Master Examination Practice Drill #8 2011 (16) O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles.

Slides:



Advertisements
Similar presentations
Wiring Design and Protection Including Ground Fault Circuit Interrupters.
Advertisements

FIRE PUMP ELECTRICAL CONFIGURATIONS UNDER 600 VOLTS.
Master Examination Practice Drill # O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded.
Master Examination Practice Drill # Ted “Smitty” Smith.
DAY 4 CHAPTER 3 CONDUCTOR SIZES,TYPES, ETC.. Continuous Load. A load where the maximum current is expected to continue for 3 hours or more. Continuous.
EET Survey of Electronics
Electrical Power Systems
Master Examination Practice Drill # O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at.
2014 CHANGES TWO MINUTE DRILL COPYRIGHT TED “SMITTY” SMITH ©2014.
The Home Inspection Book: A Guide for Professionals By Marcia Darvin Spada Copyright, Thomson/South-Western, 2003, Revised, 2006.
©Ted “Smitty” Smith This speed drill focuses on calculations that will be required for the journeyman and masters examination. The question slide.
Tom Kader Chief Electrical Inspector Spaces About Electrical Equipment Sufficient access and working space shall be provided and maintained about.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 25- Residential Improving your skill in code Look Up Increasing Speed Drill.
Objectives Review electric circuits and electricity pricing - Introduce HW5 Select conductor and conduit List electrical devices.
©Ted “Smitty” Smith  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead.
Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up.
Two Minute Drill Number 26- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
COMMERCIAL ELECTRICAL (Chapter 11)
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.
Two Minute Drill Number 27- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Calculation Speed Drill # NEC
Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.
Copyright 2008 Ted "Smitty" Smith.  Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. 
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 31- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 22- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 24- Residential.
Speed Drill 51 Wireways and Raceways.
2008 Code Drills (C) Copyright 2008 Ted "Smitty" Smith 1 Smitty’s Speed Drills.
Ag. Mechanics for Beginning Teachers
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
Starting Residential Wiring.  The most important element in wiring. Safety is proper grounding.  Grounding is the connection of all parts of a wiring.
HOUSE WIRING Final Review. Electricity Electricity = flow of electrons Conductor= electricity passes thru easily - Metal, water, person Insulator = restricts.
Installation of Heating, Cooling, and Refrigeration Systems Electricity for Refrigeration, Heating and Air Conditioning 7th Edition Chapter 8 Installation.
ELECTRICAL WIRING WIRING BASICS Written by Bobby Joslin
ELECTRICAL INSTRUMENTS ( service and utilization )
N.E.C. Installation Techniques and Common Violations
Smitty’s Two Minute Drill Grounding
Advanced Calculations Drill 1 for the 2011 NEC
License Examination Practice Drill
2011 Changes Two Minute Drill
Smitty’s Two Minute Drills
Smitty’s Two Minute Drill Overcurrent Protection
Smitty’s Two Minute Drill Mixed Content -05
Theory and Calculations
Smitty’s Two Minute Drill #9: Special Occupancies
Practice Code Look Up Two Minute Drill #7
Conductors and Cables 2017 NEC
Ampacity Calculations and Overcurrent Protection 1
Calculations: Transformers and Service Conductor Calculations
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Overcurrent Protection— Fuses and Circuit Breakers
2014 Changes Two Minute Drill
EET 323 – Electrical System Design Lecture 9: Grounding
Smitty’s Two Minute Drill Grounding and Bonding
Objectives Learn about Electricity Pricing Electric systems.
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Varied Number 7
Calculations Review Drill
Calculation Speed Drill Varied-1
Varied Calculations Drill 2
Presentation transcript:

Master Examination Practice Drill # (16)

O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles installed in _________ require GFCI protection for personnel. O I. Bathrooms O II. Kitchens A. I only B. II only C. Neither I nor II D. Both I and II

QuestionAnswerReferenceNEC PG. # 1.D210.8(B)(1)&(2)51

O 2. Communications wires and cables shall have a voltage rating of NOT less than _____. A. 60 volts B. 120 volts C. 300 volts D. 600 volts

QuestionAnswerReferenceNEC PG. # 2.C

O 3. An emergency system is required to have NO more than ______ to have power available in the event of failure of the normal electrical supply system. A. 10 seconds B. 15 seconds C. 45 seconds D. 5 minutes

QuestionAnswerReferenceNEC PG. # 3.A

O 4. X-ray equipment installed in a hospital may be served by a hard service cord with a suitable plug provided the branch-circuit rating does NOT exceed _______. A. 15 amperes B. 20 amperes C. 30 amperes D. 50 amperes

QuestionAnswerReferenceNEC PG. # 4.C517.71(A), Ex.455

O 5. Conductors supplying more than one (1) motor shall have an ampacity of NOT less than _____ of the full-load current rating of the largest motor in the group and 100% of the full-load current ratings of all the other motors in the group. A. 125 percent B. 110 percent C. 150 percent D. 175 percent

QuestionAnswerReferenceNEC PG. # 5.A430.24(1)&(2)318

O 6. Given: A straight pull of size 4 AWG and larger conductors is to be made in a junction box that will have 3 in. conduit and two (2) 2 in. conduits entering on the same side and exiting on the opposite wall. No splices will be contained in the box. Which of the following listed junction boxes is the MINIMUM required for this installation? A. 18 in. x 12 in. B. 20 in. x 18 in. C. 24 in. x 24 in. D. 30 in. x 30 in.

QuestionAnswerReferenceNEC PG. # 6.C314.28(A)(1)183 3in. (largest conduit) x 8 = 24 in.

O 7. Given” A recreational vehicle campground has one hundred-fifty (150) campsites provided with electrical power. Twenty-five (25) of the campsites are reserved as tent sites. How many of the sites are required to have a 20-ampere, 125-volt receptacle? A. 105 B. 125 C. 150 D. None

QuestionAnswerReferenceNEC PG. # 7.C

O 8. Determine the MAXIMUM overcurrent protection permitted for size 14 AWG THWN copper motor control-circuit conductors tapped from the load side of a motor overcurrent protection device. Given: The conductors require short-circuit protection and do not extend beyond the motor control equipment enclosure. A. 20 amperes B. 25 amperes C. 30 amperes D. 100 amperes

QuestionAnswerReferenceNEC PG. # 8.DTbl (B)327

O 9. Where size 6 AWG THWN copper branch- circuit conductors supply a 240-volt, single- phase, 5,000 VA non-motor operated appliance, the MAXIMUM standard size circuit breaker permitted for overcurrent protection on this circuit is rated _______. A. 55 amperes B. 40 amperes C. 35 amperes D. 30 amperes

QuestionAnswerReferenceNEC PG. # 9.C422.11(E)(3)291 Single – phase current formula 240.6(A)91 I = Power I = 5,000 VA = 20.8 amperes x 150% = 31.2 amperes Volts Volts *NOTE – The next standard size circuit breaker with a rating of 35 amperes should be selected

O 10. The ampacity of size 1/0 AWG THWN/THHN, dual-rated copper conductors enclosed in rigid metal conduit (RMC) when installed underground in direct contact with the earth is _______. A. 170 amperes B. 125 amperes C. 130 amperes D. 150 amperes

QuestionAnswerReferenceNEC PG. # 10.D300.5(B)137 Tbl (A)169 Tbl (B)(16)

O 11. Every electrified truck parking space intended to provide an electrical supply for transport refrigerated units shall be equipped with a _______. O I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire receptacle O II. 60 ampere, 280-volt, 3-phase, 3-pole, 4-wire receptacle A. I only B. II only C. Either I or II D. Both I and II

QuestionAnswerReferenceNEC PG. # 11.C626.31(C(551

O 12. Flexible cord is permitted to be connected to fluorescent luminaires where the cord ___________. A. Has an ampacity of at least 20 amperes B. Is visible its entire length C. Is at least a size 12 AWG D. Runs through holes in walls

QuestionAnswerReferenceNEC PG. # 12.B410.62(C)(1)(2)a.284

O 13. An outdoor motor fuel gasoline dispensing pump is considered to be a Class I, Div. 2 hazardous location up to _____ above grade level within _____ horizontally from any edge of the motor fuel pump enclosure. A. 18 inches – 10 feet B. 24 inches – 20 feet C. 24 inches – 10 feet D. 18 inches – 30 feet

QuestionAnswerReferenceNEC PG. # 13.ATbl (B)(1)426

O 14. Determine the MAXIMUM permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 15 hp, 208-volt, three-phase, squirrel cage, Design B, continuous-duty ac motor. Assume the rating you select will be sufficient for the starting current of the motor and exceptions need not be applied. A amperes B amperes C amperes D amperes

QuestionAnswerReferenceNEC PG. # 14.C430.6(A)(1)311 Tbl (C)(1)322 Tbl FLC of motor – 46.2 amperes x 250% = amperes

O 15. What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. PVC conduit? A. 10 feet B. 8 feet C. 6 feet D. 5 feet

QuestionAnswerReferenceNEC PG. # 15.DTbl

O 16. Unless approved for a higher voltage, surface nonmetallic raceways are NOT permitted where the voltage is _______ or more between conductors. A. 120 volts B. 150 volts C. 300 volts D. 277 volts

QuestionAnswerReferenceNEC PG. # 16.C388.12(3)237

O 17. Determine the MAXIMUM size overload protection required for a 480-volt, 3-phase, 15 hp, continuous-duty ac motor, where given the following related information. Assume the value you select will permit the overload device to carry the motor load and modification of this value is not required.  Design C  Temperature rise – 40° C  Service factor – 1.12  Nameplate ampere rating – 18 amperes A amperesC amperes B amperesD amperes

QuestionAnswerReferenceNEC PG. # 17.A430.6(A)(2) (A)(1)319 FLA = 18 amperes x 115% = 20.7 amperes

O 18. Any pipe or duct system foreign to the electrical installation must not enter a transformer vault? Which of the following listed is NOT considered foreign to the vault? A. A roof drain B. A building water main C. An air duct passing through the vault D. An automatic fire protection water sprinkler

QuestionAnswerReferenceNEC PG. # 18. D

O 19. Given: A 50 kVA transformer with a 480- volt, 3-phase, primary and a 208Y/120 volt, 3-phase secondary is to be installed. Overcurrent protection is required on both primary and secondary side of the transformer. Determine the MAXIMUM size overcurrent protection device permitted on the primary side. A. 125 amperes B. 150 amperes C. 175 amperes D. 200 amperes

QuestionAnswerReferenceNEC PG. # 19.B450.3(B)348 Tbl (B) (A(91 3 – phase current formula I = kVA x 1000 I = 50 x 1000 = 50,000 = 60.2 amperes E x volts x amperes x 250% = amperes *NOTE – A 150 ampere OCP device is required

O 20. An inverse time circuit breaker used as the disconnecting means for a 50 hp, 480- volt, three-phase continuous-duty, induction- type type ac motor shall have an ampere rating of at LEAST ________. A. 82 amperes B. 75 amperes C. 163 amperes D. 98 amperes

QuestionAnswerReferenceNEC PG. # 20.B430.6(A)(1)311 Tbl (A)332 FLC of motor = 65 amperes x amperes

O 21. Circuit breakers are NOT rated to carry 100 percent of the continuous load continuously, unless they have a rating for at LEAST _________. A. 100 amperes B. 200 amperes C. 400 amperes D. 600 amperes

QuestionAnswerReferenceNEC PG. # 21.DTrade Knowledge

O 22. A fifteen (15) ft. horizontal run of rigid metal conduit (RMC) is to be installed between two enclosures located in a Class II, Division 1 hazardous location. One enclosure is dust ignition proof, the other is not. The NEC® requires a MINIMUM of _______ sealing fittings. A. None required B. One C. Two D. Three

QuestionAnswerReferenceNEC PG. # 22.A502.15(2)387

O 32. Where fuses are used for motor overload protection, if the supply system is a 3-wire, 3-phase, ac with one conductor grounded, the NEC® requires a MINIMUM of how many fuses? A. None required B. One C. Two D. Three

QuestionAnswerReferenceNEC PG. # 23.D

O 24. Conductors leading to a gasoline motor fuel dispensing pump shall be _________. A. Provided with a switch B. Red in color C. Orange in color D. Insulated with MTW insulation

QuestionAnswerReferenceNEC PG. # 24.A514.11(A)428

O 25. In general, direct-buried cables of 13,000 volts must be buried at a depth of NOT less than ______. A. 24 inches B. 30 inches C. 36 inches D. 42 inches

QuestionAnswerReferenceNEC PG. # 25.BTbl , Col. 1146

Click here to continue to non- timed drill

O 1. In commercial and industrial establishments, all 15- and 20- ampere, single-phase, 125 volt receptacles installed in _________ require GFCI protection for personnel. O I. Bathrooms O II. Kitchens A. I only B. II only C. Neither I nor II D. Both I and II

QuestionAnswerReferenceNEC PG. # 1.D210.8(B)(1)&(2)51

O 2. Communications wires and cables shall have a voltage rating of NOT less than _____. A. 60 volts B. 120 volts C. 300 volts D. 600 volts

QuestionAnswerReferenceNEC PG. # 2.C

O 3. An emergency system is required to have NO more than ______ to have power available in the event of failure of the normal electrical supply system. A. 10 seconds B. 15 seconds C. 45 seconds D. 5 minutes

QuestionAnswerReferenceNEC PG. # 3.A

O 4. X-ray equipment installed in a hospital may be served by a hard service cord with a suitable plug provided the branch-circuit rating does NOT exceed _______. A. 15 amperes B. 20 amperes C. 30 amperes D. 50 amperes

QuestionAnswerReferenceNEC PG. # 4.C517.71(A), Ex.455

O 5. Conductors supplying more than one (1) motor shall have an ampacity of NOT less than _____ of the full-load current rating of the largest motor in the group and 100% of the full-load current ratings of all the other motors in the group. A. 125 percent B. 110 percent C. 150 percent D. 175 percent

QuestionAnswerReferenceNEC PG. # 5.A430.24(1)&(2)318

O 6. Given: A straight pull of size 4 AWG and larger conductors is to be made in a junction box that will have 3 in. conduit and two (2) 2 in. conduits entering on the same side and exiting on the opposite wall. No splices will be contained in the box. Which of the following listed junction boxes is the MINIMUM required for this installation? A. 18 in. x 12 in. B. 20 in. x 18 in. C. 24 in. x 24 in. D. 30 in. x 30 in.

QuestionAnswerReferenceNEC PG. # 6.C314.28(A)(1)183 3in. (largest conduit) x 8 = 24 in.

O 7. Given” A recreational vehicle campground has one hundred-fifty (150) campsites provided with electrical power. Twenty-five (25) of the campsites are reserved as tent sites. How many of the sites are required to have a 20-ampere, 125-volt receptacle? A. 105 B. 125 C. 150 D. None

QuestionAnswerReferenceNEC PG. # 7.C

O 8. Determine the MAXIMUM overcurrent protection permitted for size 14 AWG THWN copper motor control-circuit conductors tapped from the load side of a motor overcurrent protection device. Given: The conductors require short-circuit protection and do not extend beyond the motor control equipment enclosure. A. 20 amperes B. 25 amperes C. 30 amperes D. 100 amperes

QuestionAnswerReferenceNEC PG. # 8.DTbl (B)327

O 9. Where size 6 AWG THWN copper branch- circuit conductors supply a 240-volt, single- phase, 5,000 VA non-motor operated appliance, the MAXIMUM standard size circuit breaker permitted for overcurrent protection on this circuit is rated _______. A. 55 amperes B. 40 amperes C. 35 amperes D. 30 amperes

QuestionAnswerReferenceNEC PG. # 9.C422.11(E)(3)291 Single – phase current formula 240.6(A)91 I = Power I = 5,000 VA = 20.8 amperes x 150% = 31.2 amperes Volts Volts *NOTE – The next standard size circuit breaker with a rating of 35 amperes should be selected

O 10. The ampacity of size 1/0 AWG THWN/THHN, dual-rated copper conductors enclosed in rigid metal conduit (RMC) when installed underground in direct contact with the earth is _______. A. 170 amperes B. 125 amperes C. 130 amperes D. 150 amperes

QuestionAnswerReferenceNEC PG. # 10.D300.5(B)137 Tbl (A)169 Tbl (B)(16)

O 11. Every electrified truck parking space intended to provide an electrical supply for transport refrigerated units shall be equipped with a _______. O I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire receptacle O II. 60 ampere, 280-volt, 3-phase, 3-pole, 4-wire receptacle A. I only B. II only C. Either I or II D. Both I and II

QuestionAnswerReferenceNEC PG. # 11.C626.31(C(551

O 12. Flexible cord is permitted to be connected to fluorescent luminaires where the cord ___________. A. Has an ampacity of at least 20 amperes B. Is visible its entire length C. Is at least a size 12 AWG D. Runs through holes in walls

QuestionAnswerReferenceNEC PG. # 12.B410.62(C)(1)(2)a.284

O 13. An outdoor motor fuel gasoline dispensing pump is considered to be a Class I, Div. 2 hazardous location up to _____ above grade level within _____ horizontally from any edge of the motor fuel pump enclosure. A. 18 inches – 10 feet B. 24 inches – 20 feet C. 24 inches – 10 feet D. 18 inches – 30 feet

QuestionAnswerReferenceNEC PG. # 13.ATbl (B)(1)426

O 14. Determine the MAXIMUM permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 15 hp, 208-volt, three-phase, squirrel cage, Design B, continuous-duty ac motor. Assume the rating you select will be sufficient for the starting current of the motor and exceptions need not be applied. A amperes B amperes C amperes D amperes

QuestionAnswerReferenceNEC PG. # 14.C430.6(A)(1)311 Tbl (C)(1)322 Tbl FLC of motor – 46.2 amperes x 250% = amperes

O 15. What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. PVC conduit? A. 10 feet B. 8 feet C. 6 feet D. 5 feet

QuestionAnswerReferenceNEC PG. # 15.DTbl

O 16. Unless approved for a higher voltage, surface nonmetallic raceways are NOT permitted where the voltage is _______ or more between conductors. A. 120 volts B. 150 volts C. 300 volts D. 277 volts

QuestionAnswerReferenceNEC PG. # 16.C388.12(3)237

O 17. Determine the MAXIMUM size overload protection required for a 480-volt, 3-phase, 15 hp, continuous-duty ac motor, where given the following related information. Assume the value you select will permit the overload device to carry the motor load and modification of this value is not required.  Design C  Temperature rise – 40° C  Service factor – 1.12  Nameplate ampere rating – 18 amperes A amperesC amperes B amperesD amperes

QuestionAnswerReferenceNEC PG. # 17.A430.6(A)(2) (A)(1)319 FLA = 18 amperes x 115% = 20.7 amperes

O 18. Any pipe or duct system foreign to the electrical installation must not enter a transformer vault? Which of the following listed is NOT considered foreign to the vault? A. A roof drain B. A building water main C. An air duct passing through the vault D. An automatic fire protection water sprinkler

QuestionAnswerReferenceNEC PG. # 18. D

O 19. Given: A 50 kVA transformer with a 480- volt, 3-phase, primary and a 208Y/120 volt, 3-phase secondary is to be installed. Overcurrent protection is required on both primary and secondary side of the transformer. Determine the MAXIMUM size overcurrent protection device permitted on the primary side. A. 125 amperes B. 150 amperes C. 175 amperes D. 200 amperes

QuestionAnswerReferenceNEC PG. # 19.B450.3(B)348 Tbl (B) (A(91 3 – phase current formula I = kVA x 1000 I = 50 x 1000 = 50,000 = 60.2 amperes E x volts x amperes x 250% = amperes *NOTE – A 150 ampere OCP device is required

O 20. An inverse time circuit breaker used as the disconnecting means for a 50 hp, 480- volt, three-phase continuous-duty, induction- type type ac motor shall have an ampere rating of at LEAST ________. A. 82 amperes B. 75 amperes C. 163 amperes D. 98 amperes

QuestionAnswerReferenceNEC PG. # 20.B430.6(A)(1)311 Tbl (A)332 FLC of motor = 65 amperes x amperes

O 21. Circuit breakers are NOT rated to carry 100 percent of the continuous load continuously, unless they have a rating for at LEAST _________. A. 100 amperes B. 200 amperes C. 400 amperes D. 600 amperes

QuestionAnswerReferenceNEC PG. # 21.DTrade Knowledge

O 22. A fifteen (15) ft. horizontal run of rigid metal conduit (RMC) is to be installed between two enclosures located in a Class II, Division 1 hazardous location. One enclosure is dust ignition proof, the other is not. The NEC® requires a MINIMUM of _______ sealing fittings. A. None required B. One C. Two D. Three

QuestionAnswerReferenceNEC PG. # 22.A502.15(2)387

O 32. Where fuses are used for motor overload protection, if the supply system is a 3-wire, 3-phase, ac with one conductor grounded, the NEC® requires a MINIMUM of how many fuses? A. None required B. One C. Two D. Three

QuestionAnswerReferenceNEC PG. # 23.D

O 24. Conductors leading to a gasoline motor fuel dispensing pump shall be _________. A. Provided with a switch B. Red in color C. Orange in color D. Insulated with MTW insulation

QuestionAnswerReferenceNEC PG. # 24.A514.11(A)428

O 25. In general, direct-buried cables of 13,000 volts must be buried at a depth of NOT less than ______. A. 24 inches B. 30 inches C. 36 inches D. 42 inches

QuestionAnswerReferenceNEC PG. # 25.BTbl , Col. 1146