PSU Building Thermal and Mechanical Systems Laboratory Environment A/E Kurt M. Shank, M.S. & Stanley A. Mumma, Ph.D., P.E. College of Engineering Department.

Slides:



Advertisements
Similar presentations
100% Outside Air and Dehumidification Management
Advertisements

DOUG BOSWELL MECHANICAL OPTION APRIL 16, 2008 Temple University Tyler School of Art.
1 Stanley A. Mumma, Ph.D., P.E. Prof. Emeritus, Architectural Engineering Penn State University, Univ. Park, PA Web:
Components of HVAC System
Chilled Beam Presentation
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY. “Air conditioning is the control of the humidity of air by either increasing or decreasing its moisture content.
STEM Center Delaware County Community College – Media, PA Thesis Final Presentation Dan Saxton Mechanical Option.
Stanley A. Mumma, Ph.D., P.E. Prof. Emeritus, Architectural Engineering PSU, Univ. Park, PA Web: Chilled Surfaces:
1 Condensation Control Experiences in an “historic” Building with Movable Sash ASHRAE Anaheim Seminar 53, 1/28/04 Stanley A. Mumma, Ph.D., P.E. Professor,
Ceiling Radiant Cooling Panels as a Viable Distributed Parallel Sensible Cooling Technology Christopher L. Conroy, E.I.T. L. D. Astorino Companies, Pittsburgh.
1 Meeting ASHRAE Fundamentals, Standard 55 & 62.1 with Chilled Beams Displacement Ventilation.
1 Decoupling the Building Latent and Sensible Loads Using 100% Outside Air Systems ASHRAE Chicago Seminar 39 January 24, 2006 Stanley A. Mumma, Ph.D.,
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
AIR CONDITIONING SYSTEMS 1. All Air Systems An all-Air System is defined as a system providing complete sensible and latent cooling capacity in the cold.
Field Experience Controlling a Dedicated Outdoor Air System (DOAS)
Web Based BACnet Compatible Controls Applied to Emerging HVAC Technologies Stanley A. Mumma, Ph.D., P.E. Prof. Architectural Engineering Penn State University.
Building Systems Integration - Energy and Cost Analysis The Milton Hershey School New Supply Center Justin Bem AE Senior Thesis – Spring 2007 Mechanical.
 Install new air cooled high efficiency screw chiller (variable speed)  Install new fan coils with ECM motors and low temperature heating coils and proper.
Objectives Discuss Project Topics Learn to design VAV and DOAS System.
1 Stanley A. Mumma, Ph.D., P.E. Professor Emeritus Penn State Univ. Park, PA Web: Active and Passive.
Conditioning of Moist Air
Best Practices in HVAC Design/Retrofit
Ductless Heat Pumps Sizing Example
Presentation Outline Introduction System Optimization Analysis Acoustical Breadth Conclusion Acknowledgements Questions Thesis Final Presentation Army.
Ductwork Systems and Supply Arch 432. What You Need To Know Become familiar with the materials sizing ductwork Understand sizing units.
Lecture Objectives: Specify Exam Time Finish with HVAC systems –HW3 Introduce Projects 1 & 2 –eQUEST –other options.
Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E.
HVACR416 - Design Heat Loss / Heat Gain Part 1. Why? The primary function of Air Conditioning is to maintain conditions that are… o Conductive to human.
Application and Design for The Charles E. and Mary Parente Life Sciences Building Kings College Wilkes-Barre PA Ryan James Wanko Building Mechanical and.
1 Stanley A. Mumma, Ph.D., P.E. Prof. Emeritus, Architectural Engineering Penn State University, Univ. Park, PA Web:
Spring 2007 Senior Thesis Justin D. Schultz Mechanical Option The Hauptman-Woodward Medical Research Institute Dedicated Outdoor Air Applications at the.
University of Maryland’s Gossett Field House College Park, MD Jason Borowski Architectural Engineering Mechanical Option Pennsylvania State University.
2003 ASHRAE Annual Meeting Kansas City Energy Conservation Benefits of a DOAS with Parallel Sensible Cooling by Ceiling Radiant Panels Jae-Weon Jeong Stanley.
1 Stanley A. Mumma, Ph.D., P.E. Prof. Emeritus, Architectural Engineering Penn State University, Univ. Park, PA 2014 Conference Presentation.
1 Stanley A. Mumma, Ph.D., P.E. Prof. Emeritus, Architectural Engineering Penn State University, Univ. Park, PA Web:
Greenbriar East Elementary School Fairfax, Virginia Michelle L. Siano Mechanical Option Spring 2005 Senior Thesis.
Straumann USA 60 Minuteman Road Andover, MA Kevin Kaufman Mechanical Option The Pennsylvania State University Architectural Engineering.
Achieving Dry Outside Air in an Energy-Efficient Manner PSU Building Thermal and Mechanical Systems Laboratory Environment A/E Stanley A. Mumma, Ph.D.,
Final Projects Grading criteria is posted on the course website Preliminary results are due Next Tuesday Final Project delivery on Monday Dec. 7 th –Final.
Building Systems Integration - Energy and Cost Analysis The Milton Hershey School New Supply Center Justin Bem AE Senior Thesis – Spring 2007 Mechanical.
Malory J. Faust ∙ Mechanical Option ∙ Senior Thesis 2007.
Ductwork Systems and Supply Arch 432. What You Need To Know Become familiar with the materials sizing ductwork Understand sizing units.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Jesse A. Fisher Mechanical Option Spring 2005 Riverpark Corporate Center, Phase 1 Salt Lake City, Utah.
Hamot Women’s Hospital Erie, PA Michael Galleher Mechanical Option l AE-Senior Thesis l April 12, 2011 l Advisor Dr. Jelena Srebric.
ASHRAE Tech. Paper, Long Beach, CA. June 26,2007 Poster Session Presentation: Poster contents. Jae-Weon Jeong, PhD Assistant Professor. Texas A&M University-Kingsville.
Application of Ceiling Radiant Cooling in a University Environment ASHRAE Chicago Seminar 7, 1/26/03 Stanley A. Mumma, Ph.D., P.E. Professor, Architectural.
Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado 123 Alpha Drive Pittsburgh, Pennsylvania
Objectives Propose residential system related final project –Compare VAV systems with DOAS systems.
All content in this presentation is protected – © 2008 American Power Conversion Corporation Row Cooling.
Michael Reilly, Jr. – Mechanical Option Advisor – James Freihaut, PhD & Dustin Eplee The Pennsylvania State University Nassau Community College Life Sciences.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
ENVIROCENTER PHASE II JESSUP, MD
Pros and Cons of operating a DOAS EW continuously
Doug Jefferson, Business Development Engineer
David Anderson Mechanical Option
Grunenwald Science and Technology Building
HVAC Basics Arkan Arzesh HVAC – Heating, Ventilation, Air-conditioning.
Munters DOAS, Chilled Beams and VRV
Energy Efficiency in District Coiling System
Chilled Beam Performance:
Cheryl Hughes Regional Sales Manager October 6, 2015
Feasibility of Ice Storage
HCB 3-Chap 19A: All-Air Systems_Single Zone
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Professor of Architectural Engineering College of Engineering
Objectives Finish with Heat exchangers
Presentation transcript:

PSU Building Thermal and Mechanical Systems Laboratory Environment A/E Kurt M. Shank, M.S. & Stanley A. Mumma, Ph.D., P.E. College of Engineering Department of Arch. Engineering Penn State University Park, PA Selecting the Supply Air Conditions for a Dedicated OA System Working in Parallel with Distributed Sen. Cooling Equip.

Presentation Outline l Objective l Present 3 hypotheses, regarding SAT, SA- DPT, and Terminal Reheat l Load, Energy, and Cost impact of SAT l Load, Energy, and Cost impact of SA-DPT l Terminal Reheat and SAT l Conclusions and Recommendations

Objective l Challenge the current practice of supplying air from dedicated OA systems at a neutral temperature (~70F). l Develop a methodology for selecting the proper supply air conditions.

Hypothesis 1: Load, Energy, & Cost will decrease with DBT LCC 44F70F PW, 1st & Op $ PW, Op $ 1st $

System Wide Impact of DBT on Load, Energy, and Cost l Assumptions –Atlanta, GA data; 12 hr/day, 6 day/wk. –10,000 scfm of OA –Supply air DPT, 44F –20 scfm of OA/person –Resulting space DPT, 52F –Space condition, 78F, 40% RH –No terminal reheat required, i.e. space not overcooled with ventilation air (relaxed later)

System Wide Impact of DBT on Load, Energy, and Cost l Assumptions, Continued –Constant design sensible load, split between the DOAS and the parallel system; i.e. reduce SAT (greater sensible cooling done) and reduce the load on the parallel system (there- fore size). –Fan Coil first cost, $6/cfm –Ceiling Radiant Panel cost, $8/sq. ft. –Sensible Wheel in DOAS, $2/scfm OA Building Load DOAS Parallel

Load Mix with 10,000 scfm OA in Atlanta.

Reason Peak Load Increased with Increasing SAT l Because of less than 100% effectiveness at the enthalpy wheel, only about 80% of the sensible cooling done on the return air (state 5-6) by the supply air (state 3-4) is able to be recovered by the enthalpy wheel (state 6-2). Consequently, the more reheat, the greater the cooling required when the parallel system is considered. Illustrated on the next slide.

Reason Peak Load Increased with Increasing SAT, illustrated 6 5 6’ 1 2 2’ Path from 6-6’ is the increase in reheat, and the path 2-2’ is the reduction in coil load. Since it is shorter than 6-6’, the cooling coil load is not reduced as much as the cooling capability of the supply air when reheated.

Energy Mix with 10,000 scfm OA in Atlanta, 3744 hours

Parallel system 1st cost reduction with SAT Hypothesis 1 confirmed, low SAT best

Hypothesis 2, Load, Energy, & Cost will decrease with DPT l Assumptions: –Atlanta, GA data, 12 hr/day, 6 day/wk. –10,000 scfm OA –Building Sensible Load, 75 Tons (representative of a 60,000 sq ft building, served by an all air system with a design supply air flow rate of 0.6 scfm/sq.ft. at 55F)

System Wide Impact of DPT on Load, Energy, and Cost l Assumptions, continued: –Allowable space RH range, 40-60% for acceptable IAQ. (Sterling and Sterling) –Chiller capacity drops 10% when the chilled water temp. drops from 45 to 40F. –Chiller kW/ton increases by 10% when the chilled water temp. drops from 45 to 40F. –Chiller 45F CHWT: 0.79

System Wide Impact of DPT on Load, Energy, and Cost l Assumptions, continued: –Fan Coil and CRCP performance as below Key: CRCP, Btu/hr per ft 2 FCU, Btu/hr per cfm F 65 HT CHWT

System Wide Impact of DPT on Load, Energy, and Cost l Assumptions, continued: –FCU fan efficiency, 74% and 2”TP –FCU & CRCP pumps, 80% eff., water temp rise 5F, and pressure drop 30 ft water. –Chiller installed 1st cost, $1000/ton –Energy costs, $0.09/kWh

System Wide Impact of DPT on 1st and energy Costs Hypothesis 2 confirmed, low SA-DPT best

Hypothesis 3, Terminal Reheat will be needed sparingly if at all l Issues: –Terminal Reheat is permitted where it is required to meet Std. 62--Which is why so many all air VAV systems use terminal reheat –VAV box minimums are set to meet the ventilation requirements. The minimum setting will always be at or above that required by the DOAS system since “ z c “ in Eq. 6.1 will always be less than or equal to 1.

Hypothesis 3: Terminal Reheat l Issues continued: –If “ z c “ = 0.4 and a space needs 200 scfm of OA, then the box minimum must be 500 scfm. “ z c “ for a dedicated OA system is always 1, so it will deliver the 200 scfm. –A room served by a VAV box with a minimum setting of 500 scfm at 55F is prone to overcool the space sooner than the dedicated OA system supplying 200 scfm of air at either 55 or 44F. (500*[78-55] >200*[78-44]) or (11,500>6,800)

Overcooling potential with the DOAS l Assumptions: –Envelope UA, 0.09 Btu/hr-F/ft 2 of floor area –Summer OA, 90F –Winter OA, 20F –Ventilation, 15 or 20 scfm/person –Occupancy Density, 0-90/1000 ft 2 –Internal generation, Lights, equipment; 0-15 W/ft 2

Overcooling with the DOAS, the energy balance/person Q env OA, scfm 44-55F IG/ft 2 Floor area /person Balance Point IG/ft 2 =Q DOAS / ft 2 + Q env / ft 2 -Q sen / ft 2

Overcooling with the DOAS Graphic from the energy bal. IG, W/ft Occupancy/1000 ft Winter Summer 20 4 Example: 20 people per 1000 ft 2, 4 W/ft 2, If the IG less than 4 W/ft 2 with an occupancy density of 20, the DOAS will overcool; if more, need parallel cooling.

Conclusion: l The 3 hypothesis verified l For many building applications, terminal reheat is seldom if ever needed with 55F or even 44F SAT from the DOAS. l Old Paradigm of supplying the air at a neutral temperature, in dedicated OA applications, should be abandoned.

Recommendation l The supply air DPT should be low enough to maintain the space RH no higher than 40%, about 44F in many cases. l The supply air dry bulb temperature should be at 55F or below. l Where Occupancy densities are very high, and terminal reheat is frequently required, use recovered heat.