A.Klepper2 LAN (RJ45) BMS with BACnet-Technology PC workplace with CGVision LAN (RJ45) Visualisation of BACnet objects (event orientated) IP-Router Config-server ZB-S CG-S Bus / FTT10A ZB-S or CG2000 Systems ZB-S IP-Router Client 1 ZB-S CG-S Bus / FTT10A ZB-S or CG2000 Systems ZB-S TCP/IP connection – CGVision via CG-S/IP-Router BACnet/IP – BMS on CGVision BMS has access to the BACnet Server ! Visualisation of BACnet Objects Schema: BACnet-connection via OPC-Client/BACnet Server OPC-Client SNVT BACnet Server BACnet Objects Ethernet BACnet /IP TCP/IP CG2000
A.Klepper3 BACnet status informations 22 pcs. Status informations each device (ZB-S / CG2000) 1) Device in normal operation 2) Sum failure with luminaire failure 3) Sum failure without luminaire failure 4) Communication error CG-S bus 5) Device in battery mode 6) Battery duration test is activ 7) Device is blocked 8) Bettery failure (e.g. interruption) 9) Sum failure in a circuit (e.g.:fuse) 10) Mains failure (sum) 11)Deep discharge protection is activ 12)Interruption of the battery circuit 13)Charging failure battery 14)Isolation failure battery, battery + or – against protection earth 15)Rated duration test time not reached 16)General luminaire failure 17)Functionstest is activ 18)Battery voltage to high 19)Charging unit failure 20)Charging booster failure 21)Mains failure - device 22)Mains failure – sub distribution board
A.Klepper4 BACnet analogue datas and switch commandos 4 pcs. Analogue values each device 1) Battery current (Charging- discharging current) 2) Battery voltage 3) Battery temperature 4) Battery capacity 16 (ZB-S) or 30 (CG2000) pcs. switch commandos each device 1)LON-Switch 1 2)LON-Switch 2 … 16)LON-Switch 16 (ZB-S) ….. 30)LON-Switch 30 (only CG2000) 3 pcs. status informations e. device (mirror of relay outputs) 1)Emergency operation 2)Normal operation 3)Sum failure 6 pcs. control comandos each device 1)Block device 2)Release device 3)Start functiontest 4)Start battery duration test 5)Stop battery duration test 6)Quit deep discharge protection
A.Klepper5 Example of status informations via BACnet Screenshot of a BACnet OPC-Server:
A.Klepper6 Example of switch commandos via BACnet Screenshot of a BACnet OPC-Server: