Lecture 17: VAV and Terminal Reheat Systems Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to.

Slides:



Advertisements
Similar presentations
HVAC 13a CNST 305 Environmental Systems 1 Dr. Berryman
Advertisements

Chapter 3. HVAC Delivery Systems
HVAC Basics Bin Yan HVAC – Heating, Ventilation, Air-conditioning.
Chapter 12 HVAC Controls Pneumatic Control Systems • Air Compressor Stations • Transmitters and Controllers • Pneumatic Thermostats • Auxiliary Components.
Circulating Water System
HEALTHCARE BUILDING AUTOMATION
RWD CONTROLLERS TECHNICAL
Lecture 19: HVAC Outside Air Systems and Modeling Guidelines Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under.
Lecture 10: Zone and Modeling Controls, Simple HVAC for Load Calculations Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign.
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning
Foundations of Real Estate Management BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building ®
Foundations of Real Estate Management TM BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building.
Components of HVAC System
HVAC Heating, Ventilation and Air Conditioning -something that you never think about until it doesn’t work properly.
Lecture 23: Primary System Loops and Components Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract.
Objectives Finish with ducts and fans Define project topics.
Lecture 20: Radiant Systems Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the National Renewable.
Lecture 22: Primary System Loops in EnergyPlus
Lecture 7: Building Modeling Questions Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the National.
HVAC Systems Overview HVAC Overview - # 1 Tom Lawrence
Siemens Building TechnologiesRWD heatpump controllers Xavier Zabalegui/David Jefferson 1 January 2003 RWD Heat Pump controllers RWD Heat Pump Controllers.
Objectives Finish with Multizone Systems
Lecture 18: Template Systems and Autosizing Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Objectives Review/Learn about HVAC Configurations Describing systems and processes in the psychrometric chart Analyze processes in AHU and buildings –Finish.
Lecture 15: Air Primary Loops and Controls Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the.
PSU Building Thermal and Mechanical Systems Laboratory Environment A/E Kurt M. Shank, M.S. & Stanley A. Mumma, Ph.D., P.E. College of Engineering Department.
Objectives Discuss Project Topics Learn to design VAV and DOAS System.
An intelligent VAV zoning system
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
© American Standard Inc Fan Pressure Optimization The Trane Company.
Lecture 1: An Overview of Simulation and EnergyPlus Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract.
Lecture 16: Zone Air Paths and Air Distribution Units
Conditioning of Moist Air
Lecture 5: Building Envelope Description (Part I)
Important variables Water: Air: Conversion:
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
Lecture Objectives: Finish with HVAC Systems Discuss Final Project.
Lecture Objectives: Specify Exam Time Finish with HVAC systems –HW3 Introduce Projects 1 & 2 –eQUEST –other options.
Chapter 11: Space Air Diffusion Conditioned air is normally supplied to air outlets at velocities much higher than would be acceptable in the occupied.
STUDY ON HVAC SYSTEM STUDY ON HVAC SYSTEM
MECHANICAL ENGINEERING FOR SYSTEM BALANCE ASHRAE MEETING 2/15/2007 NORTHERN NEVADA CHAPTER 126 MATT BRENNAN, TBE.
1 Lamp operating factor Published lumen output is based on laboratory conditions Voltage  Rated at line voltage of 115V Standard reactor ballast  Electromagnetic.
Lecture Objectives: Clarify issues related to eQUEST –for midterm project Learn more about various HVAC - economizer - heat recovery Discuss about the.
Introduction to Energy Management. Week/Lesson 7 HVAC System Types.
Energy Cost Budget Highlights Jason Glazer, PE GARD Analytics Arlington Heights, Illinois Energy Cost.
Final Projects Grading criteria is posted on the course website Preliminary results are due Next Tuesday Final Project delivery on Monday Dec. 7 th –Final.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Lecture Objectives: Discuss the exam problems Answer question about HW 3 and Final Project Assignments Building-System-Plant connection –HVAC Systems.
Objectives Learn about Fans Discuss: Exam (I will have an extra office hour on Monday at 8:00 am) Final Project (I need your group member lists till tomorrow).
Objectives Propose residential system related final project –Compare VAV systems with DOAS systems.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Fan Coil Controller FC/S 1.1
Building Automation System
Objectives Finish analysis of most common HVAC Systems
Technology in Architecture
BUILDING HEATING AND COOLING
HVAC Basics Arkan Arzesh HVAC – Heating, Ventilation, Air-conditioning.
Types of HVAC Technology Used in Business Establishments
Chilled Beam Performance:
HCB 3-Chap 19A: All-Air Systems_Single Zone
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Lecture Objectives: Discuss HW4 parts
Follow-ups from Classes 8 and 9
Objectives Finish with Heat exchangers
Objective Revie the Cooling Cycle Learn about air distribution systems
‘‘ BUILDING AUTOMATION’’
Presentation transcript:

Lecture 17: VAV and Terminal Reheat Systems Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the National Renewable Energy Laboratory. All material Copyright U.S.D.O.E. - All rights reserved

2 Purpose of this Lecture  Gain an understanding of how to: Define Air Loops and Zone Equipment input for various types of fan systems  VAV  Terminal Reheat  Review various keywords already covered and show how they interact to form a complete system definition

VAV Systems in EnergyPlus

4 VAV with Reheat and Outside Air Example  Air Loop contains the Mixed Air System, Supply Fan and the Cooling Coil  Outside air system will be discussed later in more detail  Zone Equipment Loop contains the Splitter, VAV Box Air Distribution Unit, the zones, and the Return Air Path with the Mixer.

5 VAV with Reheat Air Loop Air Primary Loop, Typical Terminal Reheat 1, !- Primary Air Loop Name Reheat System 1 Controllers, !- Name: Controller List Reheat System 1 Avail List, !- Name: System Availability Manager List 1.3, !- Primary air design volumetric flow rate {m3/s} Air Loop Branches, !- Air Loop Branch List Name, !- Air Loop Connector List Name Air Loop Inlet Node, !- ReturnAir AirLoop Inlet Node Return Air Mixer Outlet Node, !- ZoneEquipGroup Outlet Node Zone Equipment Inlet Node, !- SupplyAirPath ZoneEquipGroup Inlet Nodes Air Loop Outlet Node; !- AirLoop Outlet Nodes

6 VAV with Reheat Controller and Branch Lists CONTROLLER LIST, Reheat System 1 Controllers, !- Name Controller:Simple, !- Controller Type 1 Main Cooling Coil Controller; !- Controller Name 1 BRANCH LIST, Air Loop Branches, !- Branch List Name Air Loop Main Branch; !- Branch Name 1

7 VAV with Reheat Main Branch BRANCH, Air Loop Main Branch, !- Branch Name 1.3, !- Maximum Branch Flow Rate {m3/s} OUTSIDE AIR SYSTEM, !- Comp1 Type OA Sys 1, !- Comp1 Name Air Loop Inlet Node, !- Comp1 Inlet Node Name Mixed Air Node, !- Comp1 Outlet Node Name PASSIVE, !- Comp1 Branch Control Type FAN:SIMPLE:VariableVolume, !- Comp2 Type Var Vol Supply Fan 1, !- Comp2 Name Mixed Air Node, !- Comp2 Inlet Node Name Cooling Coil Air Inlet Node, !- Comp2 Outlet Node Name ACTIVE, !- Comp2 Branch Control Type

8 VAV with Reheat Main Branch (cont’d) COIL:Water:DetailedFlatCooling, !- Comp3 Type Detailed Cooling Coil, !- Comp3 Name Cooling Coil Air Inlet Node, !- Comp3 Inlet Node Name Air Loop Outlet Node, !- Comp3 Outlet Node Name PASSIVE; !- Comp3 Branch Control Type

9 VAV with Reheat System Availability Manager SYSTEM AVAILABILITY MANAGER LIST, Reheat System 1 Avail List, !- Name SYSTEM AVAILABILITY MANAGER:SCHEDULED, !- System Availability Manager type 1 Reheat System 1 Avail; !- System Availability Manager name 1 SYSTEM AVAILABILITY MANAGER:SCHEDULED, Reheat System 1 Avail, !- Name FanAndCoilAvailSched; !- Schedule name

10 VAV with Reheat Supply Fan FAN:SIMPLE:VariableVolume, Var Vol Supply Fan 1, !- Fan Name CoolingCoilAvailSched, !- Available Schedule 0.7, !- Fan Total Efficiency 600.0, !- Delta Pressure {Pa} 1.3, !- Max Flow Rate {m3/s} 0.20, !- Min Flow Rate {m3/s} 0.9, !- Motor Efficiency 1.0, !- Motor In Airstream Fraction , !- FanCoefficient , !- FanCoefficient , !- FanCoefficient , !- FanCoefficient , !- FanCoefficient 5 Air Loop Inlet Node, !- Fan_Inlet_Node Cooling Coil Air Inlet Node; !- Fan_Outlet_Node

11 VAV with Reheat Cooling Coil COIL:Water:SimpleCooling, Main Cooling Coil 1, !- Coil Name CoolingCoilAvailSched, !- Available Schedule autosize, !- UA of the Coil {W/K} autosize, !- Max Water Flow Rate of Coil {m3/s} 0.9, !- Leaving Relative Humidity of Coil Main Cooling Coil 1 Water Inlet Node, !- Coil_Water_Inlet_Node Main Cooling Coil 1 Water Outlet Node, !- Coil_Water_Outlet_Node Mixed Air Node 1, !- Coil_Air_Inlet_Node Main Cooling Coil 1 Outlet Node; !- Coil_Air_Outlet_Node

12 VAV with Reheat Cooling Coil Controller Controller:Simple, Main Cooling Coil Controller, !- Name TEMP, !- Control variable Reverse, !- Action FLOW, !- Actuator variable Air Loop Outlet Node, !- Control_Node Cooling Coil Water Inlet Node, !- Actuator_Node 0.001, !- Controller Convergence Tolerance: delta temp from setpoint {C} , !- Max Actuated Flow {m3/s} 0.0; !- Min Actuated Flow {m3/s}

13 VAV with Reheat Zone Supply Air Path ZONE SUPPLY AIR PATH, TermReheatSupplyPath, !- Supply Air Path Name Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Zone Splitter, !- KEY--System Component Type Zone Supply Air Splitter; !- Component Name

14 VAV with Reheat Zone Splitter ZONE SPLITTER, Zone Supply Air Splitter, !- Splitter Name Zone Equipment Inlet Node, !- Inlet_Node Zone 1 Inlet Node, !- Outlet_Node_1 Zone 2 Inlet Node, !- Outlet_Node_2 Zone 3 Inlet Node; !- Outlet_Node_3

15 VAV with Reheat Zone Return Air Path ZONE RETURN AIR PATH, TermReheatReturnPath, !- Return Air Path Name Return Air Mixer Outlet, !- Return Air Path Outlet Node Zone Mixer, !- KEY--System Component Type 1 Zone Return Air Mixer; !- Component Name 1

16 VAV with Reheat Zone Mixer ZONE MIXER, Zone Return Air Mixer, !- Mixer Name Return Air Mixer Outlet, !- Outlet_Node Zone 1 Outlet Node, !- Inlet_Node_1 Zone 2 Outlet Node, !- Inlet_Node_2 Zone 3 Outlet Node; !- Inlet_Node_3

17 VAV with Reheat Zone Equip Configuration CONTROLLED ZONE EQUIP CONFIGURATION, RESISTIVE ZONE, !- Zone Name Zone1Equipment, !- List Name: Zone Equipment Zone1Inlets, !- List Name: Zone Inlet Nodes, !- List Name: Zone Exhaust Nodes Zone 1 Node, !- Zone Air Node Name Zone 1 Outlet Node; !- Zone Return Air Node Name

18 VAV with Reheat Zone Equipment List ZONE EQUIPMENT LIST, Zone1Equipment, !- Name AIR DISTRIBUTION UNIT, !- KEY--Zone Equipment Type 1 Zone1TermReheat, !- Type Name 1 1, !- Cooling Priority 1; !- Heating Priority

19 VAV with Reheat Air Distribution Unit AIR DISTRIBUTION UNIT, Zone1TermReheat, !- Air Distribution Unit Name Zone 1 Reheat Air Outlet Node, !- Air Dist Unit Outlet Node Name SINGLE DUCT:VAV:REHEAT, !- KEY--System Component Type 1 Zone 1 VAV System; !- Component Name 1 NODE LIST, Zone1Inlets, !- Node List Name Zone 1 Reheat Air Outlet Node; !- Node_ID_1

20 VAV with Reheat VAV Terminal Unit SINGLE DUCT:VAV:REHEAT, SPACE1-1 VAV Reheat, !- Name of System ReheatCoilAvailSched, !- Availability schedule for VAV System SPACE1-1 Zone Coil Air In Node, !- Damper Outlet Node SPACE1-1 ATU In Node, !- Damper Inlet Node 0.33, !- Maximum air flow rate {m3/s} 0.3, !- Min air flow fraction SPACE1-1 Zone Coil Water In Node, !- Control node COIL:Water:SimpleHeating, !- Reheat Component Object SPACE1-1 Zone Coil, !- Name of Reheat Component , !- Max Reheat Water Flow {m3/s} 0.0, !- Min Reheat Water Flow {m3/s} SPACE1-1 In Node, !- Reheat Air Outlet Node 0.001, !- Convergence Tolerance REVERSE ACTION; !- Damper Heating Action

21 VAV with Reheat Reheat Coil COIL:Water:SimpleHeating, SPACE1-1 Zone Coil, !- Coil Name ReheatCoilAvailSched, !- Available Schedule 300., !- UA of the Coil {W/K} , !- Max Water Flow Rate of Coil {m3/s} SPACE1-1 Zone Coil Water In Node, !- Coil_Water_Inlet_Node SPACE1-1 Zone Coil Water Out Node, !- Coil_Water_Outlet_Node SPACE1-1 Zone Coil Air In Node, !- Coil_Air_Inlet_Node SPACE1-1 In Node; !- Coil_Air_Outlet_Node

Terminal Reheat Systems in EnergyPlus

23 TermReheat Controller and Branch Lists CONTROLLER LIST, Reheat System 1 Controllers, !- Name Controller:Simple, !- Controller Type 1 Main Cooling Coil Controller; !- Controller Name 1 BRANCH LIST, Air Loop Branches, !- Branch List Name Air Loop Main Branch; !- Branch Name 1

24 TermReheat Main Branch BRANCH, Air Loop Main Branch, !- Branch Name 1.3, !- Maximum Branch Flow Rate {m3/s} FAN:SIMPLE:VariableVolume, !- Comp1 Type Var Vol Supply Fan 1, !- Comp1 Name Air Loop Inlet Node, !- Comp1 Inlet Node Name Cooling Coil Air Inlet Node, !- Comp1 Outlet Node Name ACTIVE, !- Comp1 Branch Control Type COIL:Water:DetailedFlatCooling, !- Comp2 Type Detailed Cooling Coil, !- Comp2 Name Cooling Coil Air Inlet Node, !- Comp2 Inlet Node Name Air Loop Outlet Node, !- Comp2 Outlet Node Name PASSIVE; !- Comp2 Branch Control Type

25 TermReheat System Availability Manager SYSTEM AVAILABILITY MANAGER LIST, Reheat System 1 Avail List, !- Name SYSTEM AVAILABILITY MANAGER:SCHEDULED, !- System Availability Manager type 1 Reheat System 1 Avail; !- System Availability Manager name 1 SYSTEM AVAILABILITY MANAGER:SCHEDULED, Reheat System 1 Avail, !- Name FanAndCoilAvailSched; !- Schedule name

26 TermReheat Supply Fan FAN:SIMPLE:ConstVolume, Supply Fan 1, !- Fan Name FanAndCoilAvailSched, !- Available Schedule 0.7, !- Fan Total Efficiency 600.0, !- Delta Pressure {Pa} 1.3, !- Max Flow Rate {m3/s} 0.9, !- Motor Efficiency 1.0, !- Motor In Airstream Fraction Air Loop Inlet Node, !- Fan_Inlet_Node Cooling Coil Air Inlet Node; !- Fan_Outlet_Node

27 TermReheat Cooling Coil COIL:Water:SimpleCooling, Main Cooling Coil 1, !- Coil Name CoolingCoilAvailSched, !- Available Schedule autosize, !- UA of the Coil {W/K} autosize, !- Max Water Flow Rate of Coil {m3/s} 0.9, !- Leaving Relative Humidity of Coil Main Cooling Coil 1 Water Inlet Node, !- Coil_Water_Inlet_Node Main Cooling Coil 1 Water Outlet Node, !- Coil_Water_Outlet_Node Mixed Air Node 1, !- Coil_Air_Inlet_Node Main Cooling Coil 1 Outlet Node; !- Coil_Air_Outlet_Node

28 TermReheat Cooling Coil Controller Controller:Simple, Main Cooling Coil Controller, !- Name TEMP, !- Control variable Reverse, !- Action FLOW, !- Actuator variable Air Loop Outlet Node, !- Control_Node Cooling Coil Water Inlet Node, !- Actuator_Node 0.001, !- Controller Convergence Tolerance: delta temp from setpoint {C} , !- Max Actuated Flow {m3/s} 0.0; !- Min Actuated Flow {m3/s}

29 TermReheat Zone Thermostat ZONE CONTROL:THERMOSTATIC, Zone 1 Thermostat, !- Thermostat Name RESISTIVE ZONE, !- Zone Name Zone Control Type Sched, !- Control Type SCHEDULE Name SINGLE HEATING SETPOINT, !- Control Type #1 Heating Setpoint with SB, !- Control Type Name #1 SINGLE COOLING SETPOINT, !- Control Type #2 Cooling Setpoint with SB; !- Control Type Name #2

30 TermReheat Thermostat Setpoints SINGLE HEATING SETPOINT, Heating Setpoint with SB, !- Name Heating Setpoints; !- Setpoint Temperature SCHEDULE Name SINGLE COOLING SETPOINT, Cooling Setpoint with SB, !- Name Cooling Setpoints; !- Setpoint Temperature SCHEDULE Name

31 TermReheat Zone Supply Air Path ZONE SUPPLY AIR PATH, TermReheatSupplyPath, !- Supply Air Path Name Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Zone Splitter, !- KEY--System Component Type Zone Supply Air Splitter; !- Component Name

32 TermReheat Zone Return Air Path ZONE RETURN AIR PATH, TermReheatReturnPath, !- Return Air Path Name Return Air Mixer Outlet, !- Return Air Path Outlet Node Zone Mixer, !- KEY--System Component Type 1 Zone Return Air Mixer; !- Component Name 1

33 TermReheat Zone Splitter ZONE SPLITTER, Zone Supply Air Splitter, !- Splitter Name Zone Equipment Inlet Node, !- Inlet_Node Zone 1 Inlet Node, !- Outlet_Node_1 Zone 2 Inlet Node, !- Outlet_Node_2 Zone 3 Inlet Node; !- Outlet_Node_3

34 TermReheat Zone Mixer ZONE MIXER, Zone Return Air Mixer, !- Mixer Name Return Air Mixer Outlet, !- Outlet_Node Zone 1 Outlet Node, !- Inlet_Node_1 Zone 2 Outlet Node, !- Inlet_Node_2 Zone 3 Outlet Node; !- Inlet_Node_3

35 TermReheat Zone Equip Configuration CONTROLLED ZONE EQUIP CONFIGURATION, RESISTIVE ZONE, !- Zone Name Zone1Equipment, !- List Name: Zone Equipment Zone1Inlets, !- List Name: Zone Inlet Nodes, !- List Name: Zone Exhaust Nodes Zone 1 Node, !- Zone Air Node Name Zone 1 Outlet Node; !- Zone Return Air Node Name

36 TermReheat Zone Equipment List ZONE EQUIPMENT LIST, Zone1Equipment, !- Name AIR DISTRIBUTION UNIT, !- KEY--Zone Equipment Type 1 Zone1TermReheat, !- Type Name 1 1, !- Cooling Priority 1; !- Heating Priority

37 TermReheat Air Distribution Unit AIR DISTRIBUTION UNIT, Zone1TermReheat, !- Air Distribution Unit Name Zone 1 Reheat Air Outlet Node, !- Air Dist Unit Outlet Node Name SINGLE DUCT:VAV:REHEAT, !- KEY--System Component Type 1 Zone 1 VAV System; !- Component Name 1 NODE LIST, Zone1Inlets, !- Node List Name Zone 1 Reheat Air Outlet Node; !- Node_ID_1

38 TermReheat VAV Terminal Unit SINGLE DUCT:VAV:REHEAT, SPACE1-1 VAV Reheat, !- Name of System ReheatCoilAvailSched, !- Availability schedule for VAV System SPACE1-1 Zone Coil Air In Node, !- Damper Outlet Node SPACE1-1 ATU In Node, !- Damper Inlet Node 0.33, !- Maximum air flow rate {m3/s} 0.3, !- Min air flow fraction SPACE1-1 Zone Coil Water In Node, !- Control node COIL:Water:SimpleHeating, !- Reheat Component Object SPACE1-1 Zone Coil, !- Name of Reheat Component , !- Max Reheat Water Flow {m3/s} 0.0, !- Min Reheat Water Flow {m3/s} SPACE1-1 In Node, !- Reheat Air Outlet Node 0.001, !- Convergence Tolerance REVERSE ACTION; !- Damper Heating Action

39 TermReheat Reheat Coil COIL:Water:SimpleHeating, SPACE1-1 Zone Coil, !- Coil Name ReheatCoilAvailSched, !- Available Schedule 300., !- UA of the Coil {W/K} , !- Max Water Flow Rate of Coil {m3/s} SPACE1-1 Zone Coil Water In Node, !- Coil_Water_Inlet_Node SPACE1-1 Zone Coil Water Out Node, !- Coil_Water_Outlet_Node SPACE1-1 Zone Coil Air In Node, !- Coil_Air_Inlet_Node SPACE1-1 In Node; !- Coil_Air_Outlet_Node

40 Summary  This lecture highlighted the EnergyPlus input necessary to define most VAV and Terminal Reheat systems Air loop and zone equipment input Thermostat input Fan and coil component input Controller input