TESTING AND COMMISIONING

Slides:



Advertisements
Similar presentations
Engine Cooling And Lubrication
Advertisements

Chapter 12 Transformers. Chapter 12 Transformers.
Presentation : IMS – Tech Managers ConferenceAuthor : IMS StaffCreation date : 08 March 2012Classification : D3Conservation :Page : ‹#› 07 - TransformersAuthor.
Thermostats, Pressure Switches, and Other Electric Control Devices
Setup/Installation/Operation of an Environmental Control Unit (ECU)
Wine Cellar Split System Basics. Definitions Split System – A cooling unit that “splits” the cooling coil and the condenser apart into two remote pieces.
Objective of the session.
TESTING, MAINTENANCE & PROTECTION OF DISTRIBUTION TRANSFORMERS
Cooling As working temperatures rise, the strength of metals used reduces. This in turn will force manufacturers to use superior metals/alloys, which can.
GENERATOR PROTECTION.
Introduction to Hydraulics ClassAct SRS enabled. In this presentation you will: identify the fundamental parts of a hydraulic system and safety issues.
Review of 1- AC Circuit Fundamentals
Announcements Be reading Chapter 3
Unit Transformer Unit transformer are step up transformer which is connected to generating house & step up voltage from 15kV voltage to 132 voltage level.
Transformer.
Electrical Machines LSEGG216A 9080V. Transformer.
REFRIGERATION SYSTEMS
Hydronic Mechanical Controls
Chapter 2 Transformers.
Electrical Machines LSEGG216A 9080V. Transformer Losses & Efficiency Week 3.
Air-Source Heat Pumps I North Seattle Community College HVAC Program Instructor – Mark T. Weber, M.Ed. Airsource Heat Pump 1.
1 Combustion Oil Fired Equipment. 2 OIL Combustion of oil fired equipment has the same basics of gas. Remember, Oil is a liquid and this must be converted.
NFPA 31 Standard for the installation of Oil- Burning Equipment
Transformer.
Batteries The purpose of the battery is to act as a reservoir for storing electricity.
POWER SYSTEM PROTECTION
Circuit breakers The main purpose of a circuit breaker is to: Switch load currents Make onto a fault Break normal and fault currents Carry fault current.
Transformer Taking the ratio of the two equations
Connections of a CT and a PT to supply, load and relay.
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Welcome to my Presentation On Transformer. Presented By Emon Arifin Shakil ID#
Introduction to switchgears
SEMINAR PRESENTATION ON 220 KV GSS UDAIPUR
ON 400 KV GSS RAISER JAIPUR ROAD ,BIKANER
Transformer Current & Voltage Practice
Lecture 09Electro Mechanical System1 Chapter 11 Special Transformers.
PRESENTED BY Gupta.Deepakkumar.R ( ) Condition Monitoring of Transformer (The heart of Power System)
HIMACHAL PRADESH STATE ELECTRICITY BOARD LTD.
Protection of Power Systems
Refrigeration Systems
HASMUKH GOSWAMI COLLEGE OF ENGINEERING
7 A/C System Components, Operation, and Service.
AIR CONDITIONING (COOLING)
Transformer vaishnav gaurav yadav shalu
REFRIGERATION SYSTEMS Er. Gagandeep kaur Associate Prof., Electrical Engg. PTU Giani Zail Singh Campus, Bathinda. Id:
DC Machine & Transformer
Outage of Generator Transformer due to High DGA. BRIEF HISTORY 200 MVA 400 kV GT erected at site. After satisfactory pre-commissioning checks GT was successfully.
Md.Hamidul Haque ID: Prog:BSEEE SEC:E/3 International University of Business Agriculture and Technology (IUBAT )
PREPARED BY, ENROLLMENT NO: CLASS: 3 RD E&C Transformer 1 3-Ø Transformer Hansaba College of Engineering & Technology, Sidhpur.
Transformers. Single Phase Transformers Principles of Operation – Single Phase.
ET 332b Ac Motors, Generators and Power Systems 1 Lesson 11_et332b.pptx.
HNC/D Engineering Science
TESTING AND MAINTENANCE OF POWER TRANSFORMER
Automotive Heating And Air Conditioning
CHAPTER 4 SINGLE-PHASE TRANSFORMER
Testing of Transformers
Per-Unit System.
A presentation on Measurement of Winding Resistance and Insulation Resistance of 3 Phase 11 kV/ 433 V, 16KVA Oil cooled type Transformer PRESENTED BY:
Electrical Machine-I EE 2107 Dr. Md. Sherajul Islam
المحولات Transformers
Lesson 11: Transformer Name Plate Data and Connections
3-Phase Transformer Construction, Principal, Working, Operation Advantages Over 1-Phase Transformer Introduction Advatages Construction Principal Working.
Calculations: Transformers and Service Conductor Calculations
Electrical Machines LSEGG216A 9080V.
Remarks: New AC Pressure Test, IEC 60298: For switchgear, which are 80% of values detailed of IEC (TABLE 3.7). 2) Reduced Value AC Pressure Test,
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
Presentation transcript:

TESTING AND COMMISIONING DET310 CHAPTER 4 THE POWER TRANSFORMER THE POWER TRANSFORMER

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 3.1 INTRODUCTION Substation transformers can range from the size of a garbage can to the size of a small house; they can be equipped with a wide array of gauges, bushings, and other types of auxiliary equipment. INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.2 TRANSFORMER NAME PLATE The transformer nameplate contains most of the Important information that will be needed in the field . The nameplate should never be removed from the Transformer and should always be kept clean and legible. INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 CONTINUE- SERIAL NUMBER i) WEIGHT CLASS j) DIMENSION KVA RATING k) TAP CHANGER VOLTAGE RATING WINDING VEKTOR GROUPING PERCENTAGE IMPEDANCE INSULATING FLUIDS INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.2.1 TRANSFORMER CLASS ONAN - Oil natural air natural ONAF - Oil natural air force (use fan) OFAF - Oil force air force ( use oil pump and fan) OFWF - Oil force water force (use oil pump and water cooling) ODAF – Oil force and air force Example Transformer Rating: 1000 KVA 550C ONAN, which stands for the capability to supply 1000KVA with a temperature rise of 550degres celcius with normal oil circulation (no fans or pumps). INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Hermetically sealed ONAN INSUALTION TEST OF ELECTRICAL EQUIPMENT Conservator Type OFAF Conservator Type OFAF

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.2.2 VA RATING Every transformer has a maximum output current that it can deliver at its standard output voltage. This VA rating (KVA or MVA for large power transformers) is dependent on the ambient temperature or cooling provided. Exceeding the VA rating will cause over-heating of the core and windings and subsequent damage INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Continue- The capacity of a power transformer is defined by full load power, in kVA it can produce. INSUALTION TEST OF ELECTRICAL EQUIPMENT Where S = Full load Power Uph= rated voltage at no load (V) Iph = rated output current (A) For Star Connection: I phase= Phase Voltage=

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.2.3 VOLTAGE RATING Transformer rated voltage is usually specified by the voltage ratio Example: 11/0.415kV ; Primary rated Voltage : 11kV Secondary rated Voltage: 0.415kV 4.2.4 WINDING EXAMPLE: PRIMARY : DELTA SECONDARY: STAR 4.2.5 VEKTOR GROUP The vector groups denotes denotes the way the transformers windings are connected: INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Continue: Example: Dy11 D= HV delta winding y= low voltage star winding 11=clock face (30 degrees lead) with reference to the HV 12 o’clock INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Continue: Winding falls into three main types: star, delta, and zigzag Can be categorised into four groups Group1: 0 degress phase shift: Yy0,Dd0,Dz0,Zd0 Group 2: 1800 deg phase shift: Yy6, Dd6, Zd6, Dz6 Group 3: -30 deg phase shift: Dy1, Yd1, Yz1, Zy1 Group 4: +30 deg phaseshift:Dy11,Yd11,Yz11,Zy11 INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.2.6: IMPEDANCE The impedance of transformers is express in percentage values to Enable fault level calculations to be carried out Example: 11/0.416kV Impedance: 4.75% Fault level: INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.2.7 TRANSFORMER OIL Act as an insulation and thermal transfer agent Mineral hydrocarbon oil to BS 148 Sometimes synthetic liquids, called askarels (pyroclor) are used instead of oil as they are non-inflammable and non-explosive but very expensive INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.2.8 TAP CHANGER 4.2.8 TAP CHANGER INSUALTION TEST OF ELECTRICAL EQUIPMENT Tap Changger

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 TAP CHANGER FUNCTION: ALLOWS THE NOMINAL VOLTAGE TO ADJUSTED TYPICALLY 2.5% AND 5% ABOVE AND BELOW NOMINAL VOLTAGE EXAMPLE: 11kV 5 taps Tap1: 5% below: 10.45 V Tap2: 2.5 % below 10.725 V Tap 3: Nominal Tap : 11kV Tap 4: 2.5 % above: 11.275 kV Tap 5: 5% above: 11.5kV INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.3 TRANSFORMER OIL 4.3.1 OIL DETERIORATION Oxidisation of Oil- - Oil reacts with oxygen to form a hydrocarbon sludge - The sludge is deposited on the winding tank walls - Causing heat to develop. - Sludge may also block the cooling ducts. - Oxidisation will results in formation of hydrocarbon and acid - Causing corrosion of the various metals within the transformers INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.3.2 Thermal Decomposition of Oil Heating of a Transformer will results of thermal decomposition Will lead to breakdown of oil insulation Prolonged operation above 98 deg reduces transformers life 4.3.3 Contamination Particularly from moisture which enters through transformer breather INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.4 Oil System for Large Transformer The conservator - Oil reservoir and expansion vessel - Exhaust through breathing device-usually fitted with silica gel or drycol refrigeration dryer type b) Explosion Vent - Consists of a thin and relatively weak diaphragm -Under internal fault, the excess pressure in the tanks burst into explosion vent to release the pressure - Under normal circumstances, seals the transformer from the atmosphere INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 CONSERVATOR TANK INSUALTION TEST OF ELECTRICAL EQUIPMENT BREATHER

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 RELIEVE VALVE INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.5 THE BUCHOLZ A mechanical relay connected through pipe and situated between main tank and conservator tank of a transformer. Only certain kVA transformer need to be installed with one, normally above 1MVA. It will be connected to the trip coil of the circuit breaker controlling the transformer or the installation INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Continue Principles of operation: Electrical faults cause violent generation of gases, which flows to the highest point, namely the conservator. This gases will Trapped inside the Bucholz compartment causing the level of oil to reduce thus causing the relay to initiate. INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 continue”: Buchholz relay can be triggered by three operation 1) Air from atmosphere while filling the transformer oil 2) Mechanical failure 3) Insulation breakdown from oil 4) Winding insulation breakdown Gas formed usually consists of hydrogen, Acetylene and carbon monoxide. INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Continue: If the gas only contained less then 2% carbon monoxide, only breakdown in oil occurs. 2) If the gas contained more then 20%, the fault are due to both breakdown of oil and insulation INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.6 COMMISSIONING TESTS 4.6.1 DATA COLLECTION - manufacture and date of manufacturer - serial Number - rating-normal and assisted - nominal voltages - full load current at nominal tap - percentage impedance - vektor group - tap changer type, range and no of tap INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.6.2 General check and Inspection Coordinating Gaps Labelling Earth Connections Breathers Valves in operational position Tightness of fastening Insulators undamaged and clean No oil leaks Correct oil levels in conservators INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.6.3 Insulation Tests Check Insulation between low voltage winding to earth with 1kV IR tester Check Insulation between high voltage winding to earth with 5 kV IR tester. 3. Check Insulation between HV and LV winding with 5 kV IR tester Duration of all are one minutes INSUALTION TEST OF ELECTRICAL EQUIPMENT

POWER TRANSFOMER COMMISSIONING TEST Insulation Test 1kv and 5kV: Power Transformer Hv Side Lv Side E Bacaan 100 M,ohms keatas ARB

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.6.4 Polarization Index Test. Carry out IR test between Low Voltage to Earth with 1kV IR tester Carry out IR test between HV to Earth with 5kV IR tester Carry out IR test between HV to LV with 5kV IR tester Duration of test is 10 minutes Divide the value obtained with value for 1 min test Polarization Index = R10/R1 INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Between Insulation Resistance (MΩ) PI Accepted value 1 Minute 10 Minute Primary & Earth 4000MΩ 7000MΩ 1.75 Not less than 1.2 Secondary & Earth 3500MΩ 8000MΩ 2.29 Primary & Secondary 5100MΩ 10000MΩ 2.00 INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.6.5 Ratio Test Inject 415V three phase supply to HV side of transformer with the LV side open circuited. 2)Measure the HV side and LV side voltage and calculate the ratio. Compare the ratio with the name plate value and ensure that the ratio is within the tolerance. 3)Repeat for all transformer taps. INSUALTION TEST OF ELECTRICAL EQUIPMENT

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 Primary Voltage Secondary output voltage Tap No Voltage AB: 200 BC: 200 CA: 200 an bn cn 4.32 1 11550 4.43 2 11275 4.54 3 11000 4.66 4 10725 4.78 5 10450 INSUALTION TEST OF ELECTRICAL EQUIPMENT Example: a) At tap changer no 1: VAB = 200V (Delta) Therefore the ratio is correct.

TESTING AND COMMISIONING INSUALTION TEST OF ELECTRICAL EQUIPMENT DET310 4.6.7 Impedance test: Positive sequence impedance Inject three phase supply to HV side of transformer with LV side short circuited as shown below. 2)With the transformer at nominal tap, measure and record the current and voltage at HV side. 3) Calculate the percentage impedance as given below: % Impedance Where Vm = measured voltage Im = measured current Vr = rated voltage Ir = rated current Compare the results with declared value on the nameplate. Repeat the above for transformer at lowest and highest tap positions. INSUALTION TEST OF ELECTRICAL EQUIPMENT