Electrical Machines LSEGG216A 9080V
Transformer Losses & Efficiency Week 3
Objectives 1.Describe the power losses which occur in a transformer 2.Describe the tests which allow the power losses of a transformer to be calculated 3.Calculate transformer losses and efficiency using test results 4.Define the all day efficiency of a transformer 5.Calculate the all day efficiency of a transformer 6.Describe the relationship between transformer cooling and rating
5.Calculate the all day efficiency of a transformer 6.Describe the relationship between transformer cooling and rating 7.Describe the methods of cooling 8.List the properties of transformer oil 9.Describe the tests conducted on transformer oil Objective s
Transformer Ratings Transformers are rated to supply a given output in Volt Amps or VA at a specified frequency and terminal voltage.
They are NOT rated in Watts The load power factor is unknown
Transformer Ratings They are NOT rated in Watts The load power factor is unknown
Problem V 1 = 6,351 V V 2 = 230 V S = 2 kVA Power output at unity PF ? P = 2 kVA x 1 P = 2 kW Power = S x PF
Problem V 1 = 6,351 V V 2 = 230 V S = 2 kVA Full load secondary current at 0.8 PF ? I = A
Student Exercise 1
V 2 = 200 VV 1 = 1270 V S = 20 kVA P = 20 kW (a)Power output at unity power factor
V 2 = 200 VV 1 = 1270 V S = 20 kVA P = 16 kW (b)Power output at 0.8 power factor
V 2 = 200 VV 1 = 1270 V S = 20 kVA I = 100 A (c)Full-load secondary current at unity power factor
V 2 = 200 VV 1 = 1270 V S = 20 kVA I = 62.5 A (d)Secondary current when transformer supplies 10 kW at 0.8 power factor
Efficiency Ratio between Input power and Output Power
Efficiency Efficiency is normally expressed as a percentage
Transformer Efficiency Power In Power Out Overcome Iron Losses Overcome Copper Losses Some Power is used to: η = 100%η = 95%η = 90%
Student Exercise 2
V 1 = 230 V V 2 = 32 V S = 20 kVA η = 90%PF = 0.85 (a)Power output of transformer P = 85 W
V 1 = 230 V V 2 = 32 V S = 20 kVA η = 90%PF = 0.85 (b)Power input P = 94.4 W
V 1 = 230 V V 2 = 32 V S = 20 kVA η = 90%PF = 0.85 (c)Losses P = 9.4W
Transformer Losses Copper Losses (Cu) Varies with load current Produces H EAT Created by resistance of windings Short circuit test supplies copper losses
Short Circuit Test Copper Losses (Cu) Secondary Short Circuited Limited Supply Voltage ≈ 5-10 % Wattmeter indicates Copper Losses (Cu)
Short Circuit Test Copper Losses (Cu) Finds Cooper losses at full load Copper losses vary with the square of the load Full load C u loss = 100 W Transformer loaded at 50% P Cu = 25 W
Copper Losses (Cu) % Load Cu Losses (W)
Transformer Losses Iron Losses (F e ) Fixed Always present Related to transformers construction Eddy Currents Reduced by laminations Produces HEAT Hysteresis Reduced by using special steels in laminations
Open Circuit Test Finds Iron Losses (Fe) Full Supply Voltage Secondary Open Circuit Wattmeter indicates Iron Losses (Fe)
Transformer Efficiency Student Exercise 3
S out = 30 kVA Fe = 220 WCu FL = 840 W Calculate η%at Full Load η% = 96.6%
S out = 30 kVA Fe = 220 WCu FL = 840 W Calculate η%at 75%Load η% = 97%
S out = 30 kVA Fe = 220 WCu FL = 840 W Calculate η%at 50%Load η% = 97.21%
S out = 30 kVA Fe = 220 WCu FL = 840 W Calculate η%at 25%Load η% = 96.49%
100%η = 96.6% 75%η = 97% 50%η = 97.21% 25% η = 96.49%
% Load Losses (W) η%η% Cu Losses Fe Losses η%η% Fe = Cu =Max η
Maximum Efficiency Fe = Cu =Max η Fe = 220Cu = 840 Load %= 51.18% η%= 97.21%
All Day Efficiency Most Transformers are connected permanently The time that the transformer has to be calculated when determining efficiency Able to determine the best transformer for the application by its efficiency
All Day Efficiency Transformer A S out = 300 kVAFe = 1.25 kVACu = 3.75 kVA
All Day Efficiency Transformer B S out = 300 kVAFe = 2.5 kVACu = 2.5 kVA
Transformer Cooling Transformer ratings can be increased if their windings are cooled by some external means The most common cooling mediums are in direct with transformer windings; and/or AirOil The most common methods of circulation are Forced and/or Natural
Transformer Classification Transformers are allocated symbols which indicate the type of cooling used Can consist of up to 4 letters indicating the cooling system 1 st Letter2 nd Letter3 rd Letter4 th Letter The cooling medium in contact with the windings The cooling medium in contact with the external cooling system Kind of MediumCirculation typeKind of MediumCirculation type
Transformer Classification Type AN Dry Transformer with Natural Air Flow A ir N atural
Transformer Classification Type AF Dry Transformer with Forced Air Flow A ir F orced
Transformer Classification Type ONAN Oil Tank Cooling Natural Oil Flow - Natural Air Flow O il N atural A ir N atural
Transformer Classification Type ONAF Oil Tank Cooling Natural Oil Flow - Forced Air Flow O il N atural A ir F orced
Transformer Classification Type OFAF Oil Tank Cooling Forced Oil Flow – Forced Air Flow O il F orced A ir F orced
Transformer Oil Low Viscosity High Flash point Chemically inert Good insulator Acts as Coolant & Insulator
Transformer Oil Tests Dielectric Strength Acidity Power factor Interfacial tension Dissolved Gas
THE END