Fire, Thermal & Acoustic Insulation
New European Resistance To Fire Standards
Introduction Brief introduction to CEN Brief introduction to reaction to fire standards Resistance to fire standards Examples of fire tested systems
Background The European Union is promoting a free flow of goods within the Union The free flow of goods was limited due to technical barriers between the national member states Harmonize standards within the European Union to enable a free flow of construction products ‘Real fire experience' should be the basis for adopting new fire tests
Background
UK Fire Statistics 2002 – 623 attributed deaths in 1999 Historically, UK has not required limits in smoke generation from building products Between 1987 –97, a 100% increase occurred in those effected by gas or smoke
CEN European Committee for Standardisation CEN, the European Committee for Standardization, was founded in 1961 by the national standards bodies in the European Economic Community: 28 National Members and their respective experts vote for and implement European Standards 8 Associate Members and two Counsellors CEN Management Centre, Brussels
CEN Membership Austria Belgium Cyprus Czech Republic Denmark Estonia Finland France Germany Greece Hungary Iceland Ireland Italy Latvia Lithuania Luxembourg Malta The Netherlands Norway Poland Portugal Slovakia Slovenia Spain Sweden Switzerland United Kingdom
Construction Product Directive The European Commission gives mandates to CEN The commission issues mandates in accordance with the Construction Product Directive, in order to ensure that the standards fulfil the essential requirement
Essential Requirements In CPD Mechanical resistance and stability Safety in case of fire Hygiene, health and the environment Safety in use Protection against noise Energy economy and heat retention
Safety In Case Of Fire the load-bearing capacity of the construction can be maintained for a specific period of time the generation and spread of fire and smoke within the works are limited the spread of the fire to neighbouring construction works is limited occupants can leave the works or be rescued by other means the safety of rescue teams is taken into consideration Construction works must be designed and built in such a way that in the event of an outbreak of fire:
CEN TC 127 CEN is organised in Technical Committees TC127 is responsible for the development and maintenance of the standards for fire safety in buildings CEN TC127 is organised into working groups taking care of specific items The working groups have members from laboratories, industry and authorities
New EN Fire Testing Standards CEN TC 127 has compiled a set of harmonised fire testing and classification standards which enables the industry to fulfil the second essential requirement The work is still in progress and new standards will be produced The EN standards will be reviewed every 5 year
New EN Fire Testing Standards The new standards are prepared using existing national and ISO standards in accordance with the Vienna Agreement
Old National Fire Testing Standards Old national standards such as BS, DIN, AFNOR etc. will be withdrawn after a transition period, when an EN standard is issued, the existing standards will no longer be maintained or be valid for use
Reaction To Fire / Resistance To Fire
Reaction To Fire Short introduction
Reaction To Fire As part of the new EN standard system, a new reaction to fire classification and testing system has been developed This new system replaces the existing 28 national systems
Reaction To Fire In order to be able to classify a building product with respect to reaction to fire a set of test shall be done: Non- combustibility test EN ISO 1182 Calorific potential EN ISO 1716 SBI (single burning Item) EN Small scale Flame EN 11925
Reaction To Fire
After testing a construction product classification is made in accordance with EN
Class A1 and Class A2
Class B to Class F
Resistance To Fire
Resistance To Fire Basic Standards EN Fire resistance tests - Part 1: General requirements EN Fire resistance tests - Part 2: Alternative and additional procedures These standards describe the basic requirements to fire testing
EN This standard is replacing ISO 834 as basic for fire tests The major difference between ISO 834 and EN are: –Thermocouples for furnace control –Pressure in furnace –The use of rowing thermocouples –The use of gap gauges
Thermocouples For Furnace Control Plate thermocouple
Consequences Of The New Plate Thermocouples For Furnace Control The large exposed surface of the plate thermocouple makes it more sensitive to radiation than a conventional TC This compensates for the differences in the thermal characteristics of the furnaces
This graph shows a test controlled by a plate thermocouple The temperatures measured by a conventional TC are higher therefore the test is less severe The graph is produced by DIFT Consequences Of The New Plate Thermocouples For Furnace Control
The fire exposure in tests according to EN is more severe and give a higher degree of fire safety Every European fire test laboratory will produce a uniform result
The required pressure in the furnace is increased to 20 Pa 100 mm from the top of the sample and a negative 20 Pa 100mm above the furnace base of a horizontal sample The neutral plane has consequently been moved to a lower point bbb P Consequences Of The New Plate Thermocouples For Furnace Control
Constructions sensitive to leakages in joints will have more severe conditions The integrity criteria will fail earlier due to the higher pressure, as hot gases will be will be pressed out through any small leakages Consequences Of The New Plate Thermocouples For Furnace Control
Roving Thermocouple In addition to the fixed thermocouples on the unexposed surface of the sample a roving thermocouple can be used to determine hot spots on the unexposed surface Hot spots can now be detected even if they are far away from fixed thermocouples
Integrity Failure Gap gauges of 6mm or 25mm wide are used where cracks form between elements in the sample, in conjunction with cotton pads to determine whether integrity failure has occurred
EN This standard describes alternative and additional procedures to EN –HC curve –External exposure curve –Slow heating curve –Measurement of radiation (glazed constructions) –Impact exposure (sand bag and steel ball)
EN HC Normal External Slow
Specific Resistance To Fire Standards EN 1364 Fire resistance tests for non- load bearing elements –Part 1: Walls –Part 2: Ceilings –prEN 1364 Part 3 Curtain Wall (full configuration)
EN 1365 Fire resistance tests for load bearing elements –Part 1: Walls –Part 2: Floors and Roofs –Part 3: Beams –Part 4: Columns –Part 5: Balconies and Walkways –Part 6: Stairs Specific Resistance To Fire Standards
EN 1366 Fire resistance tests for service installations –Part 1: Ducts (ventilation ducts) –Part 2: Fire dampers –Part 3: Penetration seals –prEN 1366 part 4 Part 4: Linear joint seals –Part 5: Service ducts and shafts –Part 6: Raised access and hollow core floors –Part 7: Conveyor systems and their closures –Part 8: Smoke extraction ducts –PrEN 1366 Part 9 Single compartment smoke extraction ducts –PrEN 1366 Part 10: Smoke control dampers
EN 1634 Fire resistance tests for door and shutter assemblies –Part 1: Fire doors and shutters –Part 3: Smoke control doors and shutters Specific Resistance To Fire Standards
ENV Test methods for determining the contribution to the fire resistance of structural members –Part 2: Vertical protective membranes –Part 3: Applied protection to concrete members –Part 4: Applied protection to steel members –Part 5: Applied protection to concrete/profiled sheet steel composite members –Part 6: Applied protection to concrete filled hollow steel columns –Part 7: Applied protection to timber members Specific Resistance To Fire Standards
All standards have a clear description of direct field of application of a test result All standards will be followed up with a EXtended field of APplication standard (EXAP), which gives rules for the extension of the field of application The EXAP standard will reduce the need for Engineering assessments, and give uniform evaluation criteria Specific Resistance To Fire Standards
Almost every part of the construction and services industry are covered by its own standard The large number of standards minimize the need for ad-hoc testing of specific constructions Specific Resistance To Fire Standards
Classification Of Fire Resisting Constructions After a successful fire test the construction can be classified in accordance with one of the following standards
Classification Of Fire Resisting Constructions EN consists of the following parts: –Part 1: Classification using data from reaction to fire tests –Part 2: Classification using data from fire resistance tests, excluding ventilation services –Part 3: Classification using data from fire resistance tests on components of normal building service installations –Part 4: Classification using data from fire resistance tests on components of smoke control systems
Classification Of Fire Resisting Constructions R - Mechanical resistance –limiting deformation –limiting rate of deformation E - Integrity –ignition of cotton pad –cracks and openings –occurrence of sustained flaming on the unexposed side I - Insulation –average temperature rise –maximum temperature rise
W - Radiation –maximum radiation level S - Smoke leakage –limiting leakage rate M - Mechanical action –resistance to impact C - Self-closing –self closure in the event of fire Classification Of Fire Resisting Constructions
Classification Of Load Bearing Walls With Fire Separating Function
Classification Of Load Bearing Floors And Roofs With Fire Separating Function
EN 1364 Resistance Tests For Non-Load Bearing Elements Part 1: Walls Fixing to three sides of the frame: A free edge giving the wall assembly a three dimensional deflection as in practice This gives a more severe condition than if the wall only was fixed to two sides which only gives a two dimensional deflection
EN 1364 Resistance Tests For Non- Load Bearing Elements Part 1: Walls
Ceilings prENV or EN Suspended ceilings can be handled in two different configurations. Deck Suspended ceiling prENV EN
Ducts EN Ventilation ducts are required to be tested for fire inside, outside, horizontal and vertical a total of 4 tests to obtain a full classification If ventilation ducts are to be used for smoke and heat extraction further testing is necessary
Ducts EN
Example Duct A Horizontal
New European Resistance To Fire Standards Summary