20” and above) WWW.ROBERTSMECH.COM Common Violations (NFPA 54) Z223 Sizing Tables

the Smallest Outlet Area Outlet Diameter Not Greater than 7 Times the Smallest Outlet Area 13.2.17 Where two or more appliances are connected to a vertical vent or chimney, the flow area of the largest section of vertical or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area, or draft hood outlet area unless designed in accordance with approved engineering methods. WWW.ROBERTSMECH.COM Common Violations (NFPA 54) Z223.1-2002 13.2.17 (Sizing of Venting Systems)

10.10.4.2 Vent connectors serving Category I appliances shall not be connected into any portion of mechanical draft systems operating under positive static pressure, such as those serving Category III or Category IV appliances. WWW.ROBERTSMECH.COM Common Violations (NFPA 54) Z223.1-2002 10.10.4.2 (Venting of Equipment)

Common Violations (NFPA 54) Z223.1-2002 10.5.4.3 (NFPA 211) 4-2.2 10.5.4.3 Masonry chimneys shall be built and installed in accordance with NFPA 211. 4-2.2 Masonry chimneys shall be lined….Cat II, III and IV gas appliances - special gas vents listed for installation within masonry chimneys. WWW.ROBERTSMECH.COM Common Violations (NFPA 54) Z223.1-2002 10.5.4.3 (NFPA 211) 4-2.2

10.3.3 Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 10.3.4 Vent connectors serving equipment vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. WWW.ROBERTSMECH.COM Common Violations (NFPA 54) Z223.1- 2002 10.3 (Mechanical Draft Systems)

Resolving Codes using Mechanical Draft System 503.6.9.3 Mechanical draft. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 10.5.3.1 Size of Chimneys. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. WWW.ROBERTSMECH.COM International Fuel Gas Code - Section 503 (Venting of Equipment) Z223.1- 2002 Standard for Venting of Equipment Resolving Codes using Mechanical Draft System

Mechanical Draft System (Check List) System should be UL listed (as a designed system). System must Monitor proper draft at all times. System must interlock, alarm and lock out appliances. System must be supplied with engineering (Acceptable Engineering Method) specific to installed appliances. System should modulate to match today’s efficient appliances. System performance should be guaranteed. WWW.ROBERTSMECH.COM Mechanical Draft System (Check List)

Vent Category Review Category Characteristic Type Draft Vent I II III IV Non-Condensing Negative pressure Natural draft appliance and fan assisted < 86 % efficient Draft hood: Negative Fan-assist: - 0.02 to - 0.08 WWW.ROBERTSMECH.COM B-Vent Fan assisted appliance > 86 % efficient Fan-assist: - 0.02 to - 0.08 Condensing Negative pressure AL29-4C Forced draft / Direct Vent < 86 % efficient Forced Draft (Pressure stack) Direct Vent (AL29) Non-Condensing Positive pressure Positive Condensing Positive pressure Fan assisted/ Pulse Positive AL29-4C Vent Category Review

WWW.ROBERTSMECH.COM Combustion Air

Combustion Air Code Z223.1-2002 8.3.3 Outdoor Combustion Air. 8.3.3.2 One Permanent Opening Method: One permanent opening, commencing within 12 in. of the top of the enclosure, shall be provided. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following: 1 in.²/3000 Btu of the total input rating of all equipment located in the enclosure, and not less than the sum of the areas of all vent connectors in the space. WWW.ROBERTSMECH.COM Z223.1-2002 8.3.3 Outdoor Combustion Air. Combustion Air Code

Sizing Combustion Air Louvers (Gravity) Louver(s) Sizing: 1 sq.in./4000 Btu per louver 4000 MBH = 1000 in2 of free area per louver. Typical louver has 30-60% free area. Depending on louver design actual louver size will be: Using 45% free area louvers = Two 5’ x 4’ louvers WWW.ROBERTSMECH.COM 2000 MBH 2000 MBH Sizing Combustion Air Louvers (Gravity) Tip: Check with the Louver Manufacturer for accurate ‘free space’ than watch equal products in the submittals.

Combustion Code Summery. NFPA 54 gas NFPA 31 oil BOCA all SBCCI gas & oil SBCCI solid Minimum No. openings required 2 Outdoor opening, sq. in./Btuh 1/4000 2/1000 Vertical ducts, sq. in./Btuh - Horizontal ducts, sq. in./Btuh 1/2000 Ducts same as opening yes Minimum duct dimension, inches 3 Louver & grill free area opening Free area allowance, wood* 20-25% 25% Free area allowance, metal* 60-75% 75% Damper interlocked *use manufacturer's free area rating when available. WWW.ROBERTSMECH.COM Combustion Code Summery.

Below Grade Mechanical Rooms Total fuel input rate of all fuel-burning devices located in the boiler room considered. The Btu rate per hour of all boilers at maximum burning rate, plus other devices such as water heaters, are used to size air openings. Outside air openings sizing must be done based on its free area. (Protective mesh must be no smaller than 0.25 inch to minimize dirt build-up or obstruction. WWW.ROBERTSMECH.COM Below Grade Mechanical Rooms

Direct Connect Combustion Air Best with Fan Assisted Appliances. Roof or Single side. Careful combining Combustion air intakes. Watch Horizontal lengths (fitting equal 10’). FREEZE PROTECTION WWW.ROBERTSMECH.COM Direct Connect Combustion Air Tip: Freeze protection should be proven damper system operating in the specific boiler sequence. Allows combining inlet also prevent freezing without power.

8. 3. 6 Mechanical Combustion Air Supply 8.3.6 Mechanical Combustion Air Supply. Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from outdoors at the minimum rate of 0.35 ft³/min per 1000 Btu/hr for all appliances located within the space. 8.3.6.1 Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. 8.3.6.2 Each of the appliances served shall be interlocked to the mechanical air supply system to prevent main burner operation where the mechanical air supply system is not in operation. WWW.ROBERTSMECH.COM Z223.1-2002 Combustion Air Code

Mechanical Combustion Air WWW.ROBERTSMECH.COM Guaranteed to provide proper combustion air. Small opening / more aesthetic. Solves Code Issues Mechanical Combustion Air Tip: Multiple water heaters or boilers running high efficiency firing rates warrant a modulating combustion air system.

Sizing Mechanical Combustion Air Louver Sizing: Engineered using ASHRAE Chimney Design Equation. Flue Gas Volume corrected for temperature = 1,400 cfm of combustion air 1400 cfm/500 fpm = 2.8 ft2 of louver free area Using a 45% free area louver = One 3’ x 2’ louver 2000 MBH WWW.ROBERTSMECH.COM Sizing Mechanical Combustion Air Tip: Be sure to consider any mechanical exhaust in the boiler. Fan must keep up with all ventilation as well.

The Barometric Damper NORMAL OPERATION Barometric Damper is weighted to open and ‘break’ draft by mixing a % of room air. The chimney is drawing at a specific rate, but now draws from the water heater/boiler and room. Typical draft for negative commercial appliances is -.02 to -.08. WWW.ROBERTSMECH.COM The Barometric Damper Tip: Use a barometric damper on stacks over 25’ or 30’ as long as the appliance is category I or II (negative).

The Barometric Damper NEGATIVE MECH ROOM: Room goes negative. Barometric is pulled into the room. The barometric becomes a source of make up air for the room. Problem is, this make up air is deadly. WWW.ROBERTSMECH.COM The Barometric Damper Tip: Pay close attention to the combustion air in a room. Look for sources of problems such as old leaky returns.

Thank You! www.robertsmech.com More Information / Additional Training: Roberts Mechanical Equipment P: 216-587-0005 F: 216-587-0008 Or visit our industry leading web site at: www.robertsmech.com Written by/Property of: Grant Roberts WWW.ROBERTSMECH.COM Thank You!