Dr M A Panneerselvam, Professor, Anna University HIGH VOLTAGE ENGINEERING FOR B.E.(EEE) STUDENTS OF ANNA UNIVERSITY Dr M A Panneerselvam, Professor, Anna University
INTRODUCTION OF THE FACULTY NAME : Dr. M.A. PANNEERSELVAM QUALIFICATION : B.E., (ELECTRICAL) M.E (HIGH VOLTAGE ENGINEERING) Ph.D (HIGH VOLTAGE AREA OF SPECIALISATION : ELECTRICAL MACHINES & HIGH VOLTAGE ENGINEERING Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University NO. OF PAPERS : ABOUT 30 IN BOTH NATIONAL PUBLISHED & INTERNATIONAL JOURNALS NO. OF Ph.D’s PRODUCED : 4 CANDIDATES WORKING FOR Ph.D. CURRENTLY : 4 Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University LIST OF REFERENCES 1. High Voltage Engineering -4 th Edition- M.S. Naidu and V.Kamaraju- Tata Mc.Graw-Hill Publishing Co. Ltd.,- New Delhi- 2009. 2. High Voltage Engineering -3 rd Edition- C.L. Wadhwa - New Age International(P) Ltd. Publishers - New Delhi, Bangalore …- 2010. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 3. High Voltage Engineering - J.R.Lucas - Sri Lanka - 2001. 4. High Voltage Engineering- Kuffel,E and Abdullah,M - Pergomon Press, Oxford-1970. 5. High Voltage Engineering Fundamentals - 2 nd Edition - Kuffel,E , Zaengl,W.S and Kuffel,J - Butterworths, London- 2000. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 6. High Voltage Measurement Techniques - Schwab,A.J - M.I.T. Press, Cambridge - 1972. 7. High voltage Technology - Alston,L.L - Oxford University Press, Oxford-1968. 8. High Voltage Laboratory Techniques- Craggs, J.D. and Meek, J.M - Butterworths, London- 1954. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 9. Indian Standards Specification on High Voltage Testing of Electrical Apparatus ( IS 1876-1961, IS 2071 Part I-1974, IS 2071 Part II-1974, IS 2071 Part III-1976, IS 2026 Part III- 1981, IS 3070 Part I-1985, IS 2516 Part II/Sec.2-1965 and IS 698 ). Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University THE SUBJECT DEALS WITH THE FOLLOWING TOPICS: 1.OVERVOLTAGES 2.BREAKDOWN IN GASES, SOLIDS , LIQUIDS AND VACUUM DIELECTRICS Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 3.GENERATION OF VERY HIGH VOLTAGES AND CURRENTS 4.MEASUREMENT OF VERY HIGH VOLTAGES AND CURRENTS 5.HIGH VOLTAGE TESTING & INSULATION COORDINATION Dr M A Panneerselvam, Professor, Anna University
UNIT 1 : OVERVOLTAGES 1.0 NATURE OF OVERVOLTAGES 1.External overvoltages / Lightning overvoltages Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 2.Internal overvoltages / Switching surges 3.Power frequency overvoltages due to system faults 4.DC overvoltages Dr M A Panneerselvam, Professor, Anna University
1.1 LIGHTNING OVERVOLTAGES Due to lightning and thunder storms overvoltages are injected onto the transmission lines. CLOUD + + + + - - - + + + + - - - - + + + + - - - - - - - - - ++++ - - - -++++ - - - - +++++ - - - +++++ DISCHARGE Dr M A Panneerselvam, Professor, Anna University TYPE - I
Dr M A Panneerselvam, Professor, Anna University DISCHARGE - - - - - - - - - - - - -- - - - - - - - - -- - - - - -- - - - - - - - - - -- - - - - - - -- - - - - - - -- - - - - - - - - - + + + + + + + + + + + + + + + + + + + + + + CLOUD CLOUD TYPE - II Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University - - - - - - - - - - - - -- - - - - - - - - -- - - - - -- - - - - - - - - - -- - - - - - - -- - - - - - - -- - - - - - - - - - + + + + + + + + + + + + + + + + + + + + + + I AMPS I AMPS / 2 / 2 / 2 / 2 +++++++++++++++++++ - - - - - - - - - - - - - - - - - - Ƶ Ƶ Ƶ Ƶ TYPE - III Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University PROPAGATION OF LIGHTNING CHANNEL Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.1.1 Voltage developed due to lightning stroke: EQUIVALENT CIRCUIT Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University For a lightning stroke current of 200 kA and assuming a surge impedance of 400 Ω for overhead line, the voltage developed is equal to( I x Z/ 2 ) = 200 x 103 x 400/2 = 40 x 106 = 40 MV. 1.1.2 Traveling waves on transmission lines : Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University TRANSMISSION LINE WITH SURGE IMPEDANCE ‘Z’ The velocity of traveling waves on overhead lines is 300 m / μs and on cables is approximately 150 m / μs. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.1.3 Impulse voltage wave shape: Dr M A Panneerselvam, Professor, Anna University
Specification for impulse voltage: ( AS PER INDIAN STANDARDS ) t1 Time to Front 1.2 s t2 Time to Tail 50 s Vp Peak voltage Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Tolerances allowed: For Front time, t1 ± 30% For Tail time, t2 ± 20% Oscillations around the peak ,Vp, ± 5 % Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.1.4 Types of impulse voltages : FULL IMPULSE CHOPPED IMPULSE FRONT OF WAVE IMPULSE Dr M A Panneerselvam, Professor, Anna University
1.2 INTERNAL OVERVOLTAGES (SWITCHING SURGES) 1.2.1 Reasons for switching surge voltages: Sudden opening of a line Sudden closing of a line Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Connection of inductance / Capacitance Sudden connection and removal of loads , etc. Any sudden disturbance taking place in a transmission line will cause switching surge . Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University For the range of values of the inductance and capacitance of overhead lines the frequency of the switching surges are generally in the range of kc/s and they exist for a duration of milliseconds. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.2.2 Switching surges on transmission lines: Ex.1 Opening of an unloaded OH line: Simply opening of an unloaded line transmission line may result in switching surge as shown in the fig. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Assume the switch ‘AB’ is opened Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University at time, t = 0, when the AC voltage is at its peak. During the next half cycle the voltage at terminal ‘A’ changes to negative peak of AC voltage , wheras the voltage at terminal ‘B’ remains at positive peak. Hence the voltage across the Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University B 2 Vp t = 0 A switch becomes 2 Vp .If the switch is unable withstand this voltage it breaks down and a switching surge Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University of magnitude 2 Vp travels on the line. At the terminations it gets reflected and refracted and builds up further to a higher level. Another example for generation of switching surge is the operation of a circuit breaker as shown in the next figure. Dr M A Panneerselvam, Professor, Anna University
Ex.2 Operation of a circuit breaker: RE STRIKING VOLTAGE 2Vp RECOVERY VOLTAGE ARC VOLTAGE FAULT CURRENT Dr M A Panneerselvam, Professor, Anna University
RESTRIKING VOLTAGE ACROSS A CIRCUIT BREAKER The maximum voltage across the breaker contacts = 2 Vp =2√2 VRMS The voltage after reflection and refraction at the terminals of the transmission line may reach a maximum of 5 t0 6 times the system voltage. Dr M A Panneerselvam, Professor, Anna University
1.3 PF OVERVOLTAGES DUE TO LOCAL SYSTEM FAULTS 1.3.1 Local faults in the systems are : Line to ground fault (3) Double line to ground fault (3) Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Double line fault (3) Triple line fault (1) Triple line to ground fault (1) Of the total 11 faults above, a double line to ground fault is more dangerous with respect to Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University overvoltages developed. Coefficient of earthing (COE) of a system is defined as the ratio of the Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University voltage of the healthy phase to ground to that of the line voltage in the event of a double line to ground fault. The value of COE varies between 1/√3 to 1.0(i.e., 0.59 to 1.0) depending upon the neutral impedance. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University When the value of ‘COE” is less than 70 % ,the system is said to be an effectively or solidly earthed system. When the ‘COE’ is more than 70 %, the system is said to be a non effectively earthed system. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Systems above 230 kV are generally effectively earthed. For System ratings above 230 kV the Switching surge voltages attain very high values and become more severe than impulse voltages. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Hence,the insulation design (i.e., insulation coordination) is based on switching surges rather than impulse voltages. 1.4 DC OVERVOLTAGES During the past 2 to 3 decades HVDC systems came into existence. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University HVDC systems have converters and inverters at the sending end and receiving end respectively employing thyristers. Switching surges are produced due to thyristers’ operation. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.5 TRAVELLING WAVES ON TRANSMISSION LINES: LONG TRANSMISSION LINE Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Assuming a lossless line (i.e., R=0,G=0) when the wave has travelled a distance ‘x’ after a time ‘t’, the electrostatic flux associated with the voltage wave is, q = CxV ------------(1) The current is given by the rate of charge flow , I = dq/dt = VC dx/dt---(2) Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Here dx/dt is the velocity of the travelling wave represented by, I = VC v -------------------(3) Similarly, the electromagnetic flux associated with the current wave, Φ = Lx I ---------------------(4) Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University The voltage is the rate of change of flux linkages, V = LI dx/dt = LIv --------------------(5) Dividing Eqn.(5) by (3), V/I= LIv/VCv = LI/CV V2/I2=L/C. i.e.,V/I=Z=√(L/C) --------(6) Next multiplying Eqn. (5) and (6), Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University VI = VCv x LIv = VILC v2 v2 = VI / VILC = 1/ (LC) v = 1 / √ (LC) -----------------------(7) Substituting the values for ‘L’ and ‘C’ of overhead lines we get, v = 1 / ((2x10-7 ln d/r x 2πε/(ln d/r)) = 3x108 m/sec. = 300 m/μ sec. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University which is the velocity of light. Hence, travelling waves travel with velocity of light on overhead lines. In cables, since εr >1, the velocity of travelling waves is lesser than overhead lines and is approximately 150 m/ μ sec. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Open ended line: Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University The voltage wave and current waves travelling towards the open end are related by, V / I = Z. Since the current at the open end is zero, the electromagnetic energy vanishes and is transformed into electrostatic energy: Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University i.e.,½ L(dx) I2 = ½ C(dx)e2 i.e.,(e/I)2 = L/C = Z2 . i.e., e=IZ=V. Hence, the potential at the open end is raised by ‘V’ volts and becomes V+V=2V. The incident wave = V, the reflected wave = V and the refracted (transmitted) wave = V+V= 2V Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University The refracted(transmitted) wave = Incident wave + Reflected wave. For an open ended line the reflection coefficient for voltage wave is +1 and the reflection coefficient for current wave is -1. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University VOLTAGE AND CURRENT WAVES OPEN ENDED LINE Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Short circuited line: For a short circuited line , the reflection coefficient for voltage wave is -1 and for current wave is +1. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University VOLTAGE AND CURRENT WAVES FOR SHORT CIRCUITED LINE Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Reflection and transmission coefficients for line terminated with impedance ‘R’ : Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Let the incident voltage and current waves be V and I, the reflected waves V’ and I’ and the transmitted waves V’’ and I’’. It is seen in the earlier sections that whatever be the value of terminating impedance,whether it is open or short circuited , either the current wave or Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University voltage wave is reflected back with negative sign, i.e., I’ = - V’/Z I=V/Z , I’=-V’/Z and I’’=V’’/ R. Since I’’=I+I’ and V’’= V+V’, we have, V’’/R = V/Z – V’/Z =V/Z – (V’’-V)/Z = 2V/Z – V’’/Z. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University V’’(1/R +1/Z)= V’’(R+Z)/RZ = 2V/Z V’’= V 2R/(R+Z) and I’’ = I 2Z/(R+Z) Hence , the refraction coefficients for voltage and current waves for open ended line respectively are: Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 2R / R+Z and 2Z / R+Z Similarly, the reflection coefficients for voltage and current for open ended line are respectively: (R-Z) / (R+Z) and - (R-Z) / (R+Z) Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Bewley’s Lattice Diagram: Dr M A Panneerselvam, Professor, Anna University
1.6 COMPARISON OF DIFFERENT TYPES OF OVERVOLTAGES 1 Lightning overvoltage : Lightning overvoltage is an external overvoltage as it is independent of the system parameters. It injects Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University current on to the transmission lines producing a voltage ranging from kV to MV . It has a wave shape of 1.2/50 μs and exists for a period of microseconds. The very high rate of rise of the impulse voltage striking the line is Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University equivalent to applying a voltage at very high frequency of the order of Mc/s. 2 Switching Surge : Switching surges are internal overvoltages as they are dependant upon the system Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University parameters (i.e., the voltage level, the values of R,L and C of the line). Their magnitudes range from 4 to 6 times the system voltage and they have damped oscillations of kc/s and exist for durations of milliseconds. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 3 Power frequency overvoltage : Due to local system faults such as ‘double line to ground faults’ the voltage of the healthy phase to ground will increase from phase voltage to line voltage depending upon the neural earthing impedance of the system. Dr M A Panneerselvam, Professor, Anna University
1.7 PROTECTION OF TRANSMISSION LINES AGAINST OVERVOLTAGES 1.5.0 Transmission lines are protected from lightning and switching surges by adopting the following methods :
Dr M A Panneerselvam, Professor, Anna University 1.Use of shielding wires 2. Reduction of tower footing resistance and use of counter poises 3.Using spark gaps ( sphere gap and horn gap ) 4.Connection of surge absorbers Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 5.Overhead lines connected to cables 6.Using protector tubes ( Expulsion Arresters ) 7.Using non-linear resister lightning arresters ( Valve Arresters) Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.7.1 Shielding wires: Shielding wires are ground wires connected above phase wires. The shielding angle should be less than 300 for effective protection of the transmission line against lightning stroke. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University SHIELDING ARRANGEMENT OF TRANSMISSION LINES Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.7.2 Reduction of tower footing resistance and use of counter poises : ARRANGEMENT SHOWING COUNTER POISES Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.7.3 Spark gaps : When Spark gaps are connected between phase to ground the gaps breakdown due to lightning overvoltage and lightning energy is diverted to ground through gaps. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Spark gaps are of the following types: Rod gaps Horn gaps Sphere gaps Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Sphere gaps are generally preferred as they have , Consistency in breakdown Less affected by humidity and other atmospheric conditions. Lesser impulse ratio Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University ROD GAP HORN GAP Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University IMPULSE HORN GAP SPHERE GAP Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University IMPULSE RATIO: Impulse ratio is defined as the ratio of peak impulse breakdown voltage to that of peak power frequency breakdown voltage of a given insulation. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Sphere gaps have impulse ratio around unity and hence they offer better protection against lightning overvoltages and helps in reduction of insulation of equipment connected in the system. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.7.4 Surge absorbers : Power loss takes place due to corona at excess overvoltages and helps in the reduction of such overvoltages. In addition the front time of the impulse voltage is increased resulting in reduced stress on the equipment. Dr M A Panneerselvam, Professor, Anna University
IMPULSE VOLTAGE AT DIFFERENT TIMES ON A TRANSMISSION LINE Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University Connection of resistance in series and Ferranti’s surge absorber : FERRANTI’S SURGE ABSORBER Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.7.5 Connection of UG cable to overhead line : The reflection coefficient, R = ZC – ZL / ZC + ZL . Taking ZL as 400 ohms and Zc as 60 ohms Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University The reflection coefficient , R = 60 – 400 / 60 + 400 = -340 / 460 = -0.739 The voltage transmitted into the cable 1.0 - 0.739 = 0.261 pu = 26 % of the incident voltage. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.7.6 Protector tubes ( Expulsion Arresters ) : Spark gaps have the following draw backs: They offer protection against overvoltages by diverting the lightning energy to ground but Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University they cannot arrest the power follow currents. They are always used as secondary protection except for very small system voltages. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University The drawbacks of expulsion arrestors are: They require certain minimum energy to produce gas to quench the arc. For very high current values they may explode due to very high pressure of gas generated. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University EXPULSION ARRESTER Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University 1.7.7 Non linear resister lightning arresters( Valve Arresters ) : These arresters act as valve in the sense that they offer very low impedance for lightning voltages and offer very high impedance for power frequency currents. Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University VALVE ARRESTER Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University CHARACTERISTIC CURVES FOR VALVE ARRESTORS VOLTAGE TIME CHARACTERISTICS RESIDUAL VOLTAGE Dr M A Panneerselvam, Professor, Anna University
REPRESENTATIVE PHOTOGRAPHS OF LIGHTNING DISCHARGE Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University
Dr M A Panneerselvam, Professor, Anna University